Switch Specifications
Table 6-1 lists the environmental specifications for the Cisco MDS 9700 Series.
Table 6-1 Environmental Specifications for the Cisco MDS 9700 Series
|
|
Temperature, certified for operation |
32 to 104°F (0 to 40°C) |
Temperature, ambient nonoperating and storage |
–40 to 158°F (–40 to 70°C) |
Humidity (RH), ambient (noncondensing) operating |
10 to 90% |
Humidity (RH), ambient (noncondensing) nonoperating and storage |
10 to 95% |
Altitude, certified for operation |
–197 to 6500 ft (–60 to 2000 m) |
Cisco MDS 9718 Director Specification
Table 6-2 lists the physical specifications for the Cisco MDS 9718 Director.
Table 6-2 Physical Specifications for the Cisco MDS 9718 Director
|
|
Dimensions (HxWxD) |
26 rack units (26 RU) 45.25 x 17.3 x 35 in. (114.9 x 43.9 x 88.9 cm) |
Weight |
Chassis (includes fans): 300 lb (136 kg) |
Airflow |
700 (LFM) average system velocity and between 40 and 160 cubic feet per minute (CFM) total flow through each line-card slot depending on the line-card type and fan-speed setting |
Cisco MDS 9710 Director Specification
Table 6-3 lists the physical specifications for the Cisco MDS 9710 Director.
Table 6-3 Physical Specifications for the Cisco MDS 9710 Director
|
|
Dimensions (HxWxD) |
14 rack units (14 RU) 24.35 x 17.3 x 34.0 in. (61.9 x 43.9 x 86.4 cm) |
Weight |
Chassis (includes fans): 185.5 lb (84.2 kg) |
Airflow |
700 (LFM) average system velocity and between 40 and 160 cubic feet per minute (CFM) total flow through each line-card slot depending on the line-card type and fan-speed setting |
Cisco MDS 9706 Director Specification
Table 6-4 lists the physical specifications for the Cisco MDS 9706 Director.
Table 6-4 Physical Specifications for the Cisco MDS 9706 Director
|
|
Dimensions (HxWxD) |
9 rack units (9 RU) 15.6 x 17.3 x 32.0 in. (39.62 x 43.9 x 81.3 cm) |
Weight |
Chassis (includes fans): 145 lb (65.8 kg) |
Airflow |
700 (LFM) average system velocity and between 40 and 160 cubic feet per minute (CFM) total flow through each line-card slot depending on the line-card type and fan-speed setting |
Module Specifications
Table 6-5 lists the specifications for the Cisco MDS 9700 Supervisor-4 Module.
Table 6-5 Cisco MDS 9700 Supervisor-4 Module Specifications
Table 0-6
|
|
Environmental Requirements
|
Temperature, certified for operation (module intake of ambient) |
32 to 104°F (0 to 40°C) |
Temperature, ambient nonoperating and storage |
-40 to 158°F (-40 to 70°C) |
Humidity (RH), ambient (noncondensing) operating |
10 to 90% |
Altitude, designed and tested for operation |
-197 to 6500 ft (-60 to 2000 m) |
|
Dimensions |
2.04 x 8.07 x 23.5 in. (5.18 x 20.49 x 59.69 cm) |
Weight |
7.7 lb (3.5 kg) |
Table 6-7 lists the specifications for the Cisco MDS 9700 Supervisor-1E Modules.
Table 6-7 Cisco MDS 9700 Supervisor-1E Module Specifications
Table 0-8
|
|
Environmental Requirements
|
Temperature, certified for operation (module intake of ambient) |
32 to 104°F (0 to 40°C) |
Temperature, ambient nonoperating and storage |
-40 to 158°F (-40 to 70°C) |
Humidity (RH), ambient (noncondensing) operating |
10 to 90% |
Altitude, designed and tested for operation |
-197 to 6500 ft (-60 to 2000 m) |
|
Dimensions |
2.04 x 7.94 x 21.85 in. (5.18 x 20.17 x 55.5 cm) |
Weight |
8.5 lb (3.86 kg) |
Table 6-9 lists the specifications for the Cisco MDS 9700 Supervisor-1 Modules.
Table 6-9 Cisco MDS 9700 Supervisor-1 Module Specifications
Table 0-10
|
|
Environmental Requirements
|
Temperature, certified for operation (module intake of ambient) |
32 to 104°F (0 to 40°C) |
Temperature, ambient nonoperating and storage |
-40 to 158°F (-40 to 70°C) |
Humidity (RH), ambient (noncondensing) operating |
8 to 80% |
Altitude, certified for operation |
0 to 6500 ft (0 to 2000 m) |
Altitude, designed and tested for operation |
-197 to 6500 ft (-60 to 2000 m) |
|
Dimensions |
2.04 x 7.5 x 21.8 in. (5.18 x 19.05 x 55.37 cm) |
Weight |
7 lb (3.2 kg) |
Table 6-11 lists the specifications for the Cisco MDS 9700 Series Crossbar Fabric Switching Modules.
