System Specifications

Environmental Specifications

Environment

Specification

Temperature

Ambient operating temperature

32 to 104ºF (0 to 40ºC)

Ambient nonoperating

–40 to 158ºF (–40 to 70ºC)

Relative humidity

Operating

5 to 90 percent, non-condensing

Nonoperating

5 to 90 percent, non-condensing

Altitude

Operating

0 to 10,000 ft (0 to 3,048 meters)

Nonoperating

-1000 ft. to 30,000 ft (-305 to 9144 meters)

Switch Dimensions

The dimension of the N9348Y12C-SE1 switch are

Switch

Width

Depth

Height

Cisco N9348Y12C-SE1

17.3 inches (439.4mm)

18.09 inches (459.59mm)

1.72 inches (43.7mm)

Switch and Module Weights and Quantities

This section lists the switch and its components, their weights, and the quantity of each module that is shipped with the switch, by default.

Component

Weight per module

Quantity

Cisco N9348Y12C-SE1

1

Fan modules

Port-side intake (burgundy) NXA-SFAN-35CFM-PI

0.28 lb (0.13 kg)

4

Port-side exhaust (blue) (NXA-SFAN-35CFM-PE)

0.28 lb (0.13 kg)

Power supply modules

650W AC port-side intake (burgundy) (NXA-PAC-650W-PI)

2.42 lb (1.1 kg)

2

650W AC port-side exhaust (blue) (NXA-PAC-650W-PE)

2.42 lb (1.1 kg)

930W DC port-side intake (burgundy) NXA-PDC-930W-PI

2.42 lb (1.1 kg)

930W DC port-side exhaust (blue) NXA-PDC-930W-PE

2.42 lb (1.1 kg)

1200W HVAC dual-direction (white) (N9K-PUV-1200W)

2.42 lb (1.1 kg)

Switch Power Input Requirements

This table lists the typical amount of power that the switch consumes. It also lists the maximum amount of power that you must provision for the switch and power supply for peak conditions.

Switch

Typical Power Consumption (AC or DC)

Maximum Power Consumption (AC or DC)

Heat Dissipation Requirement

Cisco N9348Y12C-SE1

275 W

490 W

1,774 BTU/hr


Note


Some power supplies have capabilities that are greater than the maximum power requirements for a switch. To determine the power consumption characteristics for the switch, use the typical and maximum requirements that are listed here.


Power Specifications

By default, the N9348Y12C-SE1 switch is powered with two 650W power supply units (PSUs) in 1+1 mode.

Power specifications include the specifications for each type of power supply module.

350W AC Power Supply Specifications

These specifications apply to the following power supplies:

  • NXA-PAC-350W-PE

  • NXA-PAC-350W-PI

Characteristic Specification
AC input voltage 100 to 120 VAC, 200 to 240 VAC
AC input frequency Nominal range: 50 to 60 Hz
Maximum AC input current

4 A at 100 to 120 VAC

2A at 200 to 240 VAC

Maximum output power per power supply 350 W
Maximum inrush current 33 A (sub-cycle duration)
Efficiency rating Climate Savers Platinum Efficiency (80Plus Platinum certified)
Form factor RSP1

350W PHV Power Supply Specifications

These specifications apply to the following power supplies:

  • NXA-PHV-350W-PE

  • NXA-PHV-350W-PI

Characteristic Specification
Input voltage

240 to 380 VDC

100 to 277 VAC

Input frequency Nominal range: 50 to 60 Hz
Maximum output power per power supply 350 W
Efficiency rating Climate Savers Platinum Efficiency (80Plus Platinum certified)
Form factor RSP1

440W DC Power Supply Specifications

These specifications apply to

  • NXA-PDC-440W-PE

  • NXA-PDC-440W-PI

Characteristic Specification
Maximum output power 440 W
Input current 16 -8 A
DC input voltage Nominal Range: -48 to -60 VDC

Power Cable Specifications

These sections show the power cables that you can order and use with this switch.

