Displaying Information About the Installed Hardware Modules
Use the show hardware command to display information about the switch hardware and the hardware modules that are installed in the switch chassis.
The documentation set for this product strives to use bias-free language. For the purposes of this documentation set, bias-free is defined as language that does not imply discrimination based on age, disability, gender, racial identity, ethnic identity, sexual orientation, socioeconomic status, and intersectionality. Exceptions may be present in the documentation due to language that is hardcoded in the user interfaces of the product software, language used based on RFP documentation, or language that is used by a referenced third-party product. Learn more about how Cisco is using Inclusive Language.
Use the show hardware command to display information about the switch hardware and the hardware modules that are installed in the switch chassis.
Use the show inventory command to display information about the field replaceable units (FRUs), including product IDs, serial numbers, and version IDs. The output for this command displays information about modules that respond to command line interface (CLI) commands. The modules are supervisors, system controllers, line cards, fans, fabric modules, and power supplies. The CLI commands do not display information for modules that do not respond to those commands, such as blank modules that cover empty slots to manage airflow.
Use the show sprom backplane command to display the backplane information, including the serial number for the switch.
Use the show environment command to display all the environment-related switch information.
switch# show environment
Power Supply:
Voltage: 12.0 Volts
Power Actual Total
Supply Model Output Capacity Status
(Watts ) (Watts )
------- ------------------- ----------- ----------- --------------
1 N9K-PAC-3000W-B 0 W 3000 W shut
2 ------------ N/A W 0 W Absent
3 N9K-PAC-3000W-B 1277 W 3000 W ok
4 ------------ N/A W 0 W Absent
5 ------------ N/A W 0 W Absent
6 ------------ N/A W 0 W Absent
7 N9K-PUV-3000W-B 1312 W 3000 W ok
8 ------------ N/A W 0 W Absent
9 ------------ N/A W 0 W Absent
10 ------------ N/A W 0 W Absent
Actual Power
Module Model Draw Allocated Status
(Watts ) (Watts )
-------- ------------------- ----------- ----------- --------------
1 N9K-X9736C-FX 398 W 720 W Powered-Up
2 N9K-X9736C-FX 381 W 900 W Powered-Up
22 N9K-C9516-FM-E2 414 W 720 W Powered-Up
24 N9K-C9516-FM-E2 377 W 720 W Powered-Up
26 N9K-C9516-FM-E2 378 W 720 W Powered-Up
27 N9K-SUP-A 56 W 72 W Powered-Up
29 N9K-SC-A 12 W 24 W Powered-Up
30 N9K-SC-A 12 W 24 W Powered-Up
fantray1 N9K-C9516-FAN 83 W 444 W Powered-Up
fantray2 N9K-C9516-FAN 86 W 444 W Powered-Up
fantray3 N9K-C9516-FAN 84 W 444 W Powered-Up
N/A - Per module power not available
Power Usage Summary:
--------------------
Power Supply redundancy mode (configured) Non-Redundant(combined)
Power Supply redundancy mode (operational) Non-Redundant(combined)
Total Power Capacity (based on configured mode) 6000 W
Total Power of all Inputs (cumulative) 6000 W
Total Power Output (actual draw) 2589 W
Total Power Allocated (budget) 5168 W
Total Power Available for additional modules 831 W
switch#
Use the show module command to display information about modules that are installed in the switch chassis. This information includes module type, bootup status, MAC addresses, serial numbers, software versions, and hardware versions. Use this command to display information about all the installed modules or a specific module.
For information on all modules, use the show module command.
For information on a specific supervisor, system controller, line card, or fabric module, use the show module slot_number command to specify a slot number.
![]() Note |
To determine the slots to specify, use the show inventory command. This command reports on only software-controlled modules such as supervisors, system controllers, line cards, fabric modules, fan trays, and power supplies. It does not report on modules that are not software controlled, such as blank modules installed in empty slots to control airflow. |
This table provides descriptions of the module status that is displayed with the show module commands.