Table 6-11 Cisco MDS 9700 Series Crossbar Fabric Switching Module Specifications
|
|
Environmental Requirements
|
Temperature, certified for operation (module intake of ambient) |
32 to 104°F (0 to 40°C) |
Temperature, ambient nonoperating and storage |
-40 to 158°F (-40 to 70°C) |
Humidity (RH), ambient (noncondensing) operating |
10 to 90% |
Altitude, certified for operation |
0 to 6500 ft (0 to 2000 m) |
Altitude, designed and tested for operation |
-197 to 6500 ft (-60 to 2000 m) |
|
Dimensions |
1.75 x 15.9 x 21.8 in. (4.4 x 40.39 x 55.37 cm) |
Weight |
17lb (7.7kg) |
Table 6-12 lists the specifications for the Cisco MDS 9700 Series 40-Gigabit FCoE Switching Module.
Table 6-12 Cisco MDS 9700 Series 40-Gigabit FCoE Module Specifications
|
|
Environmental Requirements
|
Temperature, certified for operation (module intake of ambient) |
32 to 104°F (0 to 40°C) |
Temperature, ambient nonoperating and storage |
-40 to 158°F (-40 to 70°C) |
Humidity (RH), ambient (noncondensing) operating |
5 to 90% |
Altitude, certified for operation |
0 to 6500 ft (0 to 2000 m) |
Altitude, designed and tested for operation |
-197 to 6500 ft (-60 to 2000 m) |
|
Dimensions |
1.75 x 15.9 x 21.8 in. (4.4 x 40.39 x 55.37 cm) |
Weight |
17 lb (7.7 kg) |
Table 6-13 lists the specifications for the Cisco MDS 9700 Series 10-Gigabit FCoE Switching module.
Table 6-13 Cisco MDS 9700 Series 10-Gigabit FCoE Module Specifications
|
|
Environmental Requirements
|
Temperature, certified for operation (module intake of ambient) |
32 to 104°F (0 to 40°C) |
Temperature, ambient nonoperating and storage |
-40 to 158°F (-40 to 70°C) |
Humidity (RH), ambient (noncondensing) operating |
8 to 80% |
Altitude, certified for operation |
0 to 6500 ft (0 to 2000 m) |
Altitude, designed and tested for operation |
-197 to 6500 ft (-60 to 2000 m) |
|
Dimensions |
1.75 x 15.9 x 21.8 in. (4.4 x 40.39 x 55.37 cm) |
Weight |
17 lb (7.7 kg) |
Table 6-14 lists the specifications for the Cisco MDS 9700 Series 24/10-Port SAN Extension Module.
Table 6-14 Cisco MDS 9700 Series 24/10-Port SAN Extension Module Specifications
|
|
Environmental Requirements
|
Temperature, certified for operation (module intake of ambient) |
32 to 104°F (0 to 40°C) |
Temperature, ambient nonoperating and storage |
-40 to 158°F (-40 to 70°C) |
Humidity (RH), ambient (noncondensing) operating |
5 to 90% |
Altitude, designed and tested for operation |
-197 to 6500 ft (-60 to 2000 m) |
|
Dimensions |
1.75 x 15.9 x 21.8 in. (4.4 x 40.39 x 55.37 cm) |
Weight |
17 lb (7.7 kg) |
Table 6-15 lists the specifications for the Cisco MDS 9700 48-Port 32-Gbps FC Switching Module.
Table 6-15 Cisco MDS 9700 Series 48-Port 32-Gbps Fibre Channel Switching Module Specifications
|
|
Environmental Requirements
|
Temperature, certified for operation (module intake of ambient) |
32 to 104°F (0 to 40°C) |
Temperature, ambient nonoperating and storage |
-40 to 158°F (-40 to 70°C) |
Humidity (RH), ambient (noncondensing) operating |
10 to 90% |
Altitude, designed and tested for operation |
-197 to 6500 ft (-60 to 2000 m) |
|
Dimensions |
1.75 x 15.9 x 21.8 in. (4.4 x 40.39 x 55.37 cm) |
Weight |
17.5 lb (7.94 kg) |
Table 6-16 lists the specifications for the Cisco MDS 9700 48-Port 16-Gbps FC Switching Module
Table 6-16 Cisco MDS 9700 Series 48-Port 16-Gbps Fibre Channel Switching Module Specifications
|
|
Environmental Requirements
|
Temperature, certified for operation (module intake of ambient) |
32 to 104°F (0 to 40°C) |
Temperature, ambient nonoperating and storage |
-40 to 158°F (-40 to 70°C) |
Humidity (RH), ambient (noncondensing) operating |
10 to 90% |
Altitude, designed and tested for operation |
-197 to 6500 ft (-60 to 2000 m) |
|
Dimensions |
1.75 x 15.9 x 21.8 in. (4.4 x 40.39 x 55.37 cm) |
Weight |
17 lb (7.71 kg) |
Power Specifications for the Cisco MDS 9700 Series
This section includes the following topics:
Power Supply Specifications
Table 6-17 lists the specifications for the Cisco MDS 9700 Series power supplies.