DC Power Cable Specifications

This section lists the details and illustration of NXA-PDC-440W-PE/PI.

Part ID Number

Description

Photo

NXA-PDC-440W-PE/PI

The 440W DC power supply (NXA-PDC-440W-PE/PI) is shipped with wiring instructions along with these parts: LUG,FAST, UNIN, #8AWG, RED; LUG, FORK, INSL,16-14G, # 6, NY,BLUwNARROW TONGUE; LUG, RING, 16-14AWG, #6


NXA-PDC-440W-PE/PI

AC Power Cable Specifications

This section lists the power cables used with the AC power supply modules.

Power type

Power cord part number

Cord set description

CAB-C13-C14-2M

Power cord jumper, C13 to C14 connectors, 6.6 feet (2.0 m)

CAB-C13-C14-AC

Power cord jumper, C13 to C14 (recessed receptacle), 10 A, 9.8 feet (3 m)

CAB-C13-CBN

Cabinet jumper power cord, 250V AC, 10 A, C14-C13 connectors, 2.3 feet (0.7 m)

Argentina

CAB-250V-10A-AR

250 V , 10 A, 8.2 feet (2.5 m)

Australia

CAB-9K10A-AU

250 V AC, 10 A, 3112 plug, 8.2 feet (2.5 m)

Brazil

CAB-250V-10A-BR

250 V , 10 A, 6.9 feet (2.1 m)

European Union

CAB-9K10A-EU

250 V AC, 10 A, CEE 7/7 plug, 8.2 feet (2.5 m)

India

CAB-IND-10A

10 A, 8.2 feet (2.5 m)

Israel

CAB-250V-10A-IS

250 V , 10 A, 8.2 feet (2.5 m)

Italy

CAB-9K10A-IT

250 V AC, 10 A, CEI 23-16/VII plug, 8.2 feet (2.5 m)

North America

CAB-9K12A-NA

125 V AC, 13 A, NEMA 5-15 plug, 8.2 feet (2.5 m)

North America

CAB-AC-L620-C13

NEMA L6-20-C13, 6.6 feet (2.0 m)

North America

CAB-N5K6A-NA

200/240V , 6A, 8.2 feet (2.5 m)

Peoples Republic of China

CAB-250V-10A-CN

250 V , 10 A, 8.2 feet (2.5 m)

South Africa

CAB-250V-10A-ID

250 V , 10 A, 8.2 feet (2.5 m)

Switzerland

CAB-9K10A-SW

250 V AC, 10 A, MP232 plug, 8.2 feet (2.5 m)

All except Argentina, Brazil, and Japan

NO-POWER-CORD

No power cord included with switch

Regulatory Standards Compliance Specifications

This table lists the regulatory standards compliance for the switch.
Table 1. Regulatory standards compliance: safety and EMC

Specification

Description

Regulatory compliance

Products should comply with CE Markings according to directives 2004/108/EC and 2006/95/EC.

Safety

  • CAN/CSA-C22.2 No. 60950-1 Second Edition

  • CAN/CSA-C22.2 No. 62368-1-19 Third Edition

  • ANSI/UL 60950-1 Second edition

  • IEC 62368-1

  • EN 62368-1

  • AS/NZS 62368-1

  • GB4943

  • UL 62368-1

EMC: Emissions

  • 47CFR Part 15 (CFR 47) Class A

  • AS/NZS CISPR22 Class A

  • CISPR22 Class A

  • EN55022 Class A

  • ICES003 Class A

  • VCCI Class A

  • EN61000-3-2 and EN61000-3-3

  • KN22 Class A

  • CNS13438 Class A

EMC: Immunity

  • EN55024

  • CISPR24

  • EN300386

  • KN 61000-4 series

RoHS

The product is RoH-6 compliant with exceptions for leaded-ball grid-array (BGA) balls and lead press-fit connectors.