The switch is sensitive to variations in voltage that is supplied by the power sources. Overvoltage, undervoltage, and transients
(spikes) can erase data from memory or cause components to fail. To protect against these types of problems, ensure that there
is an earth-ground connection for the switch.
Connect the grounding pad on the switch either directly to the earth-ground connection or to a fully bonded and grounded rack.
When the chassis is properly installed in a grounded rack, the switch is grounded because it has a metal-to-metal (no paint,
stain, dirt, or anything else on it) contact to the rack. See Note to ensure proper conductivity between rack and switch
is maintained.
Alternatively, ground the chassis by using a customer-supplied grounding cable that meets your local and national installation
requirements. For U.S. installations, we recommend 6-AWG wire. Connect your grounding cable to the chassis with a grounding
lug (provided in the switch accessory kit) and to the facility ground.

Note
|
Create an electrical conducting path between the product chassis and the metal surface of the enclosure, or rack in which
it is mounted, or to a grounding conductor. Provide electrical continuity by using thread-forming type mounting screws that
remove any paint or non-conductive coatings and establish a metal-to-metal contact. Remove any paint or other non-conductive
coatings on the surfaces between the mounting hardware and the enclosure or rack. Clean the surfaces and apply an antioxidant
before installation.
|