| Device | Line Card State | Status String | syslog | Description | |
|---|---|---|---|---|---|
|
Line card/FM |
powered up |
powered-up |
PLATFORM-2-MOD_PWRUP: Module 1 powered up (Serial number#) |
The hardware has electrical power. When the hardware is powered up, the software begins booting. |
|
|
Line card/FM |
testing |
testing |
No syslog |
The module has established connection with the supervisor and the module is performing bootup diagnostics. |
|
|
Line card/FM |
initializing |
initializing |
No syslog |
The diagnostics have completed successfully and the configuration is being downloaded. |
|
|
Line card/FM |
failure |
failure |
MODULE-2-MOD_DIAG_FAIL: Module 1 (Serial number:#) reported failure due to Service on linecard had a hap-reset in device DEV_SYSMGR (device error 0x335) |
The switch detects a module failure upon initialization and automatically attempts to power-cycle the module three times. After the third attempt, the module powers down. |
|
|
Line card/FM |
ok |
ok |
MODULE-5-MOD_OK: Module # is online (Serial number:#) |
The switch is ready to be configured. |
|
|
Line card/FM |
power-denied |
pwr-denied |
PLATFORM-2-MOD_PWRDENY: Module # can not be powered up due to insufficient power (Serial number#) |
The switch detects insufficient power for a line card to power up. |
|
|
Line card/FM |
power-denied |
pwr-denied |
PLATFORM-2-MOD_PWRDENY: Module # can not be powered up due to insufficient power (Serial number#) |
The switch detects insufficient power for a line card to power up. |
|
|
Line card/FM |
Powered down |
powered-dn |
PLATFORM-2-MOD_PWRDN: Module # powered down (Serial number#) |
Module is powered down by user. |
|
|
Line card/FM |
Detected |
present |
PLATFORM-2-MOD_DETECT: Module # detected (Serial number#) |
Module is powered up and is detected. |
|
|
Line card/FM |
Inserted |
inserted |
No syslog |
Module is inserted. |
|
|
Line card/FM |
Power cycled /rebooted |
pwr-cycld |
No syslog |
Module is rebooted. |
|
|
active |
active |
This module is the active supervisor or system controller module and the switch is ready to be configured. |
|||
|
Supervisor Module |
Active |
active* |
MODULE-5-ACTIVE_SUP_OK: Supervisor 27 is active (Serial number:#) |
This module is the active supervisor or system controller module and the switch is ready to be configured. |
|
|
Supervisor Module |
HA-standby |
ha-standby |
MODULE-5-STANDBY_SUP_OK: Supervisor 28 is standby |
The HA switchover mechanism is enabled on the standby supervisor module. |
|
|
Supervisor Module |
powered up |
powered-up |
The switchover mechanism is enabled on the standby system controller module. |
||
|
System Controller |
Standby |
standby |
MODULE-5-MOD_OK: Module 29 is online (Serial number:#) |
The system controller is on standby. |
|
|
System Controller |
Active |
active |
MODULE-5-MOD_OK: Module 29 is online (Serial number:#) |
The system controller is active. |
|
|
System Controller |
Power cycled/rebooted |
pwr-cycld |
No Syslog |
The system controller is rebooted. |
Use the show module [slot_number] command to display information about all the installed modules or for the module that you specify by its slot number.
![]() Note |
This example shows how to display information about a module in a specific slot (slot 4) of the chassis. |
switch# show module 4
Mod Ports Module-Type Model Status
--- ----- ----------------------------------- ------------------ ----------
4 36 36p 40G Ethernet Module N9k-X9636PQ ok
Mod Sw Hw
--- -------------- ------
4 6.1(4.11) 0.1010
Mod MAC-Address(es) Serial-Num
--- -------------------------------------- ----------
4 00-22-bd-f8-2a-83 to 00-22-bd-f8-2a-b6 SAL17257AHD
switch#
Use the show environment temperature command to display temperature readings for module temperature sensors. System controllers, supervisors, line cards, and fabric modules have temperature sensors with two thresholds.
Minor temperature threshold—When a minor threshold is exceeded, a minor alarm occurs and these actions occur for all four sensors:
Displays system messages
Sends Call Home alerts (if configured)
Sends SNMP notifications (if configured)
Major temperature threshold—When a major threshold is exceeded, a major alarm occurs and these actions occur:
For sensors 1, 3, and 4 (outlet and on-board sensors), these actions occur:
Displays system messages.
Sends Call Home alerts (if configured).
Sends SNMP notifications (if configured).
For sensor 2 (intake sensor), these actions occur:
If the threshold is exceeded in a switching module, only that module is shut down.
If the threshold is exceeded in an active supervisor module with HA-standby or standby present, only that supervisor module is shut down and the standby supervisor module takes over.
