Installing Power Modules
The following procedures describe how to reinstall the power modules back into the chassis. Be sure to follow the correct procedure for the type of power modules that you have.
Caution |
Never force a power module into the power tray if you feel any resistance! The power modules are keyed to prevent AC modules from being plugged into a DC power tray or a DC module into an AC power tray. Forcing a module into the incorrect tray can cause damage to the module and the tray. |
Caution |
While performing a FPD upgrade of the ASR 9000 6kW AC Power Module Version 3 (PWR-6KW-AC-V3) and the ASR 9000 4.4kW DC Power Module Version 3 (PWR-4.4KW-DC-V3), ensure that you connect both input power cords to the power supply. If the power cords are not connected, the FPD upgrade for the power module will fail. |
Installing AC Power Modules
Prerequisites
There are no prerequisites for this task.
Required Tools and Equipment
You need the following tool to perform this task:
- 7/16 hex socket and torque wrench, torque 50 in-lb.
Steps
Follow these steps to reinstall the AC power modules back into the chassis (see Installing a Version 1 Power- Module for the version 1 power module, Installing a Version 2 or Version 3 Power Module in the Cisco ASR 9010, 9912, 9922 Routers for the version 2 and version 3 power modules, and Installing a Version 2 Power Module in the Cisco ASR 9904 Router for installing a version 2 power module in the Cisco ASR 9904 Router.
Procedure
Step 1 |
Slide the power module into the power tray until it mates with its backplane connector. |
||
Step 2 |
Secure the module:
|
||
Step 3 |
Repeat for the other AC power modules. |
||
Step 4 |
Go to Installing Fan Trays to install the fan tray.
|
Installing DC Power Modules
Required Tools and Equipment
You need the following tool to perform this task:
- 7/16 hex socket and torque wrench, torque 50 in-lb.
Steps
Follow these steps to reinstall the DC power modules back into the chassis (see Installing a Version 1 Power- Module for the version 1 power module or Installing a Version 2 or Version 3 Power Module in the Cisco ASR 9010, 9912, 9922 Routers for the version 2 or version 3 power module.
Procedure
Step 1 |
Slide the power module into the power tray until it mates with its backplane connector. |
||
Step 2 |
Secure the module:
|
||
Step 3 |
Repeat for the other DC power modules.
|