Overview

Overview

This switch chassis includes:

  • Supervisor modules (one or two)—one of these types in slots SUP 1 and SUP 2 (Modules 27 and 28 in reports) (numbered from left to right on the chassis)

  • System controllers (two) (N9K-SC-A) in slots SC 1 and SC 2 (numbered from left to right on the chassis)

  • Line cards (up to four) in slots LC 1 to LC 4 (numbered from top to bottom on the chassis) supported by the same type of fabric module

    For compatibility information, please refer to the Line Card and Fabric Module Compatibility data sheets.


    Note


    Do not mix ACI-mode line cards with NX-OS mode line cards in the same switch.


  • Fabric modules in slots FM 1 to FM 6 (numbered from left to right on the chassis) are referred to as slot 21 to slot 26 in the system report, such as show modules CLI output.

    See the table for the required fabric module types and quantities required for maximum bandwidth.

    Table 1. Supported Fabric Modules and Line Cards

    Fabric Module

    Fabric Modules Required for Maximum Bandwidth

    Supported Line Cards

    N9K-C9504-FM

    3

    N9K-X9536PQ

    N9K-X9564PX

    N9K-X9564TX

    4

    N9K-X9408PC-CFP2

    N9K-X9432PQ

    N9K-X9464PX

    N9K-X9464TX

    N9K-X9464TX2

    6

    N9K-X9636PQ

    N9K-C9504-FM-E

    4

    4

    4

    4

    5

    5

    5

    4

    N9K-X97160YC-EX

    N9K-X9732C-EX

    N9K-X9732C-FX

    N9K-X9736C-EX

    N9K-X9736C-FX

    N9K-X9736C-FX3

    N9K-X9736Q-FX

    N9K-X9788TC-FX

    N9K-C9504-FM-S

    4

    N9K-X9432C-S

    N9K-C9504-FM-R

    6

    N9K-X9636C-RX

    N9K-X9636C-R

    N9K-X9636Q-R

    N9K-X96136YC-R

    N9K-C9504-FM-G1

    4

    4

    4

    4

    5

    5

    4

    4

    N9K-X9732C-EX

    N9K-X9736C-EX

    N9K-X97160YC-EX

    N9K-X9732C-FX

    N9K-X9736C-FX

    N9K-X9736C-FX3

    N9K-X9788TC-FX

    N9K-X9716D-GX

    1 Note that -G fabric modules require the N9K-C9504-FAN2 fan trays for operation.

    Note


    The fabric modules must be installed in specific slots. Installing fabric modules in other slots can cause a module mismatch condition.

    • For three modules, they must be in slots FM 2, FM 4, and FM 6.

    • For four modules, they must be in slots FM2, FM 3, FM 4, and FM 6.

    • For five modules, they can be in slots FM 1, FM 2, FM 3, FM 4, and FM 6. Alternatively, they can be in Slots FM 2, FM 3, FM 4, FM 5, and FM 6.

    • For five FM-E modules, they must be in Slots FM 2, FM 3, FM 4, FM 5, and FM 6.

    • For six modules, they must be in slots FM 1, FM 2, FM 3, FM 4, FM 5, and FM 6.

    • FM 5 (slot number 25) will only work with N9K-X9736C-FX, N9K-X9736Q-FX, and N9K-X9736C-FX3 and not with other line card modules.

    • All of the fabric modules in a modular switch must be of the same type.

    • When using FM-G fabric modules, any empty slots should be filled with FAN-PWR modules (N9K-C9504-FAN-PWR).

    • When using N9K-C9504-FM or N9K-C9504-FM-E fabric modules, any empty slots should be filled with N9K-C9504-FM-CV.

    • For more information about Line card and fabric module compatibility, see the Cisco Nexus 9500 Platform Line Cards and Fabric Modules Data Sheet.


  • Fan trays (three) (N9K-C9504-FAN) or (N9K-9504-FAN2) in slots FAN 1 to FAN 3 (numbered from left to right on the chassis)

  • Power supplies (up to two with the combined power mode, up to three with n+1 power redundancy mode, or up to four with the n+n power redundancy mode) in slots PS 1 to PS 4 (numbered from left to right on the chassis)

    • Cisco Nexus 9500 Series 3-kW AC power supply (N9K-PAC-3000W-B)

    • Cisco Nexus 9500 Series 3-kW Universal AC/DC power supply (N9K-PUV-3000W-B)

    • Cisco Nexus 9500 Series 3.15-kW Dual Input Universal AC/DC power supply (N9K-PUV2-3000W-B)

    • Cisco Nexus 9500 Series 3-kW (-48 V) DC power supply (N9K-PDC-3000W-B)


Note


The switch can be powered by a mix of AC, DC, and HVAC/HVDC power sources. All chassis slots are numbered from left to right or from top to bottom.


This figure shows the hardware features seen from the front of the chassis.

Hardware features on the front of the chassis

1

2 vertical mounting brackets used to mount the chassis onto a rack.

4

3-kW AC, Universal AC/DC, or DC power supplies (AC power supplies shown).

2

Line cards (up to 4).

5

Chassis LEDs.

3

Supervisor modules (1 or 2).

6

Use chassis handles to position the chassis on the bottom support rails. Do not use these handles for lifting the chassis.

This figure shows the hardware features seen from the rear of the chassis (one fan tray has been removed to show the fabric modules behind the fan trays).

Hardware features on the rear of the chassis

1

Fan trays (3—left fan tray not shown, to display the fabric modules located behind the fan trays)

4

Grounding pad

2

Fabric modules (up to 6 with up to 2 fabric modules behind each fan tray)

5

Use chassis handles to position the chassis on the bottom support rails. Do not use these handles for lifting the chassis.

3

System controllers (2)