If you do not have a standby supervisor module in your switch, you have up to 2 minutes to decrease the temperature. During this interval, the software monitors the temperature every 5 seconds and continuously sends system messages as configured.
![]() Tip |
We recommend that you install dual supervisor modules. If you are using a switch without dual supervisor modules, we recommend that you immediately replace the fan module if just one fan is not working. |
![]() Note |
A threshold value of –127 indicates that no thresholds are configured or applicable. |
![]() Note |
This command reports on only software-controlled modules, such as supervisors, system controllers, line cards, fabric modules, fan trays, and power supplies. It reports on modules that are not controlled by software, such as blank modules installed in empty slots to control airflow. |
Use the show environment temperature command to display the temperature readings for each of the powered-up modules.
switch# show environment temperature
Temperature:
--------------------------------------------------------------------
Module Sensor MajorThresh MinorThres CurTemp Status
(Celsius) (Celsius) (Celsius)
--------------------------------------------------------------------
4 CPU 105 95 32 Ok
4 TD2-1 105 95 41 Ok
4 TD2-2 105 95 41 Ok
4 TD2-3 105 95 41 Ok
4 VRM-1 110 100 41 Ok
4 VRM-2 110 100 45 Ok
4 VRM-3 110 100 40 Ok
22 CPU 105 95 34 Ok
22 TD2-1 105 95 45 Ok
22 TD2-2 105 95 41 Ok
22 VRM-1 110 100 49 Ok
22 VRM-2 110 100 47 Ok
27 OUTLET 75 55 29 Ok
27 INLET 60 42 20 Ok
27 CPU 90 80 27 Ok
28 OUTLET 75 55 27 Ok
28 INLET 60 42 22 Ok
28 CPU 90 80 33 Ok
29 CPU 105 95 40 Ok
30 CPU 105 95 34 Ok
switch#
Use the attach module slot_number command to connect to any module. When the module prompt appears, obtain further details about the module by using module-specific commands in EXEC mode.
Use the attach module command to display the standby supervisor module information, although you cannot configure the standby supervisor module using this command.
![]() Note |
To see which slots are filled with modules, use the show inventory command. |
Use the attach module slot_number command to get direct access to a specific module.
This example shows how to attach to the supervisor in slot 28.
switch# attach module 28
Attaching to module 28 ...
To exit type 'exit', to cancel type '$.'
Cisco Nexus Operating System (NX-OS) Software
TAC support: http://www.cisco.com/tac
Copyright (c) 2002-2013, Cisco Systems, Inc. All rights reserved.
The copyrights to certain works contained in this software are
owned by other third parties and used and distributed under
license. Certain components of this software are licensed under
the GNU General Public License (GPL) version 2.0 or the GNU
Lesser General Public License (LGPL) Version 2.1. A copy of each
such license is available at
http://www.opensource.org/licenses/gpl-2.0.php and
http://www.opensource.org/licenses/lgpl-2.1.php
switch(standby)#
![]() Note |
To exit the module-specific prompt, use the exit command. |
![]() Tip |
If you are not accessing the switch from a console terminal, this command is the only way to access the standby supervisor module. |
![]() Note |
This command reports on only software-controlled modules, such as supervisors, system controllers, line cards, fabric modules, fan trays, and power supplies. It reports on modules that are not controlled by software, such as blank modules installed in empty slots to control airflow. |
Use the copy running-config startup-config command from EXEC mode to save the new configuration to nonvolatile storage. Once you enter this command, the running and the startup copies of the configuration are identical.
This table lists various scenarios when module configurations are preserved or lost.
|
Scenario |
Result |
|---|---|
|
A particular switching module is removed and you used the copy running-config startup-config command. |
The configured module information is lost. |
|
A particular switching module is removed and a different switching module is replaced and you used the copy running-config startup-config command. |
The configured module information is lost. |
|
A particular switching module is removed and the same switching module is replaced before you enter the copy running-config startup-config command again. |
The configured module information is preserved. |
|
A particular switching module is removed and replaced with the same type switching module, and you entered the reload module slot_number command. |
The configured module information is preserved. |
|
A particular switching module is reloaded when you enter the reload module slot_number command. |
The configured module information is preserved. |
To shut down a module, use the poweroff module command to specify the module by its slot number in the chassis.
To power up a module, use the no poweroff module command to specify the module by its slot number in the chassis.
