- Preface
- Installation Roadmap Overview
- Cisco CRS 16-Slot Line Card Chassis Enhanced Router
- Installing Power Components
- Installing and Removing Air Circulation Components
- Installing Exterior Cosmetic Components
- Installing Line Cards, PLIMs, and Associated Components
- Removing Chassis Components
- Upgrading Chassis Components
- Cisco CRS 16-Slot EC Line Card Chassis Specifications
- Product IDs
Cisco CRS 16-Slot EC
Line Card Chassis Specifications
![]() Note | For a complete list of cards supported in the LCC, see Cisco Carrier Routing System Data Sheets at: http://www.cisco.com/en/US/products/ps5763/products_data_sheets_list.html. |
The appendix includes the following topics:
- Line Card Chassis Specifications
- Power Specifications
- Line Card Chassis Environmental Specifications
- Regulatory, Compliance, and Safety Specifications
Line Card Chassis Specifications
Below table lists the specifications for the LCC.
|
Supported Cards and Modules |
16 modular services cards (MSCs), forwarding processor (FP) cards, or label switch processor (LSP) cards (line cards) 16 physical layer interface modules (PLIMs), one for each MSC, FP, or LSP 8 switch fabric cards (SFCs) 2 route processor (RP) cards or 2 performance route processor (PRP) cards 2 fan trays 1 air filter |
|---|---|
|
Chassis Dimensions |
|
|
Height |
80 in. (203.2 cm) as shipped84 in. (213.4 cm) as installed (with two power shelves) |
|
Width |
23.6 in. (59.9 cm) (without cosmetics)36.0 in. (91.5 cm) with PDU and brackets31.8 in. (80.8 cm) with optional wide cable management troughs |
|
Depth |
36 in. (91 cm) without doors and other cosmetics 39.7 in. (101 cm) with front and rear doors 40.3 in. (102.2 cm) with optional wide cable management troughs |
|
Floor space requirement |
Chassis: 7.5 sq ft (.7 sq m) Aisle spacing to install chassis (front): 48 in. (122 cm) Aisle spacing to service FRUs (front): 36 in. (91 cm) Aisle spacing to service FRUs (rear): 36 in. (91 cm) |
|
Chassis |
|
|
Chassis shipping weight |
993 lb (450.42 kg) |
|
Chassis in shipping crate with pallet |
1300 lb (589.67 kg) |
|
Chassis with power shelves only, no power modules |
1101 lb (499.4 kg) |
|
Chassis with power shelves, power modules, alarm module |
1180 lb (535.2 kg) |
|
Chassis, fully loaded with cards, without cosmetics |
1535 lb (696.3 kg) |
|
Chassis, fully loaded with cards and cosmetics (doors, panels, grilles, and so on) |
1650 lb (748.43 kg |
|
Chassis, fully loaded with cards and cosmetics (doors, panels, grilles, and so on), AC Wye PDU, and brackets |
1720.7 lb (780.5 kg) |
|
Chassis, fully loaded with cards and cosmetics (doors, panels, grilles, and so on), AC Delta PDU, and brackets |
1720.7lb (780.5 kg) |
|
Floor Loading |
|
|
Chassis footprint |
7.2 sq ft (6689 sq cm) |
|
Floor contact area |
5.88 sq ft (5462 sq ft) |
|
Maximum floor loading |
max floor loading without cosmetics and doors 263.6 lb/sq ft max floor loading with cosmetics and doors 292.6 lb/sq ft |
|
Chassis Cooling |
2 fan trays, push-pull configuration |
|
Chassis airflow |
2700 cubic ft/ minute (76,455 liters) |
|
Power shelf airflow |
200 cubic ft/ minute (5660 liters) |
Power Specifications
Below table lists the power specifications for the LCC.
|
Description |
Value |
|---|---|
|
Power shelves |
2 AC or 2 DC power shelves (Cannot mix AC and DC power shelves.) |
|
DC power shelf |
Supports up to 8 DC power modules (PMs) 6 PMs are shipped per shelf |
|
AC power shelf |
Supports up to 6 AC power modules (PMs) 5 PMs are shipped per shelf |
|
Maximum Input Power |
|
|
DC, chassis fully loaded |
19,091 Watts |
|
AC, chassis fully loaded |
19,565 Watts |
|
Maximum Output Power |
|
|
DC, chassis fully loaded |
16.80 kW |
|
AC, chassis fully loaded |
18.00 kW |
|
Power Redundancy |
|
|
DC |
2N: Up to 8 “A” battery plant feeds and up to 8 “B” battery plant feeds |
|
AC |
2N: Up to 6 “A” AC single-phase power sources and up to 6 “B” single-phase AC power sources required. |
|
DC Input |
|
|
Nominal input voltage |
–48 VDC North America–60 VDC InternationalRange: 40 to –72 VDC |
|
Input current |
50 A max at –48 VDC40 A max at –60 VDC60 A at –40 VDC (maximum) |
|
AC Input |
Single-phase |
|
Nominal input voltage |
200 to 240 VAC (range 180 to 264 VAC) |
|
Nominal line frequency |
50/60 Hz (range 47 to 63 Hz) |
|
Recommended AC service |
20 A (North America) dedicated branch circuit16 A (International) dedicated branch circuit |
|
AC power cord length |
167 in. (4.25 m) |
Line Card Chassis Environmental Specifications
Below table lists the environmental specifications for the line card chassis.
|
Description |
Value |
||
|---|---|---|---|
|
Temperature |
Operating, nominal: 41° to 104°F (5° to 40°C) Operating, short-term: 23° to 122°F (–5° to 50°C)1 Nonoperating: –40° to 158°F (–40° to 70°C) |
||
|
Humidity |
Operating: 5 to 90% noncondensing Nonoperating: 5 to 93% noncondensing, short-term operation |
||
|
Altitude |
–197 to 5906 ft (–60 to 1800 m) at 122°F (50°C), short-term Up to 13,123 ft (4000 m) at 104°F (40°C) or below |
||
|
Heat dissipation |
49,134 BTU per hour (maximum) DC2 56,641 BTU per hour—(maximum) AC3 |
||
|
Air exhaust temperature |
140°F (60°C)—at room temperatures of 95 to 102°F (35 to 39°C) 158°F (70°C)—maximum exhaust temperature on a fully loaded system during worst-case operating conditions (50°C and 6000 ft altitude
|
||
|
Air velocity (at exhaust) |
1000 ft/min (5.1m/s) at 3500 rpm 2250 ft/min(11.4m/s) at 7500 rpm
|
||
|
Sound power level(AC and DC power) |
Fan speed 3500 RPM, temperature 80°F (27°C): 77.2 dB—modular configuration power Fan speed 5150 RPM, temperature 104°F (40°C): 88.8 dB—modular configuration power |
||
|
Shock and vibration |
Designed and tested to meet the NEBS shock and vibration standards defined in GR-63 Issue 3 March 2006. |
Regulatory, Compliance, and Safety Specifications
For information about the regulatory, compliance, and safety standards to which the Cisco CRS Series system conforms, see Regulatory Compliance and Safety Information for the Cisco CRS Carrier Routing System .

Feedback