Switch Installation

This chapter describes how to install your switch, verify the boot fast, and connect the switch to other devices. It also includes information specifically for installations in hazardous environments.

Read these topics, and perform the procedures in this order:

blank.gifPreparing for Installation

blank.gifInstalling or Removing the Flash Memory Card (Optional)

blank.gifConnecting to a Console Port

blank.gifConnecting to Power

blank.gifInstalling the Switch

blank.gifConnecting Alarm Circuits

blank.gifConnecting Destination Ports

blank.gifVerifying Switch Operation

blank.gifWhere to Go Next

Preparing for Installation

This section provides information about these topics:

blank.gifWarnings

blank.gifAdditional Information for Installation in a Hazardous Environment

blank.gifInstallation Guidelines

blank.gifVerifying Package Contents

Warnings

These warnings are translated into several languages in the Regulatory Compliance and Safety Information for this switch.

Warning: Before working on equipment that is connected to power lines, remove jewelry (including rings, necklaces, and watches). Metal objects will heat up when connected to power and ground and can cause serious burns or weld the metal object to the terminals.blank.gif Statement 43

Warning: Do not work on the system or connect or disconnect cables during periods of lightning activity.blank.gif Statement 1001

Warning: Before performing any of the following procedures, ensure that power is removed from the DC circuit.blank.gif Statement 1003

Warning: Read the installation instructions before you connect the system to its power source. blank.gifStatement 1004

Warning: This unit is intended for installation in restricted access areas. A restricted access area can be accessed only through the use of a special tool, lock and key, or other means of security. blank.gifStatement 1017

Warning: This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain that suitable grounding is available. blank.gifStatement 1024

Warning: This unit might have more than one power supply connection. All connections must be removed to de-energize the unit. blank.gifStatement 1028

Warning: Only trained and qualified personnel should be allowed to install, replace, or service this equipment.blank.gif Statement 1030

Warning: Ultimate disposal of this product should be handled according to all national laws and regulations.blank.gif Statement 1040

Warning: For connections outside the building where the equipment is installed, the following ports must be connected through an approved network termination unit with integral circuit protection. blank.gif10/100/1000 Ethernet Statement 1044

Warning: To prevent the system from overheating, do not operate it in an area that exceeds the maximum recommended ambient temperature of: 140°F (60°C)blank.gif Statement 1047

Warning: Installation of the equipment must comply with local and national electrical codes.blank.gif Statement 1074

Caution: Airflow around the switch must be unrestricted. To prevent the switch from overheating, there must be the following minimum clearances:

blank.gifTop and bottom: 2.0 in. (50.8 mm)

blank.gifSides: 2.0 in. (50.8 mm)

blank.gifFront: 2.0 in. (50.8 mm)

Additional Information for Installation in a Hazardous Environment

Hazardous Area Installation Warnings

Warning: Exposure to some chemicals could degrade the sealing properties of materials used in the sealed relay device. blank.gifStatement 381

Warning: Failure to securely tighten the captive screws can result in an electrical arc if the connector is accidentally removed. blank.gifStatement 397

Warning: When you connect or disconnect the power and/or alarm connector with power applied, an electrical arc can occur. This could cause an explosion in hazardous area installations. Be sure that all power is removed from the switch and any other circuits. Be sure that power cannot be accidentally turned on or verify that the area is nonhazardous before proceeding.blank.gif Statement 1058

Warning: In switch installations in a hazardous location, the DC power source could be located away from the vicinity of the switch. Before performing any of the following procedures, locate the DC circuit to ensure that the power is removed and cannot be turned on accidentally, or verify that the area is nonhazardous before proceeding.blank.gif Statement 1059

Warning: This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. The enclosure must meet IP 54 or NEMA type 4 minimum enclosure rating standards.blank.gif Statement 1063

Warning: When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method, for all power, input and output wiring, that complies with the governing electrical codes and in accordance with the authority having jurisdiction over Class I, Division 2 installations.blank.gif Statement 1066

Warning: Use twisted-pair supply wires suitable for 86°F (30°C) above surrounding ambient temperature outside the enclosure.blank.gif Statement 1067

Warning: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), and at altitudes up to 2000 meters without derating.blank.gif Statement 1068

Warning: Do not connect or disconnect cables to the ports while power is applied to the switch or any device on the network because an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed from the switch and cannot be accidentally be turned on, or verify that the area is nonhazardous before proceeding. blank.gifStatement 1070

Warning: If you connect or disconnect the console cable with power applied to the switch or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. blank.gifStatement 1080

Warning: Explosion Hazard—Do not connect or disconnect wiring while the field-side power is on; an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or that the area is nonhazardous before proceeding. blank.gifStatement 1081

Warning: Explosion Hazard—The area must be known to be nonhazardous before installing, servicing, or replacing the unit. blank.gifStatement 1082

Warning: Explosion Hazard—Substitution of components may impair suitability for Class I, Division 2/Zone 2blank.gif. Statement 1083

Warning: Do not insert and remove SFP modules while power is on; an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.blank.gif Statement 1087

Caution: This equipment is only suitable for use in Class I, Division 2, Groups A, B, C, D, or nonhazardous locations.

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations:

 

English:

Products marked "Class I, Div 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

Français:

Informations sur l'utilisation de cet équipement en environnements dangereux:

Les produits marqués "Class I, Div 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.

EMC Environmental Conditions for Products Installed in the European Union

This section applies to products to be installed in the European Union.

The equipment is intended to operate under the following environmental conditions with respect to EMC:

blank.gifA separate defined location under the user’s control.

blank.gifEarthing and bonding shall meet the requirements of ETS 300 253 or CCITT K27.

blank.gifAC-power distribution shall be one of the following types, where applicable: TN-S and TN-C as defined in IEC 364-3.

In addition, if equipment is operated in a domestic environment, interference could occur.

Installation Guidelines

When determining where to place the switch, observe these guidelines.

Environment and Enclosure Guidelines

Review these environmental and enclosure guidelines before installation:

blank.gifThis equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 9842 ft (3 km) without derating.

blank.gifThis equipment is considered Group 1, Class A industrial equipment, according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.

blank.gifThis equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame-spread rating of 5VA, V2, V1, V0 (or equivalent) if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication might contain additional information regarding specific enclosure-type ratings that are required to comply with certain product safety certifications.

General Guidelines

Before installation, observe these general guidelines:

Caution: Proper ESD protection is required whenever you handle Cisco equipment. Installation and maintenance personnel should be properly grounded by using ground straps to eliminate the risk of ESD damage to the switch.

Caution: Do not touch connectors or pins on component boards. Do not touch circuit components inside the switch. When not in use, store the equipment in appropriate static-safe packaging.

blank.gifIf you are responsible for the application of safety-related programmable electronic systems (PES), you need to be aware of the safety requirements in the application of the system and be trained in using the system.

Caution: The device is designed to mount on a DIN rail that conforms to Standard EN50022.