![]() Note |
To determine the slot number for a module, use the show inventory command. |
![]() Note |
Use this command with software-controlled modules, such as supervisors, system controllers, line cards, fabric modules, fan trays, and power supplies. It does not work with modules that are not controlled by software, such as blank modules installed in empty slots to control airflow. |
|
Step 1 |
Use the configure terminal to enter the global configuration mode. Example:
|
|
Step 2 |
Enter the [no] poweroff module slot_number command to shut down (or alternatively power up) a specific module. Example:
Example:
|
Verify that either the system controller, line card, or fabric slot is empty or that the module that is installed in the slot is powered down.
Clear the running configuration for a system controller, line card, or fabric slot (slots 1 to 30) that is not functioning. To clear the configuration, use the purge module command in EXEC mode.
![]() Note |
This command does not work on supervisor slots or on any line card slot that currently has a powered-up module or on blank modules. Use the purge module slot_number runnning-config command to clear the running configuration for the specified line card slot. |
switch# purge module 4 running-config
For example, suppose that you create an IP storage configuration with a line card in slot 3 of Switch A. This module uses an IP address. You decide to remove this line card module and move it to Switch B, and you no longer need the IP address. If you try to configure this unused IP address, you receive an error message that prevents you from proceeding with the configuration. In this case, you enter the purge module 3 running-config command to clear the old configuration in Switch A, before using the IP address.
To display the power usage information for the entire switch, use the show environment power command. This command shows the power usage for the power consuming modules that are installed in the switch.
![]() Note |
Power usage is reserved for both supervisor modules, regardless of whether one or both supervisor modules are present. |
Use the show environment power command to display power usage information for the switch.
To reset a module, use the reload module slot_number command and specify the module by its slot number in the chassis.
![]() Caution |
Reloading a module disrupts traffic through the module. |
![]() Note |
To see which slots are filled with modules, use the show inventory command. |
![]() Note |
These commands report on only software-controlled modules, such as supervisors, system controllers, line cards, fabric modules, fan trays, and power supplies. Modules that are uncontrolled by software, such as blank modules installed in empty slots to control airflow are not reported on. |
|
Step 1 |
Use the configure terminal command to enter the global configuration mode. Example:
|
|
Step 2 |
Use the reload module slot_number command to specify the slot number of the module to reset. Example:
|
To reboot or reload the switch, use the reload command without any options.
![]() Note |
Save the running configuration first. If you use the reload command, use the copy running-config startup-config command. |
|
Step 1 |
Use the configure terminal command to enter the global configuration mode. Example:
|
|
Step 2 |
Use the copy running-config startup-config command to save the running configuration. Example:
|
|
Step 3 |
Use the reload command to reload the switch. Example:
|
The switch has one or two supervisor modules of these types:
Supervisor A (N9K-SUP-A) modules with four cores, 4 executable threads, 16 GB of memory, and 64 GB of SSD)
Supervisor A+ (N9K-SUP-A+) with four cores, 8 executable threads, 1.8 GHz, 16 GB of memory, and 64 GB of SSD
Supervisor B (N9K-SUP-B) with six cores, 12 executable threads, 2.2 GHz, 24 GB of memory, and 256 GB of SSD
Supervisor B+ (N9K-SUP-B+) with six cores, 12 executable threads, 1.9 GHz, 32 GB of memory, and 256 GB of SSD
When a switch has two supervisors, one supervisor is automatically active while the other is in standby mode. If the active supervisor goes down or is disconnected for replacement, the standby supervisor automatically becomes active. If you replace one of two installed supervisor modules with another module, you can do so without interrupting operations. The supervisor that you are not replacing becomes the active supervisor and retains the kickstart configuration while you replace the other supervisor. If the switch has just one supervisor, you can install the new supervisor in the open supervisor slot during operations. Make that supervisor active after the installation.
![]() Note |
If there are two supervisors that are installed in the chassis, both must be the same type as shown in this table:
|
Supervisor modules are automatically powered up and started with the switch.
To understand the terms that are used for the supervisors, see this table.
|
Module Terms |
Usage |
Description |
|---|---|---|
|
module-27 and module-28 |
Fixed |
|
|
sup-1 and sup-2 |
Fixed |
|
|
sup-active and sup-standby |
Relative |
|
|
sup-local and sup-remote |
Relative |
If you are logged into the active supervisor, this applies:
If you are logged into the standby supervisor, this applies:
|
Configure the power modes to either use (redundancy mode for when there is a power loss, or the combined power that is provided by the installed power supply units (no power redundancy):
This mode allocates one power supply as a reserve power supply in case an available power supply fails. The remaining power supplies are allocated for available power. The reserve power supply must be at least as powerful as each power supply used for the available power. Use the ps-redundant command to activate this mode.