Table 6-17 Specifications for Cisco MDS 9700 Series Power Supplies
|
|
|
Type |
Autoranging input with power factor corrector. |
Voltage |
100 to 240 VAC (±10%). |
Current rating |
16 A maximum at 100 to 120 VAC and 1451-W output. 16 A maximum at 200 to 240 VAC and 3051-W output. For current ratings of plugs, see Figure 7-3. |
Frequency |
50 to 60 Hz (nominal) (±3 Hz for full range). |
Output capacity |
1451 W maximum (100 to 120 VAC, 1400W available to chassis) 3051 W maximum (200 to 240 VAC, 3000W available to chassis) |
Output voltage at 110/120 |
3.4V (+/- 4%) at 15A; 50V(+/- 4%) at 28A. |
Output voltage at 200/240 |
3.4V (+/- 4%) at 15A; 50V(+/- 4%) at 28A |
Efficiency |
>94% at 50% load |
ITHD |
<5.1% at 50% load |
3500-W High Voltage AC/DC Power Supply
|
Type |
Autoranging input with power factor corrector. |
Input Voltage Range |
120 VAC nominal low-line mode (85 to 132 VAC) 240 VAC nominal high-line mode (170 to 264 VAC) 277 VAC nominal high line mode (188 to 305 VAC) 240 VDC nominal high-line mode (192 to 288 VDC) 380 VDC nominal high-line mode (260 to 400 VDC) |
Input Current |
20A service, 16A maximum at nominal line voltage (240 or 277 VAC) 20A service, 16A maximum at nominal line voltage (240 or 380 VDC) |
Input Frequency |
47 to 63 Hz |
Output capacity |
1500 W maximum (100 to 120 VAC) 3100 W maximum (200 to 210 VAC) 3500 W maximum (215 to 240 and 277 VAC) 3100 W maximum (200 to 215 VDC) 3500 W maximum (220 to 380 VDC) |
Component Power Requirements and Heat Dissipation
When sizing the air-conditioning requirements for an installation, consider heat dissipation. The power and heat associated with a Cisco MDS 9700 Directors varies based upon the following considerations:
- Power supply type
- Switching module type and number of switching modules installed
- Average switching traffic levels
Table 6-18 lists the power requirements for the components of the Cisco MDS 9700 Directors.
Note
Unless noted otherwise, the power requirement data listed under the “Maximum” Power Required column in Table 6-18 is based on the worst-case conditions that are unlikely in a data center environment.
Table 6-18 Module-Wise Requirements for 3000 W AC Power Supplies
Module Type/
Product Number
|
|
|
|
|
Cisco MDS 9700 48 port 32 Gbps Switching Module (DS-X9648-1536K9) |
4 (Cisco MDS 9706) 8 (Cisco MDS 9710) 16 (Cisco MDS 9718) |
350 |
260 |
Cisco MDS 48 port 16 Gbps Switching Module (DS-X9448-768K9) |
650 |
480 |
Cisco MDS 48 Port 10 Gigabit Fibre Channel over Ethernet Module (DS-X9848-480K9) |
500 |
400 |
24 Port 40 Gbps Fibre Channel over Ethernet (FCoE) Module (DS-X9824-960K9) |
740 |
550 |
24/10 port SAN Extension Module (DS-X9334-K9) |
480 |
450 |
Cisco MDS 9700 Series Supervisor-4 Module (DS-X97-SF4-K9) |
2 |
120 |
110 |
Cisco MDS 9700 Series Supervisor-1E Module (DS-X97-SF1E-K9) |
265 |
160 |
Cisco MDS 9700 Series Supervisor-1 Module (DS-X97-SF1-K9) |
190 |
110 |
Cisco MDS 9718 Crossbar Switching Fabric-1 Module (DS-X9718-FAB1) |
6 |
300 |
160 |
Cisco MDS 9710 Crossbar Switching Fabric-3 Module (DS-X9710-FAB3) |
150 |
135 |
Cisco MDS 9706 Crossbar Switching Fabric-3 Module (DS-X9706-FAB3) |
85 |
64 |
Cisco MDS 9710 Crossbar Switching Fabric-1 Module (DS-X9710-FAB1) |
150 |
135 |
Cisco MDS 9706 Crossbar Switching Fabric-1 Module (DS-X9706-FAB1) |
85 |
64 |
Cisco MDS 9718 Fan Module (DS-C9718-FAN) |
3 |
900 |
75 |
Cisco MDS 9710 Fan Module (DS-C9710-FAN) |
600 |
50 |
Cisco MDS 9706 Fan Module (DS-C9706-FAN) |
300 |
40 |
Table 6-19 Requirements and Heat Dissipation for 3000 W AC Power Supplies for Different Solutions with 32-G Fibre Channel ports using Cisco MDS 9700 48 port 32Gbps Switching Module (DS-X9648-1536K9) and six Fabric Modules.
