Total AC Input Power |
3000 VA (volt-amps) per AC power supply |
Rated input voltage1 |
200-240 VAC nominal (range: 180 to 264 VAC) |
Rated input line frequency1 |
50/60 Hz nominal (range: 47 to 63 Hz) |
Input current rating1 |
15 A maximum @ 200 VAC |
Source AC service requirement1 |
20 A North America; 16 A international; 13 A UK |
Heat dissipation |
2800 W@9,544 BTU/hour |
Redundancy |
2 AC power supply modules required for 2N redundancy |
1 For each AC power supply module. |


|
|
---|---|
Total DC Input Power |
2800 W per DC power entry module |
Rated input voltage1 |
-48 VDC nominal in North America |
Input current rating1 |
40 A maximum (2x) |
Source DC service requirement1 |
Sufficient to supply the rated input current. Local codes apply. |
Redundancy |
2 DC power entry modules required for 2N redundancy |
1 For each DC power entry module. |


|
|
---|---|
Temperature |
Operating: 32° to 104°F (0° to 40°C) Nonoperating: -4° to 149°F (-20° to 65°C) |
Humidity |
Operating: 10 to 85% noncondensing Nonoperating: 5 to 95% noncondensing |
Altitude |
Operating: 0 to 10,000 ft (0 to 3,000 m) Nonoperating: 0 to 15,000 ft (0 to 4,570 m) |
Heat dissipation |
9,554 BTU/hr maximum |
Acoustic noise |
70 dBa maximum |
Shock |
Operating (halfsine): 21 in/sec (0.53 m/sec) Nonoperating (trapezoidal pulse): 20 G1 , 52 in/sec (1.32 m/sec) |
Vibration |
Operating: 0.35 Grms2 from 3 to 500 Hz Nonoperating: 1.0 Grms from3 to 500 Hz |