Associate the temperature alarms with the relay

Want to summarize with AI?

Log in

Configure temperature alarms to ensure critical temperature notifications are routed via relay, SNMP, or syslog.


Follow this procedure to associate temperature alarms with a relay to ensure that critical temperature notifications are routed appropriately.

Procedure

1.

Use the configure terminal command to enter global configuration mode.

Example:

Switch# configure terminal
2.

Use the alarm facility temperature { primary | secondary } relay major command to link either the primary or secondary temperature alarm to the major relay.

Example:

Switch(config)# alarm facility temperature primary relay major
3.

(Optional) Use the alarm facility temperature { primary | secondary } notifies command to send primary or secondary temperature alarm traps to an SNMP server.

Example:

Switch(config)# alarm facility temperature primary notifies
4.

(Optional) Use the alarm facility temperature { primary | secondary } syslog command to send primary or secondary temperature alarm traps to a syslog server.

Example:

Switch(config)# alarm facility temperature primary syslog
5.

(Optional) Use the no alarm facility temperature secondary command to turn off the secondary temperature alarm.

Example:

Switch(config)# no alarm facility temperature secondary
6.

Use the end command to exit to the privileged EXEC mode.

Example:

Switch# end
7.

Use the show alarm settings command to confirm that temperature alarms are configured correctly.

Example:

Switch# show alarm settings