When determining where to place the switch, observe these guidelines:

blank.gifBefore installing the switch, first verify that the switch is operational by powering it on and observing boot fast. Follow the procedures in Verifying Switch Operation.

blank.gifFor 10/100 ports and 10/100/1000 ports, the cable length from a switch to an attached device cannot exceed 328 feet (100 meters).

blank.gifFor 100BASE-FX fiber-optic ports, the cable length from a switch to an attached device cannot exceed 6562 ft (2 km).

blank.gifOperating environment is within the ranges listed in Technical Specifications

blank.gifClearance to front and rear panels meets these conditions:

blank.gifFront-panel LEDs can be easily read.

blank.gifAccess to ports is sufficient for unrestricted cabling.

blank.gifFront-panel direct current (DC) power connectors and the alarm connector are within reach of the connection to the DC power source.

blank.gifAirflow around the switch must be unrestricted. To prevent the switch from overheating, you must have the following minimum clearances:

blank.gifTop and bottom: 2.0 in. (50.8 mm)

blank.gifSides: 2.0 in. (50.8 mm)

blank.gifFront: 2.0 in. (50.8 mm)

blank.gifTemperature surrounding the unit does not exceed 140°F (60°C).

Note: When the switch is installed in an industrial enclosure, the temperature within the enclosure is greater than normal room temperature outside the enclosure.

Note: The temperature inside the enclosure cannot exceed 140°F (60°C), the maximum ambient enclosure temperature of the switch.

blank.gifCabling is away from sources of electrical noise, such as radios, power lines, and fluorescent lighting fixtures.

blank.gifConnect the unit only to a Class 2 DC power source.

Verifying Package Contents

The Cisco IE 2000 Switch Getting Started Guide on Cisco.com describes the box contents. If any item is missing or damaged, contact your Cisco representative or reseller for support.

Installing or Removing the Flash Memory Card (Optional)

The software /firmware is stored on the internal flash memory in the Cisco IE2000 switch. Optionally, you can order and install an SD memory card (SD-IE-1GB=) to store the software and the configuration changes. If you need to replace the switch, you can simply insert the SD memory card instead of configuring the new switch.

Warning: Do not insert or remove the flash card while power is on; an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.blank.gif Statement 379

To install or replace the flash memory card, follow these steps:

1.blank.gif On the front of the switch, locate the door that protects the flash memory card slot. Loosen the captive screw at the top of the door using a Phillips screwdriver to open the door. See Figure 12.

Figure 12 Installing the Flash Memory Card in the Switch

 

331548.jpg

Figure 13 Removing the Flash Memory Card from the Switch

 

331949.jpg

2.blank.gif Install or remove the card:

blank.gifTo install a card, slide it into the slot, and press it in until it clicks in place. The card is keyed so that you cannot insert it the wrong way.

blank.gifTo remove the card, push it in until it releases for it to pop out. Place it in an antistatic bag to protect it from static discharge.

3.blank.gif After the card is installed, close the guard door and fasten the captive screw using a Phillips screwdriver to keep the door in place.

Connecting to a Console Port

You can enter Cisco IOS commands and parameters through the CLI. Use one of these options to access the CLI:

blank.gifRJ-45 Console Port

blank.gifUSB Mini-Type B Console Port

Warning: If you connect or disconnect the console cable with power applied to the switch or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
blank.gifStatement 1080

RJ-45 Console Port

1.blank.gif Connect the RJ-45-to-DB-9 adapter cable to the 9-pin serial port on the PC (see Figure 14).

2.blank.gif Connect the other end of the cable to the switch console port.

3.blank.gif Start the terminal-emulation program on the PC or the terminal.

The program, frequently a PC application such as HyperTerminal or PuTTy, makes communication between the switch and your PC or terminal possible.

Figure 14 Connecting the Console Cable

 

331563.jpg

 

1

RJ-45 console port

2

Console cable (RJ-45-to-DB-9 adapter cable)

4.blank.gif Configure the baud rate and character format of the PC or terminal to match the console port characteristics:

blank.gif9600 baud

blank.gif8 data bits

blank.gif1 stop bit

blank.gifNo parity

blank.gifNone (flow control)

5.blank.gif Connect power to the switch as described in Connecting to Power.

The PC or terminal displays the bootloader sequence.

6.blank.gif Press Enter to display the setup prompt.

7.blank.gif Follow the steps in Completing the Setup Program.

USB Mini-Type B Console Port

If you are connecting the switch USB-mini console port to a Windows-based PC for the first time, install a USB driver. See Installing the Cisco Microsoft Windows XP, 2000, Vista, 7, 8, and 10 USB Device Driver for more information.

To remove the cover from the USB mini-type B console port:

1.blank.gif Use a Phillips screwdriver to loosen the captive screw on the USB mini-type B console port cover. See Figure 15.

2.blank.gif Remove the cover.

Figure 15 Removing the USB Mini-Type B Console Port Cover

 

332703.jpg

3.blank.gif Connect a USB cable to the PC USB port.

4.blank.gif Connect the other end of the cable to the switch mini-B (5-pin connector) USB-mini console port. See Figure 16.

Figure 16 Connecting the USB-Mini Console Cable

 

331554.jpg

 

1

USB-mini console port

3

USB port on the PC

2

USB cable

 

 

5.blank.gif Identify the COM port assigned to the USB-mini console port:

a.blank.gif Choose Start > Control Panel > Systems.

b.blank.gif Click the Hardware tab and choose Device Manager. Expand the Ports section. The assigned COM port appears in parenthesis at the end of the line with this entry: Cisco USB System Management Console.

6.blank.gif Start the terminal-emulation program on the PC or the terminal.

The program, frequently a PC application such as HyperTerminal or ProcommPlus, makes communication possible between the switch and your PC or terminal.

7.blank.gif Configure the COM port.

8.blank.gif Configure the baud rate and character format of the PC or terminal to match the console port characteristics:

blank.gif9600 baud

blank.gif8 data bits

blank.gif1 stop bit

blank.gifNo parity

blank.gifNone (flow control)

9.blank.gif Connect power to the switch as described in Connecting to Power.

10.blank.gif When the PC or terminal displays the bootloader sequence, press Enter to display the setup prompt.

11.blank.gif Follow the steps in Completing the Setup Program.

Connecting to Power

In systems configured with the redundant power option, connect each of the two power supplies to separate independent power sources. If you fail to do this, your system might be susceptible to total power failure due to a fault in the external wiring or a tripped circuit breaker.

Tools and Equipment

Obtain these necessary tools and equipment:

blank.gifRatcheting torque flathead screwdriver that exerts up to 15 in-lb (1.69 N-m) of pressure.

blank.gifFor the protective ground connector, obtain a single or pair of stud size 6 ring terminals (such as Hollingsworth part number R3456B or equivalent).

blank.gifCrimping tool (such as Thomas & Bett part number WT2000, ERG-2001, or equivalent).

blank.gif10-gauge copper ground wire (such as Belden part number 9912 or equivalent).

blank.gifFor DC power connections, use UL- and CSA-rated, style 1007 or 1569 twisted-pair copper appliance wiring material (AWM) wire (such as Belden part number 9318).

blank.gifWire-stripping tools for stripping 10- and 18-gauge wires.

blank.gifA number-2 Phillips screwdriver.

blank.gifA flat-blade screwdriver.

