Environmental Specifications
Environment |
Specification |
|
---|---|---|
Temperature |
Ambient operating temperature |
32 to 104°F (0 to 40°C) |
Ambient nonoperating |
–40 to 158°F (–40 to 70°C) |
|
Relative humidity |
Ambient (noncondensing) |
5 to 95% |
Altitude |
Operating |
0 to 13,123 feet (0 to 4,000 meters) |
Switch Dimensions
Chassis or Module |
Width |
Depth |
Height |
---|---|---|---|
Cisco Nexus 9508 chassis |
17.5 inches (44.5 cm) |
31.76 inches (80.67 cm) for chassis and handles |
22.70 inches (57.78 cm) (13 RU) |
Supervisor modules |
Without mounting brackets: 7.0 inches (17.78 cm) With mounting brackets: 8.0 inches (20.32 cm) |
Inside chassis: 20.67 inches (52.5 cm) Ejector levers outside chassis: 0.75 inches (1.9 cm) |
1.75 inches (4.4 cm) |
System controller modules |
Without mounting brackets: 6.81 inches (17.3 cm) With mounting brackets: 7.81 inches (19.84 cm) |
Inside chassis: 10.74 inches (27.28 cm) Ejector levers outside chassis: 0.75 inches (1.9 cm) |
1.42 inches (3.61 cm) |
Line cards |
17.0 inches (43.18 cm) |
Inside chassis: 16.5 inches (41.91 cm) Ejector levers outside chassis: 2.5 inches (6.35 cm) |
1.75 inches (4.4 cm) |
Fabric modules |
2.46 inches (6.25 cm) |
11.7 inches (29.72 cm) |
16.4 inches (41.66 cm) |
Fan trays |
5.04 inches (12.81 cm) |
5.12 inches (13.0 cm) |
Without mounting brackets: 16.5 inches (41.91 cm) With mounting brackets: 18.08 inches (45.92 cm) |
Power supply |
5.25 inches (13.33 cm) |
Inside chassis: 17.75 inches (44.96 cm) Ejector levers outside chassis: 0.75 inches (1.9 cm) |
1.75 inches (4.4 cm) |
Weights and Quantities for the Chassis, Modules, Fan Trays, and Power Supplies
Component |
Weight per Unit |
Quantity |
|
---|---|---|---|
Cisco Nexus 9508 Chassis (N9K-C9508) |
150.0 lb (68.2 kg) |
1 |
|
Supervisor Modules |
— |
1 or 2 |
|
– |
Supervisor A module (N9K-SUP-A) |
4.8 lb (2.2 kg) |
|
– |
Supervisor B module (N9K-SUP-B) |
6.0 lb (2.7 kg) |
|
System Controller Module (N9K-SC-A) |
1.9 lb (0.9 kg) |
2 |
|
Line cards supported by N9K-C9508-FM fabric modules |
— |
1 to 8 |
|
– |
8-port 100-Gigabit Ethernet CFP2 line card (N9K-X9408PC-CFP2) |
11.48 lb (5.2 kg) |
|
– |
32-port 40-Gigabit Ethernet QSFP+ line card (N9K-X9432PQ) |
10.85 lb (4.92 kg) |
|
– |
36-port 40-Gigabit Ethernet QSFP+ line card (N9K-X9536PQ) |
11.99 lb (5.44 kg) |
|
– |
36-port 40-Gigabit Ethernet QSFP+ aggregation line card (N9K-X9636PQ) |
11.48 lb (5.2 kg) |
|
– |
48-port 1/10-Gigabit Ethernet SFP+ and 4-port 40-Gigabit Ethernet QSFP+ line card (N9K-X9464PX) |
10.76 lb (4.88 kg) |
|
– |
48-port 1/10-GBASE-T plus 4-port 40-Gigabit Ethernet QSFP+ I/O module (N9K-X9464TX) |
10.01 lb (4.54 kg) |
|
– |
48-port 1/10-GBASE-T plus 4-port 40-Gigabit QSFP+ I/O module (N9K-X9464TX2) |
10.01 lb (4.54 kg) |
|
– |
48-port 1/10-Gigabit Ethernet SFP+ and 4-port 40-Gigabit Ethernet QSFP+ line card (N9K-X9564PX) |