For example, if a switch requires 2.0 kW of available power and the switch has three power supplies that each output 3 kW, then one of the power supplies provides 3.0 kW of available power and one power supply provides 3.0 kW of reserve power, in case a power supply fails.
This mode insures load sharing, but the budget becomes half the total PSU capacity. Use a different power source for the active and reserve power sources, so that if the power source that is used for active power fails, the reserve power supply can provide power for the switch. To activate this mode, use the insrc-redundant command.
For example, if the switch requires 4.0 kW of power, the switch has four power supplies that each output 3 kW. If you have two power grids, you use both grid A and grid B to power four 3-kW power supplies that provide the available power for the switch.
This mode allocates the combined power of all power supplies to active power for switch operations. This mode does not allocate reserve power for power redundancy in case of power outages or power supply failures. This mode is not recommended for production.
The amounts of available and reserve power depend on the power redundancy mode that you specify. The amounts of available and reserve power also depends on the number of power supplies that are installed in the switch. For each redundancy mode, consider:
The power supply that outputs the most power provides the reserve power so that it can take over for any other power supply that fails. All the other installed power supplies provide the available power. You activate this power mode by using the power redundancy-mode ps-redundant command.
For example, if the power requirement for a switch is 5.2 kW and the switch has two 3.0-kW power supplies outputting 3.0 kW each, consider these power planning scenarios:
Scenario 1—No added power supplies
One 3-kW power supply provides the reserve power and the other 3-kW power supply, also outputting 3.0 kW, provides the available power. The available power (3.0 kW) does not meet the switch requirements of 5.2 kW, so the switch powers up, except for some of its line cards.
Scenario 2—Adding one 3-kW power supply
One 3-kW power supply, which outputs 3.0 kW, provides the reserve power and the other two 3-kW power supplies, also outputting 3.0 kW each, provide enough power (6.0 kW) to meet the switch requirements (5.2 kW), so the entire switch powers up.
The table shows the results for each scenario.
| Scenario | Power Requirement | Output (kW) for Power Supplies | Available Power | Reserve Power | Result | ||
|---|---|---|---|---|---|---|---|
| 1 | 2 | 3 | |||||
|
1 |
5.2 kW |
3.0 kW |
3.0 kW |
— |
3.0 kW |
3.0 kW |
Available power is less than the power requirement for the switch. You cannot power the entire switch (some of the line cards will not power up). |
|
2 |
5.2 kW |
3.0 kW |
3.0 kW |
3.0 kW |
6.0 kW |
3.0 kW |
Available power exceeds the power requirement for the switch, so the entire switch powers up. |
For grid redundancy mode, the power supplies must be divided into two equal sets and installed as:
Slots PS 1 to PS 5 must be connected to one grid (Grid A)
Slots PS 6 to PS 10 must be connected to another grid (Grid B)
Half of the 3-kW power supplies are connected to one power source (grid) and the other half are connected to another power source. The available power is provided by one power source and the reserve power is provided by the other power source. If the power source that provides the available power fails, the switch uses the reserve power source to provide its required power. To activate this power mode, use the power redundancy-mode insrc_redundant command.
For example, if the power requirement for a switch is 5.2 kW and the switch has two power supplies that output 3 kW, consider these power planning scenarios:
Scenario 1—No added power supplies
The available power is 3.0 kW (output from one 3-kW power supply) and the reserve power is 3.0 kW (output from the other power supply). The available power (3.0 kW) does not meet the switch requirements (5.2 kW), so most of the modules power up, but some of the line cards will not power up.
Scenario 2—Adding two 3-kW power supplies
The available power is 6.0 kW (output from two 3-kW power supplies on grid A) and the reserve power is 6.0 kW (output from the other two power supplies on grid B). The available power (6.0 kW) exceeds the power requirement of the switch (5.2 kW), so the entire switch powers up.