Supported Power Supplies

The supported power supplies are listed in Table 11.

 

Table 11 Supported Power Supplies

 

PWR-IE170W-PC-DC=
PWR-IE170W-PC-AC=
PWR-IE65W-PC-DC=
PWR-IE65W-PC-AC=
PWR-IE50W-AC-IEC=
PWR-IE50W-AC=
Current

DC-DC

AC-DC

DC-DC

AC-DC

AC-DC

AC-DC

Input

10.8-60 VDC

90-264 VAC or 106-300 VDC

18-60 VDC/4.3 Amp

110/220 VAC and 88-300 VDC

110/220 VAC

110/220VAC and 88-300 VDC

Output

54 VDC/3.15 A

54 VDC/3.15 A

54VDC/1.2 Amp

54VDC/1.2 Amp

24VDC/2.1Amp

24 VDC / 2.1Amp

Dimensions

5.93 in H x 4.47 in. W x 5.75 in. D

5.93 in H x 3.72 in. W x 5.60 in. D

5.9 in H x 2.1 in. W x 4.9 in. D

5.9 in. H x 2.1 in. W x 4.9 in. D

5.8 in. H x 2 in. W x 4.4 in. D

5.8 in. H x 2 in. W x 4.4 in. D

Attachable?

Non-
attachable

Non-
attachable

Non-
attachable

Non-
attachable

Attachable unit

Attachable unit

Usage

Designed for PoE modules, can be used to power the switch.

Designed for PoE modules, can be used to power the switch.

Designed for PoE1 modules, can be used to power the switch.

Designed for PoE modules, can be used to power the switch.

Powers the switch. Cannot be used to power PoE modules, which require 48V DC.

Powers the switch. Cannot be used to power PoE modules, which require 48V DC.

1.The models that support PoE provide up to four ports of either PoE (15.4 W per port; IEEE 802.3af) or PoE+ (30 W per port; IEEE 802.3at), depending on the power source used. See .

Installing the Power Converter on a DIN Rail, Wall, or Rack Adapter

You install the power converter on a DIN rail, wall, or rack as you would a switch module.

Warning: This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. The enclosure must meet IP 54 or NEMA type 4 minimum enclosure rating standards.blank.gif Statement 1063

Caution: To prevent the switch assembly from overheating, there must be a minimum of 3 inches (76.19 mm) between any other device and the top, bottom, or sides of the switch assembly.

Grounding the Switch

Follow the grounding requirements at your site.

Warning: This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain that suitable grounding is available.blank.gif Statement 1024

Warning: This equipment is intended to be grounded to comply with emission and immunity requirements. Ensure that the switch functional ground lug is connected to earth ground during normal use.blank.gif Statement 1064

Caution: To ensure that the equipment is reliably connected to earth ground, follow the grounding procedure instructions, and use a UL-listed ring terminal lug suitable for number 10-to-12 AWG wire, such as Hollingsworth part number R3456B or equivalent)

Caution: Use at least a 4 mm2 conductor to connect to the external grounding screw.

The ground lug is not supplied with the switch. You can use one of the these options:

blank.gifSingle ring terminal

blank.gifTwo single ring terminals

To ground the switch to earth ground by using the ground screw, follow these steps:

1.blank.gif Use a standard Phillips screwdriver or a ratcheting torque screwdriver with a Phillips head to remove the ground screw from the front panel of the switch.

Store the ground screw for later use.

2.blank.gif Use the manufacturer’s guidelines to determine the wire length to be stripped.

3.blank.gif Insert the ground wire into the ring terminal lug, and using a crimping tool, crimp the terminal to the wire. See Figure 17.

If two ring terminals are being used, repeat this action for a second ring terminal.

Figure 17 Crimping the Ring Terminal

 

76666.jpg

 

4.blank.gif Slide the ground screw through the terminal.

5.blank.gif Insert the ground screw into the functional ground screw opening on the front panel.

6.blank.gif Use a ratcheting torque screwdriver to tighten the ground screws and ring terminal to the switch front panel to 3.5 in-lb (0.4 N-m). See Figure 18 or Figure 19.

Note: Do not exceed 3.5 in-lb (0.4 N-m) of torque.

Figure 18 Installing the Ground-Lug Screw (Single Ring Terminal)

331951.jpg
1

Ground cable

Figure 19 Installing the Ground-Lug Screws (Two Single Ring Terminals)

331555.jpg

 

1

Ground cable

7.blank.gif Attach the other end of the ground wire to a grounded bare metal surface, such as a ground bus, a grounded DIN rail, or a grounded bare rack.

Connecting the Power Converter to an AC Power Source

These sections describe the steps required to connect the power converter to an AC power source:

blank.gifPreparing the AC Power Connection

blank.gifConnecting the AC Power Source to the Power Converter

Preparing the AC Power Connection

To connect the power converter to an AC power source, you need an AC power cord. Power cord connector types and standards vary by country. Power-cord wiring color codes also vary by country. You must have a qualified electrician select, prepare, and install the appropriate power cord to the power supply.

Use copper conductors only, rated at a minimum temperature of 167°F (75°C).

This section does not apply to PWR-IE50W-AC-IEC, which has pluggable IEC connector.

 

Connecting the AC Power Source to the Power Converter

Caution: AC power sources must be dedicated AC branch circuits. Each branch circuit must be protected by a dedicated two-pole circuit breaker.

Caution: Do not turn on AC power until the wiring is secured.

1.blank.gif Remove the plastic cover from the input power terminals and set it aside.

2.blank.gif Insert the exposed ground wire lead into the power converter ground wire connection.

Ensure that only wire with insulation extends from the connector. See Figure 20, item 1. Note that the position of the power converter may vary on different switch models.

Figure 20 Connecting AC Power

 

347818.jpg

 

1

Ground

3

AC line

2

AC neutral

 

 

 

3.blank.gif Tighten the ground wire terminal block screw.

Note: Torque to 8 in.-lb, not to exceed 10 in-lb.

4.blank.gif Insert the line and neutral wire leads into the terminal block line and neutral connections. See Figure 20, items 2 and 3.

Ensure that you cannot see any wire lead, and that only wire with insulation extends from the connectors.

5.blank.gif Tighten the line and neutral terminal block screws to 8 in.-lb torque.

Note: Do not exceed 10 in-lb torque.

6.blank.gif Replace the plastic cover over the terminal block.

7.blank.gif Connect the other end of the wiring to your AC power source.

Connecting the Power Converter to a DC Power Source

You can also connect the power converter to a DC power source. Several power supplies can be used. Refer to Table 11 for the appropriate DC input ratings.

Use copper conductors only, rated at a minimum temperature of 167°F (75°C).

1.blank.gif Measure a single length of stranded copper wire long enough to connect the power converter to the earth ground.

The wire color differs depending on country.

For connections from the power converter to earth ground, use shielded 18-AWG stranded copper wire, such as Belden part number 9912 or the equivalent.

2.blank.gif Measure a length of twisted-pair copper wire long enough to connect the power converter to the DC power source.

