Server Specifications
This appendix lists the physical, environmental, and power specifications for the server.
Physical Specifications
The table lists the physical specifications for the server versions.
Description |
Specification |
Height |
1.7 in. (43.2 mm) |
Width |
16.9 in. (429.0 mm) |
Depth (length) |
Server only: 29.5 in. (740.3 mm) Server with slide rail: 31.0 in (787.4 mm) |
Weight |
Maximum: 37.5 lb. (17.0 Kg) Minimum: 29.0 lb. (13.2 Kg) |
Environmental Specifications
The table lists the environmental requirements and specifications for the server.
Description |
Specification |
||
Temperature, Operating |
10° C to 35° C (50° F to 95° F) with no direct sunlight Derate the maximum temperature by 1°C per every 300 meters of altitude above sea level.
|
||
Temperature, non-operating (when the server is stored or transported) |
Below -40° C or above 65° C (below -40° F or above 149° F) Maximum rate of change (operating and non-operating) 20° C/hr (36° F/hr) |
||
Extended Operating Temperature |
5° C to 40° C (41° F to 104° F) with no direct sunlight Maximum allowable operating temperature derated 1° C/175 m (1° F/319 ft) above 950 m (3117 ft) 5° C to 45° C (41° F to 113° F) with no direct sunlight Maximum allowable operating temperature derated 1° C/125 m (1° F/228 ft) above 950 m (3117 ft) System performance may be impacted when operating in the extended operating temperature range. Operation above 40° C is limited to less than 1% of annual operating hours. Hardware configuration limits apply to extended operating temperature range. |
||
Humidity (RH), operating |
8 to 90% and 24° C (75o F) maximum dew-point temperature, non-condensing environment |
||
Humidity (RH), non-operating (when the server is stored or transported) |
Below 5% or above 95% and 33o C (91o F) maximum dew-point temperature, non-condensing environment |
||
Altitude, operating |
0 to 10,000 feet |
||
Altitude, non-operating (when the server is stored or transported) |
0 to 40,000 feet |
||
Sound power level Measure A-weighted per ISO7779 LwAd (Bels) Operation at 73°F (23°C) |
5.8 |
||
Sound pressure level Measure A-weighted per ISO7779 LpAm (dBA) Operation at 73°F (23°C) |
43 |
Network Virtual Interface Card Considerations
This section describes network virtual interface card (VIC) support and considerations for the Cisco Application Policy Infrastructure Controller (APIC) APIC G5 Server.
This supported virtual interface card must be inserted to PCIe Riser 01 for Cisco APIC G5 Server.
-
APIC-G5 Cisco VIC 15425
![]() Note |
50G optics are not supported on APIC-G5 Cisco VIC 15425. Only 10G and 25G variants are supported for connections from APIC-G5 Cisco VIC 15425 to a leaf switch. |
Please see the list of transceiver options: https://www.cisco.com/c/en/us/products/collateral/interfaces-modules/transceiver-modules/datasheet-c78-736950.html.
See CIMC NIC Mode and NIC Redundancy Settings for additional considerations and more information on NIC modes.
Power Specifications
System Workload Factor |
50% |
75% |
100% |
---|---|---|---|
Maximum Input Power |
409.91 W |
409.91 W |
409.91 W |
Input Power |
268.24 W |
338.59 W |
409.91 W |
Idle Input Power |
129.18 W |
129.18 W |
129.18 W |
Input Current |
1.13 A |
1.43 A |
1.72 A |
Air Flow |
31.69 cfm |
40 cfm |
48.43 cfm |
Cooling |
915.28 BTU/hr. |
1155.31 BTU/hr. |
1398.68 BTU/hr. |
System Workload Factor |
50% |
75% |
100% |
---|---|---|---|
Maximum Input Power |
429.85 W |
429.85 W |
429.85 W |
Input Power |
280.83 W |
355 W |
429.85 W |
Idle Input Power |
134.26 W |
134.26 W |
134.26 W |
Input Current |
1.19 A |
1.5 A |
1.81 A |
Air Flow |
33.18 cfm |
41.94 cfm |
50.78 cfm |
Cooling |
958.22 BTU/hr. |
1211.31 BTU/hr. |
1466.71 BTU/hr. |
![]() Note |
Do not mix power supply types or wattages in the server. Both power supplies must be identical. |
You can get more specific power information for your exact server configuration by using the Cisco UCS Power Calculator:
https://ucspowercalculator.cisco.com
The power specifications for the supported power supply options are listed in these sections.
1050 W DC Power Supply
This section lists the specifications for each 1050 W DC power supply (Cisco part number UCSC-
PSUV21050D-D).