|
|
|
|
Heat Dissipation (BTU/hr)
|
Number of Switching Modules
|
|
|
1 |
48 |
1440 |
3430 |
12861 |
2 |
96 |
1700 |
3780 |
14173 |
3 |
144 |
1960 |
4130 |
15486 |
4 |
192 |
2220 |
4480 |
16798 |
5 |
240 |
2480 |
4830 |
18111 |
6 |
288 |
2740 |
5180 |
19423 |
7 |
336 |
3000 |
5530 |
20735 |
8 |
384 |
3260 |
5880 |
22048 |
AC Power Consumption for the Cisco MDS 9718 Director
Table 6-20 shows the typical AC power consumption for the Cisco MDS 9718 Director.
Table 6-20 Typical AC Power Consumption for Cisco MDS 9718 Director
|
|
Typical AC Power Consumption (Watts)
|
|
|
|
|
32-G Fibre Channel ports with Cisco MDS 9700 48-port 32-Gbps Switching Module (DS-X9648-1536K9) |
6 |
2545 |
3065 |
3585 |
5665 |
16-G Fibre Channel ports with Cisco MDS 9700 48-port 32-Gbps Switching Module (DS-X9648-1536K9) |
2545 |
3065 |
3585 |
5665 |
16-G Fibre Channel ports with Cisco MDS 9700 48-port 16-Gbps Switching Module (DS-X9448-768K9) |
3425 |
4385 |
5345 |
9185 |
AC Power Consumption for the Cisco MDS 9710 Director
Table 6-21 shows the typical AC power consumption for the Cisco MDS 9710 Director.
Table 6-21 Typical AC Power Consumption for Cisco MDS 9710 Director
|
|
Typical AC Power Consumption (Watts)
|
|
|
|
32-G Fibre Channel ports with Cisco MDS 9700 48-port 32-Gbps Switching Module (DS-X9648-1536K9) |
6 |
2220 |
2740 |
3260 |
16-G Fibre Channel ports with Cisco MDS 9700 48-port 32-Gbps Switching Module (DS-X9648-1536K9) |
3 |
1815 |
2335 |
2855 |
16-G Fibre Channel ports with Cisco MDS 9700 48-port 16-Gbps Switching Module (DS-X9448-768K9) |
3 |
2695 |
3655 |
4615 |
AC Power Consumption for the Cisco MDS 9706 Director
Table 6-22 shows the typical AC power consumption for the Cisco MDS 9706 Director.
Table 6-22 Typical AC Power Consumption for Cisco MDS 9706 Director
|
|
Typical AC Power Consumption (Watts)
|
|
|
32-G Fibre Channel ports with Cisco MDS 9700 48-port 32-Gbps Switching Module (DS-X9648-1536K9) |
6 |
1244 |
1764 |
16-G Fibre Channel ports with Cisco MDS 9700 48-port 32-Gbps Switching Module (DS-X9648-1536K9) |
3 |
1052 |
1572 |
16-G Fibre Channel ports with Cisco MDS 9700 48-port 16-Gbps Switching Module (DS-X9448-768K9) |
3 |
1492 |
2452 |
AC Power Supply Requirements for Grid Redundancy
The minimum number of AC PSUs required to achieve grid redundancy on each of the Cisco MDS 9700 Series Directors differ. This number is irrespective of the optics configured (See Table 6-24 ). Modifications made to the configurations may require additional PSUs as per Table 6-23 .
Note
The minimum number of AC PSUs required to achieve grid redundancy is based on the maximum reserved power per chassis for any given configuration. The actual power consumption will be lower.