For DC connections from the power converter to the DC source, use 18-AWG twisted-pair copper wire, such as Belden part number 9344 or the equivalent.

3.blank.gif Using a 18-gauge wire-stripping tool, strip the ground wire and both ends of the twisted pair wires to 0.25 inch (6.3 mm) ± 0.02 inch (0.5 mm).

Note: Do not strip more than 0.27 inch (6.8 mm) of insulation from the wires. Stripping more than the recommended amount of wire can leave exposed wire from the power and relay connector after installation.

4.blank.gif Connect one end of the stranded copper wire to a grounded bare metal surface, such as a ground bus, a grounded DIN rail, or a grounded bare rack.

5.blank.gif Insert the other end of the exposed ground wire lead into the earth-ground wire connection on the power converter terminal block.

Only wire with insulation should extend from the connection. See Figure 21, item 1.

The position of the power converter varies on different switch models.

6.blank.gif Tighten the earth-ground wire connection terminal block screw to 8 in.-lb torque.

Note: Do not exceed 10 in-lb torque.

Figure 21 AC/DC Power Input Terminal Block Wire Connections to a DC Source

 

347819.jpg

 

1

Earth ground wire connection

3

Positive DC connection

2

Return wire connection (to DC return)

 

 

Warning: An exposed wire lead from a DC-input power source can conduct harmful levels of electricity. Be sure that no exposed portion of the DC-input power source wire extends from the power and relay connector. blank.gifStatement 122

7.blank.gif Insert the twisted-pair wire leads into the terminal block line and neutral connections.

8.blank.gif Insert the wire (labeled number 1 in Figure 21) lead into the neutral wire connection and the wire (labeled number 2 in Figure 21) lead into the line wire connection.

Ensure that only wire with insulation extends from the connectors. See Figure 21.

9.blank.gif Tighten the line and neutral terminal block screws to 8 in.-lb torque.

note: Do not exceed 10 in-lb torque.

10.blank.gif Connect the red wire to the positive pole of the DC power source, and connect the black wire to the return pole.

Ensure that each pole has a current-limiting-type fuse rated to at least 600 VAC/DC (such as the KLKD Midget fuse).

Wiring the DC Power Source

Read these cautions and warnings before wiring the switch the DC power source.

Caution: This product is intended to be supplied by a Listed Class 2 power source marked with Class 2 and rated from 9.6V to 60VDC, 2.1A.

Warning: A readily accessible two-poled disconnect device must be incorporated in the fixed wiring. blank.gifStatement 1022

Warning: This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that the protective device is rated not greater than: 3A.blank.gif Statement 1005

Warning: Installation of the equipment must comply with local and national electrical codes.blank.gif Statement 1074

Warning: Before performing any of the following procedures, ensure that power is removed from the DC circuit. blank.gifStatement 1003

Warning: Only trained and qualified personnel should be allowed to install, replace, or service this equipment.blank.gif Statement 1030

Caution: For wire connections to the power and alarm connectors, you must use UL- and CSA-rated, style 1007 or 1569 twisted-pair copper appliance wiring material (AWM) wire (such as Belden part number 9318).

To wire the switch to a DC power source, follow these steps:

1.blank.gif Locate the two power connectors on the switch front panel labeled DC-A and DC-B (see Figure 22)

note: On the PoE-capable models of the switch, there is a third DC-input power connector on the switch front panel labeled PoE. See Connecting Power to the Switch PoE DC-Input (Optional).

Figure 22 Power Connector

 

331209.jpg

2.blank.gif Identify the connector positive and return DC power connections.

The labels for power connectors DC-A and DC-B are on the switch panel as displayed in Table 12.

 

Table 12 DC-A and DC-B Power Connector Labels

Label
Connection

+

Positive DC power connection

Return DC power connection

3.blank.gif Measure two strands of twisted-pair copper wire (18-to-20 AWG) long enough to connect to the DC power source.

4.blank.gif Using an 18-gauge wire-stripping tool, strip each of the two twisted pair wires coming from each DC-input power source to 0.25 inch (6.3 mm) ± 0.02 inch (0.5 mm).

Note: Do not strip more than 0.27 inch (6.8 mm) of insulation from the wire. Stripping more than the recommended amount of wire can leave exposed wire from the power connector after installation.

Figure 23 Stripping the Power Connection Wire

 

1

0.25 in. (6.3 mm) ± 0.02 in. (0.5 mm)

REV-HIGINSTL-12.jpg

5.blank.gif Remove the two captive screws that attach the power connector to the switch, and remove the power connector.

Remove both connectors if you are connecting to two power sources. See Figure 24.

Figure 24 Removing the Power Connectors from the Switch

 

332224.jpg
1

Power connectors

6.blank.gif On the power connector, insert the exposed part of the positive wire into the connection labeled “+” and the exposed part of the return wire into the connection labeled “–”. See Figure 25.

Ensure that you cannot see any wire lead. Only wire with insulation should extend from the connector.

Warning: An exposed wire lead from a DC-input power source can conduct harmful levels of electricity. Be sure that no exposed portion of the DC-input power source wire extends from the connector(s) or terminal block(s). blank.gifStatement 122

Figure 25 Inserting Wires in the Power Connector

 

332021.jpg
1

Power source positive connection

2

Power source return connection

7.blank.gif Use a ratcheting torque flathead screwdriver to torque the power connector captive screws (above the installed wire leads) to 2 in-lb (0.23 N-m). See Figure 26.

Note: Do not over-torque the power connector’s captive screws. The torque should not exceed 2 inch-lbs (0.23 N-m).

Figure 26 Torquing the Power Connector Captive Screws

 

1

Power connector captive screws

REV-HIGINSTL-15.jpg

8.blank.gif Connect the other end of the positive wire to the positive terminal on the DC power source, and connect the other end of the return wire to the return terminal on the DC power source.

When you are testing the switch, one power connection is sufficient. If you are installing the switch and are using a second power source, repeat steps 4 through 8 using the second power connector.

Figure 27 shows the completed DC-input wiring on a power connector for a primary power source and an optional secondary power source.

Figure 27 Completed DC Power Connections on the Power Connectors

 

332023.jpg

 

1

Power source A positive connection

3

Power source B positive connection

2

Power source A return connection

4

Power source B return connection

For a –48 VDC power source, this table describes the wiring connections for Figure 27.

 

1

Power source A return connection

3

Power source B return connection

2

Power source A –48 VDC connection

4

Power source B –48 VDC connection

Attaching the Power Connectors to the Switch

To attach the power connectors to the front panel of the switch, follow these steps:

1.blank.gif Insert one power connector into the DC-A receptacle on the switch front panel, and the other into the DC-B receptacle. See Figure 28.

Warning: Failure to securely tighten the captive screws can result in an electrical arc if the connector is accidentally removed. blank.gifStatement 397

Warning: When you connect or disconnect the power and/or alarm connector with power applied, an electrical arc can occur. This could cause an explosion in hazardous area installations. Be sure that all power is removed from the switch and any other circuits. Be sure that power cannot be accidentally turned on or verify that the area is nonhazardous before proceeding. blank.gifStatement 1058

Figure 28 Attaching the Power Connectors to the Switch

 

331213.jpg

 

1

DC-A power connector

3

DC-B power connector

2

DC-A power connection

4

DC-B power connection

Figure 29 Connecting the Power Connectors to the Switch

331214.jpg

 

1

DC-A power connector upper captive screw

2.blank.gif Use a ratcheting torque flathead screwdriver to tighten the captive screws on the sides of the power connectors.

