Replacing a Fan Module During Operations
Before you begin
Before you can replace a fan module, ensure that these conditions exist:
-
The replacement fan module must have the same airflow direction as the other modules in the chassis.
If you must replace the fan module during operations and the above conditions are not met, leave the fan module that you need to replace in the chassis to preserve the designed airflow until you have the required module.
Procedure
|
Step 1 |
Remove the fan module that you need to replace.
|
||
|
Step 2 |
Use these steps to replace the missing fan module within two minutes to avoid a shutdown. |