Table 6-23 AC PSU Requirements for Grid Redundancy
|
|
Minimum PSUs Required for Grid Redundancy
|
Cisco MDS 9718 |
Up to 16 x Cisco MDS 48 Port 32-Gbps Fibre Channel Switching Modules |
8 |
Up to 12 x Cisco MDS 48 Port 32-Gbps Fibre Channel Switching Modules and up to 4 x 24/10 port SAN Extension Module |
8 |
Any other supported module or a combination of supported modules:
- 48 Port 32-Gbps Fibre Channel Switching Module
- 24/10 port SAN Extension Module
- 24 Port 40-Gbps Fibre Channel over Ethernet Module
- 48 Port 16-Gbps Fibre Channel Switching Module
- 48 Port 10-Gbps Fibre Channel over Ethernet Module
|
12 |
Cisco MDS 9710 |
Up to 8 x Cisco MDS 48 Port 32-Gbps Fibre Channel Switching Modules |
4 |
Any other supported module or a combination of supported modules:
- 48 Port 32-Gbps Fibre Channel Switching Module
- 24/10 port SAN Extension Module
- 24 Port 40-Gbps Fibre Channel over Ethernet Module
- 48 Port 16-Gbps Fibre Channel Switching Module
- 48 Port 10-Gbps Fibre Channel over Ethernet Module
|
6 |
Cisco MDS 9706 |
Up to 3 x Cisco MDS 48 Port 32-Gbps Fibre Channel Switching Modules |
2 |
Any other supported module or a combination of supported modules:
- 48 Port 32-Gbps Fibre Channel Switching Module
- 24/10 port SAN Extension Module
- 24 Port 40-Gbps Fibre Channel over Ethernet Module
- 48 Port 16-Gbps Fibre Channel Switching Module
- 48 Port 10-Gbps Fibre Channel over Ethernet Module
|
4 |
SFP+ Transceiver Specifications
The Cisco MDS 9700 Series switch is compatible with SFP+ transceivers and cables that have LC connectors. The wavelength of each transceiver must match the transceiver on the other end of the cable, and the cable must not exceed the stipulated cable length for reliable communications.
Cisco SFP+ transceivers provide the uplink interfaces, laser transmit (Tx) and laser receive (Rx), and support 850 to 1610 nm nominal wavelengths, depending upon the transceiver.
Use only Cisco SFP+ transceivers on the Cisco MDS 9700 Series. Each Cisco SFP+ transceiver is encoded with model information that enables the switch to verify that the SFP+ transceiver meets the requirements for the switch.
This section provides the following topics:
Cisco Fibre Channel SFP+ Transceivers
Table 6-24 lists the Cisco Fibre Channel transceivers.
Table 6-24 Cisco Fibre Channel Transceivers
Transceiver Module
Product Number
|
|
|
DS-SFP-FC32G-SW |
32-Gbps Fibre Channel SW SFP+ |
Short wavelength |
DS-SFP-FC32G-LW |
32-Gbps Fibre Channel LW SFP+ |
Long wavelength |
DS-SFP-FC16G-SW |
16-Gbps Fibre Channel SW, SFP+ |
Short wavelength |
DS-SFP-FC16G-LW |
16-Gbps Fibre Channel LW, SFP+ |
Long wavelength |
DS-SFP-FC10G-SW |
10-Gbps Fibre Channel SW SFP+ |
Short wavelength |
DS-SFP-FC10G-LW |
10-Gbps Fibre Channel LW SFP+ |
Long wavelength |
DS-SFP-FC8G-SW |
8-Gbps Fibre Channel SW, SFP+ |
Short wavelength |
DS-SFP-FC8G-LW |
8-Gbps Fibre Channel LW, SFP+ |
Long wavelength |
DS-SFP-FC8G-ER |
8-Gbps Fibre Channel ER SFP+ |
Extended Reach |
DS-CWDM8Gxxxx |
8-Gbps Fibre Channel CWDM SFP+ |
Coarse Wavelength-Division Multiplexing (CWDM) |
SFP-10G-SR |
10GBASE-SR SFP Module |
Short Reach |
SFP-10G-LR |
10GBASE-LR SFP Module |
Long Reach |
SFP-10G-ER |
10GBASE-ER SFP Module |
Extended Reach |
DWDM-SFP10G xxxx |
10GBASE-DWDM SFP+ |
Dense Wavelength- Division Multiplexing (DWDM). 40 different wavelengths are offered . |
General Specifications for Cisco 32-Gbps Fibre Channel SFP+ Transceivers
Table 6-25 provides the general specifications for Cisco Fibre Channel SFP+ transceivers.