When you are testing the switch, one power source is sufficient. If you are installing the switch and are using a second power source, repeat this procedure for the second power connector (DC-B), which installs just below the primary power connector (DC-A).

When you are installing the switch, secure the wires coming from the power connector so that they cannot be disturbed by casual contact. For example, use tie wraps to secure the wires to the rack.

Connecting Power to the Switch PoE DC-Input (Optional)

This procedure is applicable only to the IE 2000 switch models that are PoE capable. If you have a PoE capable IE 2000 switch and do not plan on using PoE, you do not need to attach power to the PoE DC-input connector; the switch can operate without the connection being made.

PoE-capable Switch with PoE Power Supply Module Connected shows how a second power supply is connected to the switch to support PoE.PoE-capable Switch with PoE Power Supply Module Connected.

Figure 30 PoE-capable Switch with PoE Power Supply Module Connected

 

380365.jpg

 

1

Power connector

2

PoE power connector

Warning: An exposed wire lead from a DC-input power source can conduct harmful levels of electricity. Be sure that no exposed portion of the DC-input power source wire extends from the connector(s) or terminal block(s). blank.gifStatement 122

Caution: Do not over-torque the PoE power connector’s captive screws. The torque should not exceed 2 in-lb (0.23 N-m).

Note: The input rating is 48/54VDC 2.5A.

 

1.blank.gif

Verify that power is off to the DC circuit that you are going to attach to the switch PoE DC-input connector.

This can be either of the two power supplies (AC-input or DC-input) or site source DC.

As an added precaution, place the appropriate safety flag and lockout devices at the source power circuit breaker, or place a piece of adhesive tape over the circuit breaker handle to prevent accidental power restoration while you are working on the circuit.

2.blank.gif

Locate the PoE DC-input power connector, which is labeled PoE, on the switch front panel.

3.blank.gif

Loosen the power connector’s two screws and remove the plug portion of the connector from the switch.

4.blank.gif

Measure two strands of twisted-pair copper wire (18 AWG (0.8 mm 2) long enough to connect the switch to the DC power source.

5.blank.gif

Using a wire-stripping tool, strip each of the two twisted pair wires coming from each DC-input power source to 0.25 inch (6.3 mm) ± 0.02 inch (0.5 mm).

Note: Do not strip more than 0.27 inch (6.8 mm) of insulation from the wire. Stripping more than the recommended amount of wire can leave exposed wire from the power connector after installation.

6.blank.gif

Loosen the two captive screws on the PoE power plug and insert the exposed part of the positive wire into the connection labeled “+” and the exposed part of the return wire into the connection labeled “–”.

Ensure that you cannot see any wire lead. Only wire with insulation should extend from the connector.

332021.jpg 

1—Power source positive connection
2—Power source return connection

7.blank.gif

Use a ratcheting torque flathead screwdriver to tighten the power connector captive screws (above the installed wire leads) to 2 in-lb (0.23 N-m).

332022.jpg 

1—Power connector captive screws

8.blank.gif

Connect the other end of the positive wire to the positive terminal on the DC power source, and connect the other end of the return wire to the return terminal on the DC power source.

9.blank.gif

Insert the wired power plug into the switch PoE power connector and tighten the two screws to secure the plug.

Applying Power to the Power Converter

Move the circuit breaker for the AC outlet or the DC control circuit to the on position.

The LED on the power converter front panel is green when the unit is operating normally. The LED is off when the unit is not powered or is not operating normally. After the power is connected, the switch automatically begins the power-on self- test (POST), a series of tests that verifies that the switch functions properly.

Running Boot Fast

When the switch powers on, it automatically initiates a boot fast sequence. The boot fast sequence allows the switch to boot up in less than 60 seconds. To test the switch, follow the steps in these sections:

blank.gifPowering On the Switch

blank.gifVerifying Boot Fast

blank.gifDisconnecting Power

Powering On the Switch

To apply power to a switch that is directly connected to a DC power source, locate the circuit breaker on the panel board that services the DC circuit, and switch the circuit breaker to the ON position.

Verifying Boot Fast

When you power on the switch, it automatically begins a boot fast sequence. The System LED blinks green as the Cisco IOS software image loads. If the boot fast sequence fails, the System LED turns red.

Note: Boot fast failures are usually fatal. Call Cisco TAC immediately if your switch does not complete boot fast successfully. See .

Note: You can disable the boot fast and run POST by using the Cisco IOS CLI. See the Cisco IE 2000 Switch Software Configuration Guide and the Cisco IE 2000 Switch Command Reference for more information.

Disconnecting Power

To disconnect power after successfully running boot fast, follow these steps:

1.blank.gif Turn off power to the switch.

2.blank.gif Disconnect the cables.

Installing the Switch

This section describes how to install the switch:

blank.gifInstalling the Switch on a DIN Rail

blank.gifRemoving the Switch from a DIN Rail

blank.gifInstalling the Switch on the Wall

Warning: This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. The enclosure must meet IP 54 or NEMA type 4 minimum enclosure rating standards.blank.gif Statement 1063

Warning: When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method, for all power, input and output wiring, that complies with the governing electrical codes and in accordance with the authority having jurisdiction over Class I, Division 2 installations. blank.gifStatement 1066

Caution: To prevent the switch from overheating, ensure these minimum clearances:

blank.gifTop and bottom: 2.0 in. (50.8 mm)

blank.gifExposed side (not connected to the module): 2.0 in. (50.8 mm)

blank.gifFront: 2.0 in. (50.8 mm)

Installing the Switch on a DIN Rail

The switch ships with a spring-loaded latch on the rear panel for a mounting on a DIN rail.

You can install the switch as a standalone device on the DIN rail or with the expansion modules already connected. You must connect expansion modules to the switch before installing the switch on the DIN rail.

To attach the switch to a DIN rail, follow these steps:

1.blank.gif Position the rear panel of the switch directly in front of the DIN rail, making sure that the DIN rail fits in the space between the two hooks near the top of the switch and the spring-loaded latch near the bottom.

2.blank.gif Holding the bottom of the switch away from the DIN rail, place the two hooks on the back of the switch over the top of the DIN rail. See Figure 31.

Caution: Do not stack any equipment on the switch.

Figure 31 Position the Hooks Over the DIN Rail

 

331556.jpg
1

DIN Rail

2

Switch

3.blank.gif Push the switch toward the DIN rail to cause the spring-loaded latch at the bottom rear of the switch to move down, and snap into place.

After the switch is mounted on the DIN rail, connect the power and alarm wires, as described in Connecting Alarm Circuits.

For configuration instructions about the CLI setup program, see Configuring the Switch with the CLI-Based Setup Program

For instructions on how to remove the switch from a DIN rail, see Removing the Switch from a DIN Rail.

