Overview
Describes the power requirements, heat dissipation for the fan tray, line cards, and the supervisor modules of Cisco C9610 switches.
These tables provide the power and heat dissipation data. Unless otherwise noted, the information in the tables is measured under fully loaded conditions (with transceivers installed).
| PID |
AC-input power in Watts |
DC-output in Watts |
Current @ 90V |
Current @ 120V |
Current @ 180V |
Current @ 240V |
Heat Diss. in BTU / hr. |
|---|---|---|---|---|---|---|---|
| C9610-FAN |
1111 |
1000 |
12.4 |
9.3 |
6.2 |
4.7 |
3791 |
| PID |
AC-input power in Watts |
DC-output in Watts (Power requested) |
Current @ 90V |
Current @ 120V |
Current @ 180V |
Current @ 240V |
Heat Diss. in BTU / hr. |
|---|---|---|---|---|---|---|---|
| C9610-LC-40YL4CD |
466 |
420 |
5.2 |
3.9 |
2.6 |
1.95 |
1590 |
| C9610-LC-32CD |
495 |
450 |
5.6 |
4.2 |
2.8 |
2.1 |
1689 |
| C9600-LC-40YL4CD |
466 |
420 |
5.2 |
3.9 |
2.6 |
1.95 |
1590 |
| C9600-LC-48TX |
350 |
315 |
3.9 |
3.0 |
2.0 |
1.5 |
1195 |
| C9600X-LC-32CD |
495 |
450 |
5.6 |
4.2 |
2.8 |
2.1 |
1689 |
| C9600X-LC-56YL4C |
495 |
450 |
5.6 |
4.2 |
2.8 |
2.1 |
1689 |
| PID |
AC-input power in Watts |
DC-output in Watts (Power requested) |
Current @ 90V |
Current @ 120V |
Current @ 180V |
Current @ 240V |
Heat Diss. in BTU / hr. |
|---|---|---|---|---|---|---|---|
| C9610-SUP-3 |
2444 |
2200 |
27.15 |
20.37 |
13.58 |
10.18 |
8339 |
| C9610-SUP-3XL |
2444 |
2200 |
27.15 |
20.37 |
13.58 |
10.18 |
8339 |