The documentation set for this product strives to use bias-free language. For the purposes of this documentation set, bias-free is defined as language that does not imply discrimination based on age, disability, gender, racial identity, ethnic identity, sexual orientation, socioeconomic status, and intersectionality. Exceptions may be present in the documentation due to language that is hardcoded in the user interfaces of the product software, language used based on RFP documentation, or language that is used by a referenced third-party product. Learn more about how Cisco is using Inclusive Language.
Riding heat sink OSFP 800G provides connectivity for Network Interface Cards (NIC) and liquid cooled switches and routers used in AI front-end and back-end networks with reaches up to 500m.
Cisco® OSFP Riding Heat Sink (RHS) 800G transceiver modules provide 800 Gigabit Ethernet (GE), 2x 400GE, 4x 200GE, and 8x 100GE connectivity options, complying with the Octal Small Form Factor Pluggable (OSFP) Multi Source Agreement (MSA) for pluggable transceivers. These modules are primarily used in Network Interface Cards (NIC) with OSFP-RHS ports and can also be used in liquid cooled switches and routers. Cisco OSFP 800G RHS modules are used in AI applications for both front-end and back-end networks as well as other data center applications. OSFP VR8 reach up to 50m over parallel Multi-Mode Fiber (MMF) and OSFP DR8 reache up to 500m over parallel Single-Mode Fiber (SMF). The modules comply with the OSFP MSA configuration with Riding Heat Sink. They meet the IEEE 800GE requirements along with the flexibility of 400GE, 200GE, and 100GE connectivity options for data centers, high-performance computing networks, enterprise core and distribution layers, and service provider applications.
Table 1. Features and benefits
| Feature |
Benefit |
| Hot-swappable |
I/O device that plugs into an 800GE OSFP-RHS port. |
| Interoperable |
Interoperable with other IEEE-compliant 800GE, 400GE, 200GE, and 100GE interfaces where applicable. |
| Certified on Cisco platform |
Certified and tested on Cisco OSFP-RHS 800G host platforms for superior performance, quality, and reliability. |
| Compatible with IEEE 802.3 |
High-speed electrical and optical compliance with IEEE 802.3. |
| Compatible with MSA |
Compliance with OSFP MSA |
| Breakout capability |
Modules have the capability to interface to multiple 100GE, 200GE, and 400GE modules, providing higher port density for 100GE, 200GE, and 400GE interfaces. |
| OIF CMIS Compliant |
Modules are compliant to CMIS 5.3. |
| Versatile Diagnostic Monitoring (VDM) |
Module firmware can be upgraded to support Versatile Diagnostic Monitoring (VDM). |
Table 2. Cisco OSFP-RHS 800G portfolio
| Product ID |
Description |
| OSFPR-800G-VR8 |
OSFP-RHS (Riding Heat Sink) Transceiver, 800GBASE-VR8, Dual MPO-12 APC, 30/50m (OM3/OM4) parallel MMF (Multimode Fiber) |
| OSFPR-800G-DR8 |
OSFP-RHS (Riding Heat Sink) Transceiver, 800GBASE-DR8, Dual MPO-12, 500m parallel SMF (Single-Mode Fiber) |
OSFPR-800G-VR8
The Cisco OSFPR-800G-VR8 module supports 800GBASE-VR8 as well as 2x 400GBASE-VR4, 4x 200GBASE-VR2, and 8x 100GBASE-VR1 breakouts for links up to 50m (OM4/5). The module has eight pairs of multi-mode fiber with dual MPO-12 APC connectors. It is compliant with IEEE 802.3 800GBASE-VR8 and OSFP MSA module requirements with Riding Heat Sink. Optical signals are carried over eight pairs of parallel lanes, with one wavelength per lane. The optical interface can interoperate with any IEEE-compliant module regardless of the form factor. Forward Error Correction (FEC) is performed on the host platform. The OSFP-800G-VR8 module is field firmware upgradeable, complying with CMIS 5.3 firmware upgradability process. The module is shipped with firmware that does not support VDM but can be upgraded.
OSFPR-800G-DR8

OSFPR-800G-DR8
The Cisco OSFPR-800G-DR8 module (Figure 1) supports 800GBASE-DR8 as well as 2x 400GBASE-DR4, 4x 200GBASE-DR2, and 8x 100GBASE-DR1 breakouts for links up to 500m. The module has eight pairs of single-mode fiber with dual MPO-12 APC connectors. It is compliant with IEEE 802.3 800GBASE-DR8 and OSFP MSA module requirements for ports designed for OSFP Riding Heat Sink. Optical signals are carried over eight pairs of parallel lanes, with one wavelength per lane. The optical interface can interoperate with any IEEE-compliant module regardless of the form factor. Forward Error Correction (FEC) is performed on the host platform. The OSFPR- 800G-DR8 module is field firmware upgradeable, complying with CMIS 5.3 firmware upgradability process. The module is shipped with firmware that does not support VDM but can be upgraded.
Table 3. OSFP-RHS port and cabling specifications
| Cisco 800G OSFP |
Nominal wavelength (nm) |
Cable type |
Core size (microns) |
Modal bandwidth |
Cable distance |
Pull tab color |
| OSFPR-800G-VR8 |
850 |
MMF |
50 |
2000 (OM3) 4700 (OM4) 4700 (OM5) |
30m (OM3) 50m (OM4/5) |
Purple |
| OSFPR-800G-DR8 |
1310 |
SMF |
G.652 |
|
500m |
Orange |
Cisco OSFP-RHS 800G modules are supported on Cisco switches and routers. For more details, refer to the Cisco Transceiver Modules Compatibility Matrix.