11.48 lb (5.2 kg) |
|
– |
48-port 1/10-GBASE-T plus 4-port 40-Gigabit Ethernet QSFP+ I/O module (N9K-X9564TX) |
12.58 lb (5.7 kg) |
|
Line cards supported by N9K-C9508-FM-E fabric modules |
— |
1 to 8 |
|
– |
32-port 100-Gigabit Ethernet QSFP28 line card (N9K-X9732C-EX) |
12.13 lb (5.5 kg) |
|
– |
36-port 100-Gigabit Ethernet QSFP28 line card (N9K-X9736C-EX) |
11.2 lb (5.08 kg) |
|
– |
48-port 10/25-Gigabit Ethernet SFP28 and 4-port 40/100-Gigabit Ethernet QSFP28 line card (N9K-X97160YC-EX) |
12.75 lb (5.78 kg) |
|
Line cards supported by N9K-C9508-FM-R fabric modules |
— |
1 to 8 |
|
– |
36-port 100-Gigabit Ethernet QSFP28 line card (N9K-X9636C-R) |
11.48 lb (5.2 kg) |
|
– |
36-port 40-Gigabit Ethernet QSFP+ line card (N9K-X9636Q-R) |
14.0 lb (6.35 kg) |
|
-S line cards supported by N9K-C9508-FM-S fabric modules |
— |
1 to 8 |
|
– |
32-port 100-Gigabit Ethernet QSFP28 line card (N9K-X9432C-S) |
12.3 lb (5.58 kg) |
|
Fabric Modules |
— |
— |
|
– |
40-Gigabit N9K-C9508-FM fabric module - Supporting N9K-X94xx line cards - Supporting N9K-X95xx line cards - Supporting N9K-X96xx line cards |
9.59 lb (4.4 kg) |
— 6 3 4 |
– |
100-Gigabit N9K-C9508-FM-E fabric module supporting -EX line cards |
11.6 lb (5.28 kg) |
4 |
– |
100-Gigabit N9K-C9508-FM-R fabric module supporting -R line cards |
9.59 lb (4.4 kg) |
5+1 |
– |
100-Gigabit N9K-C9508-FM-S fabric module supporting -S line cards |
10.8 lb (4.9 kg) |
4 |
Fan Trays (N9K-C9508-FAN) |
8.3 lb (3.7 kg) |
3 |
|
Power Supplies |
— |
1 to 8 |
|
– |
3-kW AC Power Supply (N9K-PAC-3000W-B) |
6.2 lb (2.8 kg) |
|
– |
3-kW Universal AC/DC Power Supply (N9K-PUV-3000W-B) |
5.9 lb (2.67 kg) |
|
– |
3-kW DC Power Supply (N9K-PDC-3000W-B) |
6.4 lb (2.9 kg) |
Power Specifications
Power specifications include power requirements for the switch modules, maximum power available for the switch, power supply specifications, and power cable specifications.
- Power Requirements for Switch Modules
- Maximum Power Available to the Switch
- Power Supply Specifications
- Power Cable Specifications
Power Requirements for Switch Modules
To determine the number of power supplies required to operate all the modules in a switch, add together the maximum power amounts for each module in the switch, divide the sum by 3000 W, and if there is a fractional amount in the result, add 1 to the result. For n+1 redundancy, add one more power supply. For n+n redundancy, double the number of power supplies and provision for a second power source.
To determine the typical consumption, add together the typical power amounts for each module in the switch.
If you order new power supplies, make sure that the new power supplies use the same type of power (AC or DC) as the rest of the power supplies in the same switch. Do not use a mix of AC and DC power sources for a switch.