Table 6-25 General Specifications for Cisco 32 Gbps Fibre Channel SFP+ Transceivers
|
|
|
|
|
|
DS-SFP-FC32G-SW |
850 |
MMF |
50.0 |
28.05 |
65 ft (20m) (OM2) |
50.0 |
28.05 |
230 ft (70m) (OM3) |
50.0 |
28.05 |
328 ft (100m) (OM4) |
50.0 |
28.05 |
328 ft (100m) (OM5) |
62.5 |
14.025 |
49 ft (15m) (OM1) |
50.0 |
14.025 |
115 ft (35m) (OM2) |
50.0 |
14.025 |
328 ft (100m) (OM3) |
50.0 |
14.025 |
410 ft (125m) (OM4) |
50.0 |
14.025 |
410 ft (125m) (OM5) |
62.5 |
8.5 |
69 ft (21m) (OM1) |
50.0 |
8.5 |
164 ft (50m) (OM2) |
50.0 |
8.5 |
492 ft (150m) (OM3) |
50.0 |
8.5 |
623 ft (190m) (OM4) |
50.0 |
8.5 |
623 ft (190m) (OM5) |
DS-SFP-FC32G-LW |
1310 |
SMF |
9.0 |
28.05 |
6.2 mi (10 km) |
9.0 |
14.025 |
6.2 mi (10 km) |
9.0 |
8.5 |
6.2 mi (10 km) |
Environmental and Power Requirements for Cisco 32-Gbps Fibre Channel SFP+ Transceivers
Table 6-26 provides the power specification for the Cisco 32-Gbps Fibre Channel SFP+ transceivers.
Table 6-26 Power Requirements Specification for Cisco 32-Gbps Fibre Channel SFP+ Transceivers
|
Average Transmit
Power (dBm)
|
Average Receive
Power (dBm)
|
|
|
|
|
|
|
|
|
|
DS-SFP-FC32G-SW |
2.0 |
-6.2 |
2.0 |
-8.2 |
1.68 (8 Gbps) 1.63 (16 Gbps) 2.02 (32 Gbps) |
2.04 (8 Gbps) 1.86 (16 Gbps) 1.86 (32 Gbps) |
2.04 (8 Gbps) 1.95 (16 Gbps) 1.86 (32 Gbps) |
2.04 (8 Gbps) 1.95 (16 Gbps) 1.86 (32 Gbps) |
DS-SFP-FC32G-LW |
2.0 |
-5.0 |
2.0 |
-11.4 |
6.4 (8 Gbps) 6.4 (16 Gbps) 6.4 (32 Gbps) |
Table 6-27 provides the environment specification for the Cisco 32-Gbps Fibre Channel SFP+ transceivers.
Table 6-27 Environmental Specifications for Cisco 32-Gbps Fibre Channel SFP+ Transceivers
|
|
|
|
|
|
|
DS-SFP-FC32G-SW |
40°C |
0°C |
70°C |
-40°C |
DS-SFP-FC32G-LW |
40°C |
0°C |
70°C |
-40°C |
For information about safety, regulatory, and standards compliance, refer to the Regulatory Compliance and Safety Information for the Cisco MDS 9000 Family
General Specifications for Cisco 16-Gbps Fibre Channel SFP+ Transceivers
Table 6-28 provides the general specifications for Cisco Fibre Channel SFP+ transceivers.
Table 6-28 General Specifications for Cisco 16-Gbps Fibre Channel SFP+ Transceivers
|
|
|
|
|
|
DS-SFP-FC16G-SW |
850 |
MMF |
62.5 |
14.025 |
15 m (49 ft) (OM1) |
|
|
50.0 |
14.025 |
35 m (115 ft) (OM2) |
50.0 |
14.025 |
100 m (328 ft) (OM3) |
50.0 |
14.025 |
125 m (410 ft) (OM4) |
50.0 |
14.025 |
125 m (410 ft) (OM5) |
62.5 |
8.5 |
21 m (69 ft) (OM1) |
50.0 |
8.5 |
50 m (164 ft) (OM2) |
50. 0 |
8.5 |
150 m (492 ft) (OM3) |
50.0 |
8.5 |
190 (623 ft) (OM4) |
50.0 |
8.5 |
190 (623 ft) (OM5) |
62.5 |
4.25 |
70 m (230 ft) (OM1) |
50.0 |
4.25 |
150 m (492 ft) (OM2) |
50. 0 |
4.25 |
380 m (1247 ft) (OM3) |
5.0 |
4.25 |
400 m (1312 ft) (OM2) |
DS-SFP-FC16G-LW |
1310 |
SMF |
9.0 |
14.025 |
10 km (6.2 miles) |
|
9.0 |
8.5 |
10 km (6.2 miles) |
90 |
4.25 |
10 km (6.2 miles) |
Environmental and Power Requirements for Cisco 16-Gbps Fibre Channel SFP+ Transceivers
Table 6-29 provides the power specification for the Cisco 16-Gbps Fibre Channel SFP+ transceivers.