Table 4. Electrical specifications
| Product |
Description |
Nominal data rate |
High-speed electrical |
Link meter |
| OSFPR-800G-VR8 |
OSFP-RHS (Riding Heat Sink) Transceiver, 800GBASE-VR8, Dual MPO-12, 30/50m (OM3/OM4) parallel MMF |
800GE |
800GAUI-8 |
30m (OM3) 50m (OM4/5) |
| OSFPR-800G-DR8 |
OSFP-RHS (Riding Heat Sink) Transceiver, 800GBASE-DR8, Dual MPO-12, 500m parallel SMF |
800GE |
800GAUI-8 |
500m |
Table 5. Optical specifications
| Product |
Description |
Average transmit power per lane (dBm) min |
Average transmit power per lane (dBm) max |
Average receive power per lane (dBm) min1 |
Average receive power per lane (dBm) max |
Maximum supported insertion loss (IL) (dB) |
Wavelength h (nm) |
Pre-FEC |
| OSFPR- 800G-VR8 |
OSFP-RHS (Riding Heat Sink) Transceiver, 800GBASE-VR8, Dual MPO-12, 30/50m (OM3/ OM4) parallel MMF |
‒4.6 |
4 |
‒6.3 |
4 |
1.6 (OM3) 1.7 (OM4/5) |
842‒948 |
2.4x10-4 |
| OSFPR- 800G-DR8 |
OSFP-RHS (Riding Heat Sink) Transceiver with Integrated Heat Sink, 800GBASE- DR8, Dual MPO- 12, 500m parallel SMF |
‒2.9 |
4 |
‒5.9 |
4 |
3 |
1310 |
2.4x10-4 |
1 Average receive power per lane (min.) is informative and not the principal indicator of signal strength. A received power below this value cannot be compliant; however, a value above this does not ensure compliance.
Table 6. Mechanical specifications
| Specification |
Value |
| Module dimension with pull tab |
(H x W x D) 13 x 22.58 x 116 mm (0.51 x 0.89 x 4.57 in.) max |
| Module weight (max) |
100 g (3.5 oz) |
| Module operation temperature |
0° to 70°C (32° to 158°F) |
| Storage temperature |
-40 to 85°C (-40° to 185°F) |
Table 7. Ordering information
| Part ID |
Product description |
| OSFPR-800G-VR8 |
OSFP-RHS (Riding Heat Sink) Transceiver, 800GBASE-VR8, Dual MPO-12, 30/50m (OM3/OM4) parallel MMF |
| OSFPR-800G-DR8 |
OSFP-RHS (Riding Heat Sink) Transceiver, 800GBASE-DR8,2x MPO-12, 500m parallel SMF |
Regulatory and standards compliance
Standards
● OSFP MSA OSFP Octal Small Form Factor Pluggable Module, Rev 5.1, specification
● GR-20-CORE: Generic Requirements for Optical Fiber and Optical Fiber Cable
● GR-326-CORE: Generic Requirements for Single-Mode Optical Connectors and Jumper Assemblies
● GR-468-CORE: Generic Requirements for Optoelectronic Devices Used in Telecommunications Equipment
● GR-1435-CORE: Generic Requirements for Multifiber Optical Connectors
● Common Management Specification (CMIS) Rev 5.3
● IEEE Std 802.3
● IEEE 802.3ck
● IEEE 802.3df
Safety
● Laser Class 1 21CFR-1040 LN#50
● Laser Class 1 IEC60825-1
● Compliance with North American (FCC/ICES), European (CENELEC), Japanese (VCCI), and Telcordia NEBS standards
● GR-1089 EMC and Electrical Safety – Generic Criteria for Network Telecommunications Equipment
● EMI compliance with FCC Part 15 (30 MHz to 40 GHz) and CISPR32/CISPR22 (30 to 6000 MHz)
● RFI compliance with EN/IEC 61000-4-3 and GR-1089-CORE (10kHz to 10 GHz)
● ESD compliance with EN/IEC 61000-4-2 and GR-1089
● Certification to IEC/EN 60825-1 +A2
● RoHS 6 compliance
Table 8. Laser class for OSFP-RHS (Riding Heat Sink) modules
| Part ID |
Laser class |
| OSFPR-800G-VR8 |
1 |
| OSFPR-800G-DR8 |
1 |
Standard warranty: 5 years. Expedited replacement available via a Cisco Smart Net Total Care® Service support contract.
Information about Cisco’s environmental, social and governance (ESG) initiatives and performance is provided in Cisco’s CSR and sustainability reporting.
Table 9. Cisco Environmental Sustainability Information
| Sustainability topic |
Reference |
|
| General |
Information on product-material-content laws and regulations |
|
| Information on electronic waste laws and regulations, including our products, batteries, and packaging |
||
| Information on product takeback and reuse program |
||
| Sustainability inquiries |
Contact: csr_inquiries@cisco.com |
|
| Material |
Product packaging weight and materials |
Contact: environment@cisco.com |
Flexible payment solutions to help you achieve your objectives
Cisco Capital® makes it easier to get the right technology to achieve your objectives, enable business transformation and help you stay competitive. We can help you reduce the total cost of ownership, conserve capital, and accelerate growth. In more than 100 countries, our flexible payment solutions can help you acquire hardware, software, services and complementary third-party equipment in easy, predictable payments. Learn more.
For more information about Cisco 800G OSFP-RHS transceiver module compatibility and support, please refer to the Cisco Transceiver Modules Compatibility Matrix.