Component | Quantity | Typical | Maximum | |
---|---|---|---|---|
Supervisor modules |
1 or 2 |
— |
— |
|
– |
Supervisor A (N9K-SUP-A) |
69 W |
80 W |
|
– |
Supervisor B (N9K-SUP-B) (required for -R line cards) |
75 W |
90 W |
|
System controller modules (N9K-SC-A) |
2 |
13 W |
25 W |
|
Line cards supported by N9K-C9508-FM fabric modules |
1 to 8 |
— |
— |
|
– |
8-port 100-Gigabit Ethernet CFP2 line card (N9K-X9408PC-CFP2) |
310 W |
432 W |
|
– |
32-port 40-Gigabit Ethernet QSFP+ line card (N9K-X9432PQ) |
240 W |
300 W |
|
– |
36-port 40-Gigabit Ethernet QSFP+ line card (N9K-X9636PQ) |
260 W |
400 W |
|
– |
36-port 40-Gigabit Ethernet QSFP+ line card (N9K-X9536PQ) |
360 W |
400 W |
|
– |
48-port 1/10-Gigabit Ethernet SFP+ and 4-port 40-Gigabit Ethernet QSFP+ line card (N9K-X9464PX) |
160W |
240 W |
|
– |
48-port 1/10GBASE-T and 4-port 40-Gigabit Ethernet QSFP+ line card (N9K-X9464TX) |
300 W |
360 W |
|
– |
48-port 1/10GBASE-T and 4-port 40-Gigabit Ethernet QSFP+ line card (N9K-X9464TX2) |
288 W |
350 W |
|
– |
48-port 1/10-Gigabit Ethernet SFP+ and 4-port 40-Gigabit Ethernet QSFP+ line card (N9K-X9564PX) |
300 W |
400 W |
|
– |
48-port 1/10GBASE-T and 4-port 40-Gigabit Ethernet QSFP+ line card (N9K-X9564TX) |
450 W |
540 W |
|
Line cards supported by N9K-C9508-FM-E fabric modules |
1 to 8 |
— |
— |
|
– |
32-port 100-Gigabit Ethernet QSFP28 line card (N9K-X9732C-EX) |
430 W |
656 W |
|
– |
36-port 100-Gigabit Ethernet QSFP28 line card (N9K-X9736C-EX) |
632 W |
673 W |
|
– |
48-port 10/25-Gigabit Ethernet SFP28 and 4-port 40/100-Gigabit Ethernet QSFP28 line card (N9K-X97160YC-EX) |
415 W |
540 W |
|
Line cards supported by N9K-C9508-FM-R fabric modules |
1 to 8 |
— |
— |
|
– |
36-port 100-Gigabit Ethernet QSFP28 line card (N9K-X9636C-R) |
650 W |
902 W |
|
– |
36-port 40-Gigabit Ethernet QSFP+ line card (N9K-X9636Q-R) |
329 W |
456 W |
|
Line cards supported by N9K-C9508-FM-S fabric modules |
1 to 8 |
— |
— |
|
– |
32-port 100-Gigabit Ethernet QSFP28 line card (N9K-X9432C-S) |
440 W |
594 W |
|
Fabric modules |
— |
— |
— |
|
– |
40-Gigabit N9K-C9508-FM fabric modules - Supporting N9K-X95xx line cards - Supporting N9K-X94xx line cards |
— 3 4 |
176 W |
251 W |
– |
100-Gigabit N9K-C9508-FM-E fabric modules supporting -EX line cards |
4 |
455 W |
650 W |
– |
100-Gigabit N9K-C9508-FM-R fabric modules supporting -R line cards |
5+1 |
240 W |
250 W |
– |
100-Gigabit N9K-C9508-FM-S fabric modules supporting -S line cards |
4 |
340 W |
450 W |
Fan trays (N9K-C9508-FAN) |
3 |
176 W |
250 W |
Maximum Power Available to the Switch
The maximum power available for operations depends on the input power from your power source, the number and output capabilities of your power supplies, and the power redundancy mode that you use. The following table lists the amount of power available for 3-kW power supplies depending on power inputs, numbers of power supplies, and the mode used.
Power Inputs |
Power Supplies |
Combined Mode |
n+1 Redundancy Mode |
n+n Redundancy Mode |
---|---|---|---|---|
1 input (220 V) |
1 |
3000 W |
— |
— |
2 |
6000 W |
3000 W |
3000 W |
|
3 |
9000 W |
6000 W |
3000 W |
|
4 |
12000 W |
9000 W |
6000 W |
|
5 |
15000 W |
12000 W |
6000 W |
|
6 |
18000 W |
15000 W |
9000 W |
|
7 |
21000 W |
18000 W |
9000 W |
|
8 |
24000 W |
21000 W |
12000 W |
Power Supply Specifications
The subtopics that follow list the specifications for each power supply that is supported by this switch.
