Technical Specifications

This appendix contains the following topics:

Server Specifications

This appendix lists the physical, environmental, and power specifications for the server.

Physical Specifications

The following table lists the physical specifications for the server.

Table 1. Physical Specifications

Description

Specification

Height

1.7 in. (43.2 mm)

Width

16.9 in. (429.0 mm)

Depth (length)

Server only: 30 in. (762 mm)

Server with slide rail: 31.5 in (800.1 mm)

Weight

  • Maximum, fully configured with rail kit: 42.432 lb (19.25 kg)

  • Maximum, not configured, no rail kit: 22.32 lb (10.13 kg)

Environmental Specifications

As a Class A2 product, the server has the following environmental specifications.

Table 2. Environmental Specifications

Description

Specification

Temperature, Operating

Dry bulb temperature of 10°C to 35°C (50°F to 95°F)

Maximum temperature change of 20°C (36°F) per hour

(a temperature change within a specified period of time and not a rate of change)

Humidity condition: Uncontrolled, not to exceed 50% RH starting condition

Derate the maximum temperature by 1°C (33.8°F) per every 305 meters of altitude above 900m

Temperature, Extended Operating

5°C to 40°C (41°F to 104°F) with no direct sunlight

Humidity condition: Uncontrolled, not to exceed 50% RH starting condition

Derate the maximum temperature by 1°C (33.8°F) per every 305 meters of altitude above 900m

Temperature, non-operating

(when the server is stored or transported)

Dry bulb temperature of 40 °C to 65 °C (-40°F to 149 °F)

Humidity (RH), operating

10% to 90% and 28°C (82.4°F) maximum dew-point temperature, non-condensing environment

Minimum to be higher (more moisture) of -12 ˚C (10.4 ˚F) dew point or 8% relative humidity

Maximum to be 24 ˚C (75.2 ˚F) dew point or 90% relative humidity

Humidity (RH), non-operating

(when the server is stored or transported)

5% to 93% relative humidity, non-condensing, with a maximum wet bulb temperature of 28 °C across the 20 °C to 40 °C dry bulb range.

Altitude, operating

A maximum elevation of 3050 meters (10,006 feet)

Altitude, non-operating

(when the server is stored or transported)

An elevation of 0 to 12,000 meters (39,370 feet)

Maximum Operating Duration

Unlimited

Sound power level

Measure A-weighted per ISO7779 LwAd (Bels)

Operation at 73°F (23°C)

5.5

Sound pressure level

Measure A-weighted per ISO7779 LpAm (dBA)

Operation at 73°F (23°C)

40

Power Specifications


Note


Do not mix power supply types or wattages in the server. Both power supplies must be identical.

You can get more specific power information for your exact server configuration by using the Cisco UCS Power Calculator:

http://ucspowercalc.cisco.com

The power specifications for the supported power supply options are listed in the following sections.

1050 W V2 DC Power Supply

This section lists the specifications for each 1050 W DC power supply (Cisco part number UCSC-PSUV21050D-D). This power supply is Platinum rated.


Note


For the 80PLUS platinum certification documented in the following table, you can find test results at https://www.clearesult.com/80plus/.


Parameter

Specification

Input Connector

Molex 42820

Input Voltage Range (V rms)

-48

Maximum Allowable Input Voltage Range (V rms)

-40 to -72

Frequency Range (Hz)

NA

Maximum Allowable Frequency Range (Hz)

NA

Maximum Rated Output (W)

1050

Maximum Rated Standby Output (W)

36

Nominal Input Voltage (V rms)

-48

Nominal Input Current (A rms)

24

Maximum Input at Nominal Input Voltage (W)

1154

Maximum Input at Nominal Input Voltage (VA)

1154

Maximum Rated Efficiency (%)

Minimum rating required to achieve 80PLUS platinum certification.

91

Maximum Rated Power Factor

Minimum rating required to achieve 80PLUS platinum certification.