Removing the Switch from a DIN Rail

To remove the switch from a DIN rail, follow these steps:

1.blank.gif Ensure that power is removed from the switch, and disconnect all cables and connectors from the front panel of the switch.

2.blank.gif Insert a tool such as a flathead screwdriver in the slot at the bottom of the spring-loaded latch and use it to release the latch from the DIN rail. See Figure 32.

3.blank.gif Pull the bottom of the switch away from the DIN rail, and lift the hooks off the top of the DIN rail. See Releasing the Spring-Loaded Latch from the DIN Rail.

Figure 32 Releasing the Spring-Loaded Latch from the DIN Rail

 

331953.jpg

 

1

Push latch down

4.blank.gif Remove the switch from the DIN rail.

Installing the Switch on the Wall

Use the wall mount bracket to install the switch on the wall. According to the model of your IE2000 switch, choose one of the following wall mount bracket model:

blank.gifWALLMOUNT-IE2K-04

blank.gifWALLMOUNT-IE2K-08

blank.gifWALLMOUNT-IE2K-16

To attach the switch to a wall, follow these steps.

Warning: Read the wall-mounting instructions carefully before beginning installation. Failure to use the correct hardware or to follow the correct procedures could result in a hazardous situation to people and damage to the system. blank.gifStatement 378

1.blank.gif Remove four corner screws from the switch.

2.blank.gif Allign the wall mount bracket to the rear panel of the switch. Thread the 4-40 screws provided with the wall mount kit through each of the corner bores in the bracket and then into the switch rear cover. Tighten the screws, as shown in Figure 33.

3.blank.gif Position the switch with mounted bracket against the wall in the desired location.

Figure 33 Wall Mount Bracket Installed to the Switch

 

365677.jpg
1

4-40x5/8 Phillips Flat Head Screws

2

Switch

4.blank.gif Place six screws and screw them into the wall, as shown in Figure 34.

Figure 34 Wall Mount Bracket

 

365676.jpg

 

1

Wall

After the switch is mounted on the wall, connect the power, alarm, and ground wires, as described in Wiring the DC Power Source, Connecting Alarm Circuits, and Grounding the Switch.

For configuration instructions about the CLI setup program, see Configuring the Switch with the CLI-Based Setup Program

Connecting Alarm Circuits

After the switch is installed, you are ready to connect the DC power and alarm connections.

blank.gifWiring the Protective Ground and DC Power for Alarm Circuits

blank.gifWiring the External Alarms

Wiring the Protective Ground and DC Power for Alarm Circuits

For instructions on grounding the switch and connecting the DC power, see Grounding the Switch.

Wiring the External Alarms

The switch has two alarm input and one alarm output relay circuits for external alarms. The alarm input circuits are designed to sense if the alarm input is open or closed relative to the alarm input reference pin. Each alarm input can be configured as an open or closed contact. The alarm output relay circuit has a normally open and a normally closed contact.

Alarm signals are connected to the switch through the six-pin alarm connector. Three connections are dedicated to the two alarm input circuits: alarm input 1, alarm input 2, and a reference ground. An alarm input and the reference ground wiring connection are required to complete a single alarm input circuit. The three remaining connections are for the alarm output circuit: a normally open output, a normally closed output, and a common signal. An alarm output and the common wiring connection are required to complete a single alarm output circuit.

The labels for the alarm connector are on the switch panel and are displayed in Table 13.

 

Table 13 Alarm Connector Labels (Top to Bottom)

Label
Connection

NO

Alarm Output Normally Open (NO) connection

COM

Alarm Output Common connection

NC

Alarm Output Normally Closed (NC) connection

IN2

Alarm Input 2

REF

Alarm Input Reference Ground connection

IN1

Alarm Input 1

Warning: Explosion Hazard—Do not connect or disconnect wiring while the field-side power is on; an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or that the area is nonhazardous before proceeding.blank.gif Statement 1081

Caution: The input voltage source of the alarm output relay circuit must be an isolated source and limited to less than or equal to 24 VDC, 1.0 A or 48 VDC, 0.5 A.

Note: Wire connections to the power and alarm connectors must be UL- and CSA-rated, style 1007 or 1569 twisted-pair copper appliance wiring material (AWM) wire (such as Belden part number 9318).

To wire the switch to an external alarm device, follow these steps:

1.blank.gif Remove the captive screws that hold the alarm connector on the switch, and remove the connector from the switch chassis.

Figure 35 Removing the Alarm Connector

 

332048.jpg
1

Alarm connector

2.blank.gif Measure two strands of twisted-pair wire (18-to-20 AWG) long enough to connect to the external alarm device.

You can choose between setting up an external alarm input or output circuit.

3.blank.gif Use a wire stripper to remove the casing from both ends of each wire to 0.25 inch (6.3 mm) ± 0.02 inch (0.5 mm).

Do not strip more than 0.27 inch (6.8 mm) of insulation from the wires. Stripping more than the recommended amount of wire can leave exposed wire from the alarm connector after installation.

4.blank.gif Insert the exposed wires for the external alarm device into the connections based on an alarm input or output circuit setup (see Table 13).

For example, to wire an alarm input circuit, complete the IN1 and REF connections (See Figure 36).

Figure 36 Inserting Wires into the Alarm Connector (Alarm Input Circuit)

 

332225.jpg
1

IN1 - External device connection 1

2

REF - External device connection 2

 

5.blank.gif Use a ratcheting torque flathead screwdriver to tighten the alarm connector captive screw (above the installed wire leads) to 2 in-lb (0.23 N-m). (See Figure 37.)

Note: Do not over-torque the power and alarm connectors’ captive screws. Do not exceed 2 inch-lbs (0.23 N-m) torque.

Figure 37 Securing the Alarm Connector Captive Screws

 

332046.jpg

 

6.blank.gif Repeat the above steps to insert the input and output wires of one additional external alarm device into the alarm connector.

Figure 38 shows the completed wiring for two external alarm devices. The first alarm device circuit is wired as an alarm input circuit; the IN1 and REF connections complete the circuit. The second alarm device circuit is wired as an alarm output circuit that works on a normally open contact basis; the NO and COM connections complete the circuit.

Figure 38 Completed Connections for Three External Alarm Devices on the Alarm Connector

 

332047.jpg
1

IN1 wired connection

3

COM wired connection

2

REF wired connection

4

NO wired connection

Attaching the Alarm Connector to the Switch

Warning: Failure to securely tighten the captive screws can result in an electrical arc if the connector is accidentally removed. blank.gifStatement 397

Warning: When you connect or disconnect the power and/or alarm connector with power applied, an electrical arc can occur. This could cause an explosion in hazardous area installations. Be sure that all power is removed from the switch and any other circuits. Be sure that power cannot be accidentally turned on or verify that the area is nonhazardous before proceeding. blank.gifStatement 1058

To attach the alarm connector to the front panel of the switch:

1.blank.gif Insert the alarm connector into the receptacle on the switch front panel. See Figure 39.