Table 6-29 Power Requirements Specification for Cisco 16-Gbps Fibre Channel SFP+ Transceivers
|
Average Transmit
Power (dBm)
|
Average Receive
Power (dBm)
|
|
|
|
|
|
|
|
|
DS-SFP-FC16G-SW |
-1.3 |
-7, 8 |
0 |
-10.3 |
2.08 (4 Gbps) 1.68 (8 Gbps) 1.63 (16 Gbps) |
2.08 (4 Gbps) 1.68 (8 Gbps) 1.63 (16 Gbps) |
2.88 (4 Gbps) 1.04 (8 Gbps) 1.86 (16 Gbps) |
DS-SFP-FC16G-LW |
1.3 |
-5.0 |
2.0 |
-10.0 |
7.8 (4 Gbps) 6.4 (8 Gbps) 6.4 (16 Gbps) |
— |
— |
Table 6-30 provides the environment specification for the Cisco 16-Gbps Fibre Channel SFP+ transceivers.
Table 6-30 Environmental Specifications for Cisco 16 Gbps Fibre Channel SFP+ Transceivers
|
|
|
|
|
|
|
DS-SFP-FC16G-SW |
40°C |
0°C |
85°C |
-40°C |
DS-SFP-FC16G-LW |
40°C |
0°C |
85°C |
-40°C |
For information about safety, regulatory, and standards compliance, refer to the Regulatory Compliance and Safety Information for the Cisco MDS 9000 Family.
General Specifications for Cisco 8-Gbps Fibre Channel SFP+ Transceivers
Table 6-31 provides the general specifications for Cisco 8-Gbps Fibre Channel SFP+ transceivers.
Table 6-31 General Specifications for Cisco 8-Gbps Fibre Channel SFP+ Transceivers
|
|
|
|
|
|
DS-SFP-FC8G-SW |
850 |
MMF |
62.5 |
2.125 |
150 m (492 ft) (OM1) |
|
|
62.5 |
4.250 |
70 m (230 ft) |
62.5 |
8.500 |
21 m (69 ft) |
50.0 (OM2) |
2.125 |
300 m (984 ft) |
50.0 (OM2) |
4.250 |
150 m (492 ft) |
50.0(OM2) |
8.500 |
50 m (164 ft) |
50. 0 (OM3) |
2.125 |
500 m (1640 ft) |
50. 0 (OM3) |
4.250 |
380 m (1246 ft) |
50. 0 (OM3) |
8.500 |
150 m (492 ft) |
DS-SFP-FC8G-LW |
1310 |
SMF |
9.0 |
2.125 |
6.2 miles (10 km) |
9.0 |
4.250 |
6.2 miles (10 km) |
9.0 |
8.500 |
6.2 miles (10 km) |
DS-SFP-FC8G-ER |
1550 |
SMF |
9.0 |
2.125 |
40 km (24.85 miles) |
|
90 |
4.250 |
40 km (24.85 miles) |
90 |
8.500 |
40 km (24.85 miles) |
Environmental and Power Requirements for Cisco 8-Gbps Fibre Channel SFP+ Transceivers
Table 6-32 provides the power specification for the Cisco 8-Gbps Fibre Channel SFP+ transceivers.
Table 6-32 Power Requirements Specification for Cisco 8-Gbps Fibre Channel SFP+ Transceivers
|
Average Transmit
Power (dBm)
|
Average Receive
Power (dBm)
|
|
|
|
|
|
|
|
|
DS-SFP-FC8G-SW |
-1.3 |
-10 (2 Gbps) -9 (4 Gbps) -8.2 (8 Gbps) |
0 |
— |
2.10 (2 Gbps) 1.78 (4 Gbps) 1.58 (8 Gbps) |
2.62 (2 Gbps) 2.06 (4 Gbps) 1.68 (8 Gbps) |
3.31 (2 Gbps) 2.88 (4 Gbps) 2.04 (8 Gbps) |
DS-SFP-FC8G-LW |
–3 (2 Gbps) –1 (4 Gbps) +0.5 (8 Gbps) |
–11.7 (2 Gbps) –8.4 (4 Gbps) –8.4 (8 Gbps) |
–3 (2 Gbps) –1 (4 Gbps) +0.5 ( 8 Gbps) |
— |
7.8 (2 Gbps) 7.8 (4 Gbps) 6.4 (8 Gbps) |
DS-SFP-FC8G-ER |
4 |
- 47 |
14.1 |
— |
10.9 |
— |
— |
Table 6-33 provides the environment specification for the Cisco 8-Gbps Fibre Channel SFP+ transceivers.