- 3000-W AC Power Supply Specifications
- 3000-W Universal AC/DC Power Supply Specifications
- 3000-W DC Power Supply Specifications
3000-W AC Power Supply Specifications
Property | Specification |
---|---|
Power |
3000 W |
Input Voltage |
200 to 240 VAC |
Frequency |
50 to 60 Hz |
Efficiency |
90% or greater (20 to 100% load) |
Redundancy Modes |
Combined, n+1, and n+n |
RoHS Compliance |
Yes |
Hot Swappable |
Yes |
Airflow Direction |
Port-side intake airflow |
3000-W Universal AC/DC Power Supply Specifications
Property | Specification |
---|---|
Power |
3000 W |
Input Voltage |
200 to 277 VAC or 240 to 380 VDC or |
Frequency |
47 to 63 Hz |
Efficiency |
90% or greater (20 to 100% load) |
Redundancy Modes |
Combined, n+1, and n+n |
RoHS Compliance |
Yes |
Hot Swappable |
Yes |
Airflow Direction |
Port-side intake airflow |
3000-W DC Power Supply Specifications
Property | Specification |
---|---|
Power |
3000 W |
Input Voltage |
Minimum to Maximum: -40 to -70 VDC Nominal: -48 to -60 VDC |
Frequency |
- |
Efficiency |
90% or greater (20 to 100% load) |
Redundancy Modes |
Combined, n+1, and n+n |
RoHS Compliance |
Yes |
Hot Swappable |
Yes |
Airflow Direction |
Port-side intake airflow |
Power Cable Specifications
The subtopics that follow list the specifications for supported power cables.
- 3-kW AC Power Supply Power Cord Specifications
- 3-kW Universal AC/DC Power Supply Cables
- 3-kW DC Power Supply Power Cord Specifications
3-kW AC Power Supply Power Cord Specifications
Locale | Power Cord Part Number | Cord Set Rating | Power Cord Illustration |
---|---|---|---|
Australia and New Zealand |
CAB-AC-16A-AUS |
16 A, 250 VAC |
![]() |
Peoples Republic of China |
CAB-AC-16A-CH |
16 A, 250 VAC |
![]() |
Continental Europe |
CAB-AC-2500W-EU |
16 A, 250 VAC |
![]() |
International |
CAB-AC-2500W-INT |
16 A, 250 VAC |
![]() |
Israel |
CAB-AC-2500W-ISRL |
16 A, 250 VAC |
![]() |
Japan and North America (non locking) 200-240 VAC operation |
CAB-AC-2500W-US1 |
16 A, 250 VAC |
![]() |
Japan and North America (locking) 200-240 VAC operation |
CAB-AC-C6K-TWLK |
16 A, 250 VAC |
![]() |
Power distribution unit (PDU) |
CAB-C19-CBN |
16 A, 250 VAC |
![]() |
Switzerland |
CAB-ACS-16 |
16 A, 250 VAC |
![]() |
North America |
CAB-L520P-C19-US |
NEMA L5-20 to IEC-C19 6 feet (1.8 m) |
![]() |
3-kW Universal AC/DC Power Supply Cables
Locale |
Power Cord Part Number |
Cord Set Rating |
Power Cord Illustration |
---|---|---|---|
North America |
CAB-AC-20A-SG-C20 |
250 VAC 20 A |
![]() |
North America |
CAB-HV-25A-SG-US1 |
277 VAC/ 240 VDC/ 380 VDC 25 A |
![]() |
North America |
CAB-HV-25A-SG-US2 |
277 VAC/ 240 VDC/ 380 VDC 25 A |
![]() |
3-kW DC Power Supply Power Cord Specifications
Each 3-kW DC power supply requires four customer-supplied power cables (two negative cables and two positive cables). We recommend using 6 gauge cables. Cisco supplies 6-gauge lugs for connections to the power supply. The customer must supply the connectors required to connect the cables to the DC power source.
Transceivers, Connectors, and Cables
Transceiver and Cable Specifications
To determine which transceivers, adapters, and cables are supported by this switch, see https://www.cisco.com/c/en/us/support/interfaces-modules/transceiver-modules/products-device-support-tables-list.html.
To see the transceiver specifications and installation information, see https://www.cisco.com/c/en/us/support/interfaces-modules/transceiver-modules/products-device-support-tables-list.html.
RJ-45 Connectors
The RJ-45 connector connects Category 3, Category 5, Category 5e, Category 6, or Category 6A foil twisted-pair or unshielded twisted-pair cable from the external network to the following module interface connectors:
![]() Caution | To comply with GR-1089 intrabuilding, lightning immunity requirements, you must use a foil twisted-pair (FTP) cable that is properly grounded at both ends. |
The following figure shows the RJ-45 connector.

1 |
Pin 1 |
2 |
Pin 2 |