Figure 39 Connecting the Alarm Connector to the Switch

 

331215.jpg

 

1

Alarm connector upper captive screw

2.blank.gif Use a ratcheting torque flathead screwdriver to tighten the captive screws on the sides of the alarm connector.

Connecting Destination Ports

These section provide more information about connecting to the destination ports:

blank.gifConnecting to 10/100 and 10/100/1000 Ports

blank.gifInstalling and Removing SFP Modules

blank.gifConnecting to SFP Modules

blank.gifConnecting to a Dual-Purpose Port

Connecting to 10/100 and 10/100/1000 Ports

The switch 10/100/1000 ports automatically configure themselves to operate at the speed of attached devices. If the attached ports do not support autonegotiation, you can explicitly set the speed and duplex parameters. Connecting devices that do not autonegotiate or that have their speed and duplex parameters manually set can reduce performance or result in no linkage.

Warning: Do not connect or disconnect cables to the ports while power is applied to the switch or any device on the network because an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed from the switch and cannot be accidentally be turned on, or verify that the area is nonhazardous before proceeding.blank.gif Statement 1070

To maximize performance, choose one of these methods for configuring the Ethernet ports:

blank.gifLet the ports autonegotiate both speed and duplex.

blank.gifSet the port speed and duplex parameters on both ends of the connection.

The models that support PoE provide up to four ports of either PoE (15.4 W per port; IEEE 802.3af) or PoE+ (30 W per port; IEEE 802.3at), depending on the power source used. For more information, see .

Caution: To prevent electrostatic-discharge (ESD) damage, follow standard board and component handling procedures.

To connect to 10BASE-T, 100BASE-TX or 1000BASE-T devices, follow these steps:

1.blank.gif When connecting to workstations, servers, routers, and Cisco IP phones, connect a straight-through cable to an RJ-45 connector on the front panel. See Figure 40.

When connecting to 1000BASE-T-compatible devices, use a twisted four-pair, CAT5 or higher cable.

The auto-MDIX feature is enabled by default. For configuration information for this feature, see the Cisco IE 2000 Switch Software Configuration Guide or the Cisco IE 2000 Switch Command Reference.

Figure 40 Connecting to an Ethernet Port

 

331558.jpg
1

10/100 port

2

10/100 or 10/100/100 port (depending on model)

2.blank.gif Connect the other end of the cable to an RJ-45 connector on the other device.

The port LED turns on when both the switch and the connected device establish the link.

The port LED is amber while Spanning Tree Protocol (STP) discovers the topology and searches for loops. This can take up to 30 seconds, and then the port LED turns green. If the port LED does not turn on:

blank.gifThe device at the other end might not be turned on.

blank.gifThere might be a cable problem or a problem with the adapter installed in the attached device. For solutions to cabling problems, see Troubleshooting

3.blank.gif Reconfigure and reboot the connected device if necessary.

4.blank.gif Repeat Steps 1 through 3 to connect each device.

Installing and Removing SFP Modules

These sections describe how to install and remove SFP modules. SFP modules are inserted into SFP module slots on the front of the switch. Field-replaceable SFP modules provide the uplink interfaces, send (TX) and receive (RX).

You can use any combination of rugged SFP modules. See Table 2 for a list of supported modules. Each SFP module must be of the same type as the SFP module on the other end of the cable, and the cable must not exceed the stipulated cable length for reliable communications. See Table 2 for cable stipulations for SFP module connections.

Caution: When you use commercial SFP modules such as CWDM and 1000BX-U/D, reduce the maximum operating temperature by 59°F (15°C). The minimum operating temperature is 32°F (0°C).

Caution: To prevent electrostatic-discharge (ESD) damage, follow standard board and component handling procedures.

Warning: Do not insert and remove SFP modules while power is on; an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.blank.gif Statement 1087

Figure 41 shows an LC SFP module with a bale-clasp latch.

Caution: Do not install or remove the LC SFP module with fiber-optic cables attached because of potential damage to the cables, the cable connector, or the optical interfaces in the SFP module. Disconnect all cables before removing or installing an SFP module. Removing and installing an SFP module can shorten its useful life. Do not remove and insert SFP modules more often than is absolutely necessary.

Figure 41 LC SFP Module with Open Bale-Clasp Latch

 

86575.jpg

Figure 42 Installing an SFP Module into an SFP Module Slot

 

331559.jpg

Installing LC SFP Modules

To insert an LC SFP module into the SFP module slot:

1.blank.gif Attach an ESD-preventive wrist strap to your wrist and to a grounded bare metal surface.

2.blank.gif Find the send (TX) and receive (RX) markings that identify the correct side of the SFP module.

On some SFP modules, the send and receive (TX and RX) markings might be replaced by arrows that show the direction of the connection, either send or receive (TX or RX).

3.blank.gif Align the SFP module sideways in front of the slot opening.

4.blank.gif Insert the SFP module into the slot until the connector on the module snaps into place in the rear of the slot. See Figure 42.

5.blank.gif Remove the dust plugs from the SFP module optical ports and store them for later use.

Caution: Do not remove the dust plugs from the SFP module port or the rubber caps from the fiber-optic cable until you are ready to connect the cable. The plugs and caps protect the SFP module ports and cables from contamination and ambient light.

6.blank.gif Insert the LC cable connector into the SFP module.

Installing 1000BASE-T SFP Modules

The 1000BASE-T (copper) SFP transceiver, see Figure 43, has a bale-clasp locking mechanism that secures the transceiver in the module socket. An RJ-45 connector provides the transceiver's interface point to the network.

Figure 43 1000BASE-T SFP Transceiver

 

273166.jpg

1

RJ-45 connector

3

Open bale-clasp latch (unlocked)

2

Closed bale-clasp latch mechanism (locked)

 

 

Caution: To comply with GR-1089 intrabuilding lightning immunity requirements, you must use grounded, shielded, twisted-pair, CAT5 cabling.

When connecting to a 1000BASE-T-compatible server, workstation, or router, use four twisted-pair, straight-through CAT5 cabling for the SFP transceiver port. When connecting to a 1000BASE-T-compatible switch or repeater, use four twisted-pair, crossover CAT5 cabling.

To install a 1000BASE-T SFP transceiver:

1.blank.gif Attach an ESD-preventive wrist strap to your wrist and to the ESD ground connector on the chassis or to a properly grounded bare metal surface.

Caution: To avoid ESD damage, handle the SFP by its sides; do not touch the connector pins.

2.blank.gif Remove the new 1000BASE-T SFP module from its protective packaging.

3.blank.gif Check the markings on the SFP transceiver to verify that you have the correct model for your network.

4.blank.gif Position the SFP transceiver in front of the port socket opening.

Note: Different Cisco devices have different SFP transceiver socket configurations. Your Cisco device might require that the SFP transceiver be installed with the bale-clasp either in a latch-up or a latch-down orientation. Verify that the SFP transceiver is oriented correctly when you position it in front of the port socket.

5.blank.gif With the bale-clasp closed (locked), slide the SFP transceiver into the socket until you feel it snap in place in the socket. You may hear an audible click as the SFP transceiver latch engages in the socket (Figure 42).

6.blank.gif Connect the network interface cable RJ-45 plug to the SFP RJ-45 connector.