Table 6-33 Environmental Specifications for Cisco 8-Gbps Fibre Channel SFP+ Transceivers
|
|
|
|
|
|
|
DS-SFP-FC8G-SW |
40°C |
0°C |
85°C |
-40°C |
DS-SFP-FC8G-LW |
40°C |
0°C |
85°C |
-40°C |
DS-SFP-FC8G-ER |
40°C |
0°C |
85°C |
-40°C |
For information about safety, regulatory, and standards compliance, refer to the Regulatory Compliance and Safety Information for the Cisco MDS 9000 Family.
Maximum Environmental and Electrical Ratings for Cisco Fibre Channel SFP+ Transceivers
Table 6-34 provides the maximum environmental and electrical ratings for Cisco Fibre Channel SFP+ transceivers.
Table 6-34 Maximum Environmental and Electrical Ratings for Cisco Fibre Channel SFP+ Transceivers
|
|
|
|
|
|
Storage temperature |
TS |
-40 |
85 |
°C |
1 |
Case temperature |
TC |
0 |
70 |
°C |
1, 2 |
Relative humidity |
RH |
5 |
95 |
% |
1 |
For information about safety, regulatory, and standards compliance, refer to the Regulatory Compliance and Safety Information for the Cisco MDS 9000 Family.
10-Gigabit Fibre Channel over Ethernet Interface Distances and Options
Table 6-35 10-Gigabit Fibre Channel over Ethernet Interface Distances and Options
10-Gigabit Fibre Channel over Ethernet SFP+
|
|
|
|
Modal Bandwidth (MHz per km)
|
|
SFP-10G-SR |
850 |
MMF (FDDI-grade) MMF (OM1) MMF (400/400) MMF (OM2) MMF (OM3) MMF (OM4) MMF (OM5) |
62.5 62.5 50.0 50.0 50.0 50.0 50.0 |
160 200 400 500 2000 4700 4700 |
26 m 33 m 66 m 82 m 300 m 400 m 400 m |
SFP-10G-LRM |
1310 |
MMF |
62.5 50 50 |
500 400 500 |
220 m 100 m 220 m |
SMF |
G.652 |
— |
300 m |
SFP-10G-LR |
1310 |
SMF |
G.652 |
— |
10 km |
SFP-10G-ER |
1550 |
SMF |
G.652 |
— |
40 km |
SFP-10G-ZR |
1550 |
SMF |
G.652 |
— |
80 km |
DWDM-SFP10G-xx.xx= |
|
SMF |
— |
— |
80 km |
SFP-H10GB-CUxM (x=1, 3, or 5) |
— |
Twinax cable assembly, passive |
— |
— |
1, 3, or 5 m |
SFP-H10GB-ACUxM(x=7 or 10 |
— |
Twinax cable assembly, passive |
— |
— |
7 or 10 m |
SFP-10G-AOCxM(x=1, 2, 3, 5, 7, or 10) |
— |
Twinax cable assembly, passive |
— |
— |
1, 2, 3, 5, 7, or 10 m |
40 Gigabit Fibre Channel over Ethernet Interface Distances and Options
Table 6-36 40 Gigabit Fibre Channel over Ethernet Interface Distances and Options
10-Gigabit Fibre Channel over Ethernet SFP+
|
|
|
|
Modal Bandwidth (MHz per km)
|
|
QSFP-40G-SR4 QSFP-40G-SR4-S |
850 |
MMF (OM2) MMF (OM3) MMF (OM4) MMF (OM5) |
50.0 50.0 50.0 50.0 |
500 2000 4700 4700 |
30m 100m 150m 150m |
QSFP-40G-CSR4 QSFP-40G-CSR4-S |
850 |
MMF (OM1) MMF (OM2) MMF (OM3) MMF (OM4) MMF (OM5) |
62.5 50.0 50.0 50.0 50.0 |
200 500 2000 4700 4700 |
33m 82m 300m 400m 400m |
QSFP-40G-SR-BD |
850/900 |
MMF (OM2) MMF (OM3) MMF (OM4) MMF (OM5) |
50.0 50.0 50.0 50.0 |
500 2000 4700 4700 |
30m 100m 150m 150m |
QSFP-H40G-AOCxM (x=1, 2, 3, 5, 7, or 10) |
- |
Active optical cable assembly |
- |
- |
1, 2, 3, 5, 7, or 10m |
QSFP-40GE-LR4 |
1310 |
SMF |
G.652 |
- |
6.21 miles (10 km) |
QSFP-40GE-ER4 |
1310 |
SMF |
G.652 |
- |
40 km |