fltEquipmentFanDegraded
Fault Code
F0371
Description
[sensor_name]: Fan [Id] has asserted a predictive failure: reseat or replace fan [Id]
Explanation
This fault occurs when one or more fans in the fan module are not operational, but at least one fan is operational.
Recommended Action
If you see this fault, take the following actions:
-
Review the product specifications to determine the temperature operating range of the fan module.
-
Review the Cisco UCS Site Preparation Guide and ensure the fan module has adequate airflow, including front and back clearance
-
Verify that the airflow to the server is not blocked.
-
Verify that the site cooling system is operating properly.
-
Clean the installation site at regular intervals to avoid buildup of dust and debris. Dust and debris cause a system to overheat.
-
Replace the faulty fan modules.
Before installing or replacing this component, see the server-specific Installation and Service guide for prerequisites, safety recommendations, and warnings.
-
If the problem still persists, create a tech-support file and contact Cisco TAC.
Fault Details
Severity: warning
Cause: equipment-degraded
mibFaultCode: 371
mibFaultName:fltEquipmentFanDegraded
moClass: equipment:Fan
Type: equipment