7.blank.gif Observe the port status LED:

blank.gifGreen indicates that the SFP transceiver and the target device established a link.

blank.gifAmber indicates that the port is discovering the network topology and searching for loops. This process takes about 30 seconds, and then the LED turns green.

blank.gifOff indicates that the target device might not be turned on, there might be a cable problem, or there might be a problem with the adapter installed in the target device. Refer to Troubleshooting for solutions to cabling problems.

Removing SFP Modules from SFP Module Slots

To remove an SFP module from a module receptacle:

1.blank.gif Attach an ESD-preventive wrist strap to your wrist and to a grounded bare metal surface.

2.blank.gif Disconnect the LC from the SFP module.

3.blank.gif Insert a dust plug into the optical ports of the SFP module to keep the optical interfaces clean.

4.blank.gif Unlock and remove the SFP module.

If the module has a bale-clasp latch, pull the bale out and down to eject the module. If the bale-clasp latch is obstructed and you cannot use your index finger to open it, use a small, flat-blade screwdriver or other long, narrow instrument to open the bale-clasp latch. See Figure 44.

Figure 44 Opening a Bale-Clasp Latch on an SFP Module Using a Flat-Blade Screwdriver

 

331560.jpg
1

Bale clasp

5.blank.gif Grasp the SFP module between your thumb and index finger, and carefully remove it from the module slot.

6.blank.gif Place the removed SFP module in an antistatic bag or other protective environment.

Connecting to SFP Modules

This section describes how to connect to a fiber-optic or copper SFP port. To connect to an RJ-45 Gigabit Ethernet port, see Connecting to a Dual-Purpose Port. For instructions on how to install or remove an SFP module, see Installing and Removing SFP Modules.

Warning: Class 1 laser product.blank.gif Statement 1008

Warning: Do not connect or disconnect cables to the ports while power is applied to the switch or any device on the network because an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed from the switch and cannot be accidentally be turned on, or verify that the area is nonhazardous before proceeding.blank.gif Statement 1070

Caution: Do not remove the rubber plugs from the SFP module port or the rubber caps from the fiber-optic cable until you are ready to connect the cable. The plugs and caps protect the SFP module ports and cables from contamination and ambient light.

Caution: Before connecting to the SFP module, be sure that you understand the port and cabling guidelines in Preparing for Installation. See Cable and Connectors blank.giffor information about the LC on the SFP module.

Caution: To prevent ESD damage, follow standard board and component handling procedures.

Connecting to a Fiber Optic SFP Module

To connect a fiber-optic cable to an SFP module, follow these steps:

1.blank.gif Remove the rubber plugs from the module port and fiber-optic cable, and store them for future use.

2.blank.gif Insert one end of the fiber-optic cable into the SFP module port. See Figure 45.

Figure 45 Connecting to a Fiber-Optic SFP Module Port

 

331561.jpg
1

LC connector

3.blank.gif Insert the other cable end into a fiber-optic receptacle on a target device.

4.blank.gif Observe the port status LED:

blank.gifThe LED turns green when the switch and the target device have an established link.

blank.gifThe LED turns amber while the STP discovers the network topology and searches for loops. This process takes about 30 seconds, and then the port LED turns green.

blank.gifIf the LED is off, the target device might not be turned on, there might be a cable problem, or there might be a problem with the adapter installed in the target device. See Troubleshooting for solutions to cabling problems.

5.blank.gif If necessary, reconfigure and restart the switch or the target device.

Connecting to a 1000BASE-T SFP Module

Follow these steps to connect a CAT5 cable to a 1000BASE-T SFP module:

1.blank.gif When connecting to servers, workstations, and routers, insert a four twisted-pair, straight-through cable in the RJ-45 connector. When connecting to switches or repeaters, insert a four twisted-pair, crossover cable.

When connecting to a 1000BASE-T device, use a four twisted-pair CAT5 cable.

2.blank.gif Insert the other cable end in an RJ-45 connector on a target device.

3.blank.gif Observe the port status LED.

blank.gifThe LED turns green when the switch and the target device have an established link.

blank.gifThe LED turns amber while the STP discovers the network topology and searches for loops. This process takes about 30 seconds, and then the port LED turns green.

blank.gifIf the LED is off, the target device might not be turned on, there might be a cable problem, or there might be problem with the adapter installed in the target device. See Troubleshooting for solutions to cabling problems.

4.blank.gif If necessary, reconfigure and restart the switch or target device.

Connecting to a Dual-Purpose Port

The dual-purpose port is a single port with two interfaces, one for an RJ-45 cable and another for an SFP module. Only one interface can be active at a time. If both interfaces are connected, the SFP module has priority. For more information about dual-purpose ports, see Power Connectors.

Warning: Class 1 laser product. Statement 1008

Caution: Do not remove the rubber plugs from the SFP module port or the rubber caps from the fiber-optic cable until you are ready to connect the cable. The plugs and caps protect the SFP module ports and cables from contamination and ambient light.

Caution: Before connecting to the SFP module, be sure that you understand the port and cabling stipulations in Preparing for Installation. See Cable and Connectors blank.giffor information about the LC on the SFP module.

To connect to a dual-purpose port, follow these steps:

1.blank.gif Connect an RJ-45 connector to the 10/100/1000 port, or install an SFP module into the SFP module slot, and connect a cable to the SFP module port. See Figure 46.

For more information about RJ-45 connections, SFP modules, and optical connections, see Connecting to 10/100 and 10/100/1000 Ports, Installing and Removing SFP Modules, and Connecting to SFP Modules.

Figure 46 Connecting to a Dual-Purpose Port

 

331562.jpg
1

LC connector (optical)

2

RJ-45 connector (copper)

2.blank.gif Connect the other end of the cable to the other device.

By default, the switch detects whether an RJ-45 connector or SFP module is connected to a dual-purpose port and configures the port accordingly. You can change this setting and configure the port to recognize only an RJ-45 connector or only an SFP module by using the media typ e interface configuration command. For more information, see the Cisco IE 2000 Switch Command Reference.

Verifying Switch Operation

Before installing the switch in its final location, power on the switch, and verify that the switch powers up in boot fast style. The boot fast sequence allows the switch to boot up in less than 60 seconds.

Where to Go Next

If the default configuration is satisfactory, the switch does not need further configuration. You can use any of these management options to change the default configuration:

blank.gifStart Device Manager, which is in the switch memory, to manage individual and standalone switches. This is an easy-to-use web interface that offers quick configuration and monitoring. You can access Device Manager from anywhere in your network through a web browser. For more information, see Running Express Setup and the Device Manager online help.

blank.gifStart the Cisco Network Assistant application, which is described in the Getting Started with Cisco Network Assistant guide. Using the GUI, you can configure and monitor a switch cluster or an individual switch.

blank.gifUse the CLI to configure the switch as an individual switch from the console. See the Command Reference on Cisco.com for information about using the CLI.

blank.gifStart an SNMP application such as the CiscoView application.

blank.gifStart the Common Industrial Protocol (CIP) management tool. You can manage an entire industrial automation system with the CIP-based tools.