NA

Maximum Inrush Current (peak A)

15

Maximum Inrush Current (ms)

0.2

Maximum Ride-Through Time

This is the time output voltage remains within regulation limits at 100% load, during input voltage dropout

5

1200 W AC Power Supply

This section lists the specifications for each 1050 W AC power supply (Cisco part number UCSC-PSU1-1200W-D).

Table 3. 1200 W AC Specifications

Description

Specification

AC input voltage

Range: 100–230 VAC

AC input frequency

Range: 50 to 60Hz

Maximum AC input current

12.97 A at 100 VAC

Maximum input volt-amperes

1345 VA at 208 VAC

Maximum inrush current

20 A

Maximum hold-up time

12 ms at 1200 W

Maximum output power per PSU

1100 W at 100–120 VAC

1200 W at 208–230 VAC

Power supply output voltage

12 VDC

Power supply standby voltage

12 VDC

Efficiency rating

Climate Savers Platinum Efficiency (80Plus Titanium certified)

Form factor

RSP2

Input connector

IEC320 C14

1600 W AC Power Supply

This section lists the specifications for each 1600 W AC power supply (Cisco part number UCSC-PSU1-1600W-D). This power supply is Platinum rated.


Note


For the 80PLUS platinum certification documented in the following table, you can find test results at https://www.clearesult.com/80plus/.


Parameter

Specification

Input Connector

IEC320 C14

Input Voltage Range (V rms)

200 to 240

Maximum Allowable Input Voltage Range (V rms)

180 to 264

Frequency Range (Hz)

50 to 60

Maximum Allowable Frequency Range (Hz)

47 to 63

Maximum Rated Output (W)

Limited to 800W when operating at low-line input voltage, 100-127 V

1600

Maximum Rated Standby Output (W)

36

Nominal Input Voltage (V rms)

100

120

208

230

Nominal Input Current (A rms)

NA

NA

8.8

7.9

Maximum Input at Nominal Input Voltage (W)

NA

NA

1778

1758

Maximum Input at Nominal Input Voltage (VA)

NA

NA

1833

1813

Maximum Rated Efficiency (%)

Minimum rating required to achieve 80PLUS platinum certification.

NA

NA

90

91

Maximum Rated Power Factor

Minimum rating required to achieve 80PLUS platinum certification.

NA

NA

0.97

0.97

Maximum Inrush Current (peak A)

30

Maximum Inrush Current (ms)

0.2

Maximum Ride-Through Time

The time that the output voltage remains within regulation limits at 100% load, during input voltage dropout

12

2300 W AC Power Supply

This section lists the specifications for each 2300 W AC power supply (Cisco part number UCSC-PSU1-2300W-D). This power supply is Titanium rated.

Parameter

Specification

Input Connector

IEC320 C20

Input Voltage Range (V rms)

100 to 240

Maximum Allowable Input Voltage Range (V rms)

90 to 264

Frequency Range (Hz)

50 to 60

Maximum Allowable Frequency Range (Hz)

47 to 63

Maximum Rated Output (W)

Limited to 800W when operating at low-line input voltage, 100-127 V

2300

Maximum Rated Standby Output (W)

36

Nominal Input Voltage (V rms)

100

120

208

230

Nominal Input Current (A rms)

13

11

12

10.8

Maximum Input at Nominal Input Voltage (W)

1338

1330

2490

2480

Maximum Input at Nominal Input Voltage (VA)

1351

1343

2515

2505

Maximum Rated Efficiency (%)

Minimum rating required to achieve 80PLUS platinum certification.

92

92

93

93

Maximum Rated Power Factor

Minimum rating required to achieve 80PLUS platinum certification.

0.99

0.99

0.97

0.97

Maximum Inrush Current (peak A)

30

Maximum Inrush Current (ms)

0.2

Maximum Ride-Through Time

Time output voltage remains within regulation limits at 100% load, during input voltage dropout

12

Power Cord Specifications

Each power supply in the server has a power cord. Standard power cords or jumper power cords are available for connection to the server. The shorter jumper power cords, for use in racks, are available as an optional alternative to the standard power cords.


Note


Only the approved power cords or jumper power cords are supported. Please refer to the server specification sheet for lists of approved power cords.