Description |
Specification |
Input Connector |
Molex 42820 |
Input Voltage Range (V rms) |
-48 |
Maximum Allowable Input Voltage Range (V rms) |
-40 to -72 |
Frequency Range (Hz) |
NA |
Maximum Allowable Frequency Range (Hz) |
NA |
Maximum Rated Output (W) |
1050 W |
Maximum Rated Standby Output (W) |
36 |
Nominal Input Voltage (V rms) |
-48 |
Nominal Input Current (A rms) |
24 |
Maximum Input at Nominal Input Voltage (W) |
1154 |
Maximum Input at Nominal Input Voltage (VA) |
1154 |
Minimum Rated Efficiency (%)1 |
91 |
Minimum Rated Power Factor1 |
NA |
Maximum Inrush Current (A peak) |
15 |
Maximum Inrush Current (ms) |
0.2 |
Minimum Ride-Through Time (ms)2 |
5 |
![]() Note |
|
1200 W AC Power Supply
This section lists the specifications for each 1200 W AC Titanium Power Supply for C-series Rack Servers (Cisco part number UCSC-PSU1-1200W-D).
Description |
Specification |
Input Connector |
IEC320 C14 |
Input Voltage Range (V rms) |
100 to 240 |
Maximum Allowable Input Voltage Range (V rms) |
90 to 264 |
Frequency Range (Hz) |
50 to 60 |
Maximum Allowable Frequency Range (Hz) |
47 to 63 |
Maximum Rated Output (W)1 |
1100 W | 1200 W |
Maximum Rated Standby Output (W) |
48 |
Nominal Input Voltage (V rms) |
100 | 120 | 208 | 230 |
Nominal Input Current (A rms) |
12.97 | 10.62 | 6.47 | 5.84 |
Maximum Input at Nominal Input Voltage (W) |
1300 | 1264 | 1343 | 1340 |
Maximum Input at Nominal Input Voltage (VA) |
1300 | 1266 | 1345 | 1342 |
Minimum Rated Efficiency (%)2 |
90 | 90 | 91 | 91 |
Minimum Rated Power Factor2 |
0.97 | 0.97 | 0.97 | 0.97 |
Maximum Inrush Current (A peak) |
20 |
Maximum Inrush Current (ms) |
0.2 |
Minimum Ride-Through Time (ms)3 |
12 |
![]() Note |
|
Power Cord Specifications
Each power supply in the server has a power cord. Standard power cords or jumper power cords are available for connection to the server. The shorter jumper power cords, for use in racks, are available as an optional alternative to the standard power cords.
![]() Note |
Only the approved power cords or jumper power cords listed below are supported. |
Description |
Length (Feet) |
Length (Meters) |
CAB-48DC-40A-8AWG DC power cord, -48 VDC, 40 A, 8 AWG Three-socket Mini-Fit connector to three-wire |
11.7 |
3.5 |
CAB-C13-C14-AC AC power cord, 10 A; C13 to C14, recessed receptacle |
9.8 |
3.0 |
CAB-250V-10A-AR AC power cord, 250 V, 10 A Argentina |
8.2 |
2.5 |
CAB-C13-C14-2M-JP AC Power Cord, C13 to C14 Japan PSE Mark |
6.6 |
2.0 |
CAB-9K10A-EU AC Power Cord, 250 V, 10 A; CEE 7/7 Plug Europe |
8.2 |
2.5 |
CAB-250V-10A-IS AC Power Cord, 250 V, 10 A Israel |
8.2 |
2.5 |
CAB-250V-10A-CN AC power cord, 250 V, 10 A PR China |
8.2 |
2.5 |
CAB-ACTW AC power cord, 250 V, 10 A Taiwan |
7.5 |
2.3 |
CAB-C13-CBN AC cabinet jumper power cord, 250, 10 A, C13 to C14 |
2.2 |
0.68 |
CAB-C13-C14-2M AC cabinet jumper power cord, 250 V, 10 A, C13 to C14 |
6.6 |
2.0 |
CAB-9K10A-AU AC power cord, 250 V, 10 A, 3112 plug, Australia |
8.2 |
2.5 |
CAB-N5K6A-NA AC power cord, 200/240 V, 6 A, North America |
8.2 |
2.5 |
CAB-250V-10A-ID AC power Cord, 250 V, 10 A, India |
8.2 |
2.5 |
CAB-9K10A-SW AC power cord, 250 V, 10 A, MP232 plug Switzerland |
8.2 |
2.5 |
CAB-250V-10A-BR AC power Cord, 250 V, 10 A Brazil |
8.2 |
2.5 |
CAB-9K10A-UK AC power cord, 250 V, 10 A (13 A fuse), BS1363 plug United Kingdom |
8.2 |
2.5 |
CAB-9K12A-NA AC power cord, 125 V, 13 A, NEMA 5-15 plug North America |
8.2 |
2.5 |
CAB-AC-L620-C13 AC power cord, NEMA L6-20 to C13 connectors |
6.6 |
2.0 |
CAB-9K10A-IT AC power cord, 250 V, 10 A, CEI 23-16/VII plug Italy |
8.2 |
2.5 |
R2XX-DMYMPWRCORD No power cord; PID option for ordering server with no power cord |
NA |
NA |