The table shows the results for each scenario.
| Scenario | Power Requirement | Output for Power Supplies | Available Power | Reserve Power | Result | |||
|---|---|---|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | |||||
|
1 |
5.2 kW |
3.0 kW |
3.0 kW |
— |
— |
3.0 kW |
3.0 kW |
Available power (3.0 kW) is less than the power requirement for the switch (5.2 kW)—switch powers up, but some of the line cards cannot power up. |
|
2 |
5.2 kW |
3.0 kW |
3.0 kW |
3.0 kW |
3.0 kW |
6.0 kW |
6.0 kW |
Available power (6.0 kW) exceeds the power requirement for the switch (5.2 kW)—the entire switch powers up. |
The Total Power Capacity equals the combined output of all installed power supplies. There is no reserve power. To activate this mode, use the power redundancy-mode combined command. If the Total Power Allocated (budget) for a switch is 5.2 kW and the switch has one 3-kW power supply with 220-V input and 3.0-kW output, consider these power planning scenarios:
Scenario 1—No added power supplies
If you do not add a power supply unit, the available power (3.0 kW) is insufficient for the switch power requirement of 5.2 kW. The switch powers the supervisor modules, system controllers, fan trays, and at least one fabric module before powering as many of the fabric and line cards as the remaining available power can support (one or more fabric or line cards might not be powered).
Scenario 2—Install an extra 3-kW power supply
If you install an extra 3-kW power supply unit that can output 3.0 kW, the available power becomes 6.0 kW. The increased amount of available power exceeds the switch power requirement of 5.2 kW, so all the modules and fan trays in the switch power up.
The table shows the results for each scenario.
| Scenario | Power Requirement | Power Supply 1 Output | Power Supply 2 Output | Available Power | Reserve Power | Result |
|---|---|---|---|---|---|---|
|
1 |
5.2 kW |
3.0 kW |
— |
3.0 kW |
— |
Available power is less than the power requirement for the switch. You cannot power the entire switch. Some of the line cards will not power up. |
|
2 |
5.2 kW |
3.0 kW |
3.0 kW |
6.0 kW |
— |
Available power exceeds the power requirement for the switch, so the entire switch powers up. |
To configure the power supply mode, use the power redundancy-mode command.
![]() Note |
To display the current power supply configuration, use the show environment power command. |
For grid redundancy mode, divide and install the power supplies into two equal sets.
Slots PS 1 to PS 5 must be connected to one grid (Grid A).
Slots PS 6 to PS 10 must be connected to another grid (Grid B).
|
Step 1 |
Use the configure terminal command to enter the global configuration mode. Example:
|
|
Step 2 |
Use the power redundancy-mode mode command to specify one of these power modes:
Example:
|
Fan trays provide airflow through the switch for cooling. Each fan tray contains multiple fans to provide redundancy. The switch can continue functioning in these situations:
One or more fans fail within a fan tray—Even with multiple fan failures, the switch can continue functioning. When a fan fails within a tray, the functioning fans in the module increase their speed to compensate for the failed fans.
The fan tray is removed for replacement—The fan tray is removed and replaced while the switch is operating without presenting an electrical hazard or damage to the switch. The switch can operate for three minutes without the fan tray that you are replacing, but if the switch air-inlet temperature is less than 86 degrees Fahrenheit (30 degrees Celsius), you have up to 72 hours to replace the fan tray. Because temperatures can change over time, we recommend that you replace the fan tray within three minutes.
If you remove more than one fan tray at a time, the switch can operate up to three minutes before shutting down. To prevent a shutdown, remove only one fan tray at a time.
![]() Note |
When a fan fails or when you remove a fan tray, the remaining operating fans speed up to compensate for the loss of fans. This process can increase the noise that is made by the fan trays until you replace the missing fan tray or replace the defective fan tray. |
![]() Note |
When replacing a failed fan tray in a running system, be sure to replace the fan tray promptly. |
![]() Tip |
If one or more fans fail within a fan tray, the Fan Status LED turns red. A fan failure could lead to temperature alarms if not corrected immediately. |
The software is continuously monitoring the fan status. In a fan failure, these actions occur:
System messages are displayed.
Call Home alerts are sent (if configured).
SNMP notifications are sent (if configured).
To display the fan module statuses, see Displaying the Status for the Fan Trays.
![]() Note |
The fan trays fill slots FAN 1, FAN 2, and FAN 3 in the chassis. |
To display the status of the fan trays, use the show environment fan command.
![]() Note |
If the status is not reported for a fan tray and the status LED is not lit for that installed fan tray, check to be sure that there is a fabric module that is installed behind the fan tray. There must be a functioning fabric module installed behind that fan tray for the fan tray to power up. |