System Specifications

Specifications

The following table lists the specifications required for installing the Secure Workload cluster. See the "Preparing the Site" chapter for more additional information about the Secure Workload M6 specifications.

Table 1. Specifications

Specification

Value

Temperature

Operating: 41 to 95°F (5 to 35°C) with derating the maximum temperature by 1°C for every 1000 ft (305 m) above sea level

Storage: -40 to 149°F (-40 to 65°C)

Humidity

Operating: 10 to 80% relative humidity with a humidity gradation of 10% per hour

Storage: 5 to 93% relative humidity

Altitude

Operating: 0 to 10,000 ft (0 to 3050 m)

Storage: 0 to 40,000 ft (0 to 12,200 m)

Power

39-RU large-form factor platform, single rack: 22,500 W

39-RU large-form factor platform, dual rack: 11,500 W for each rack

8-RU small-form factor platform: 6,500 W

Weight (1 M6)

10.13 kg (without rails)

19.25 kg (with rails)

Power Cables

The following tables list the power cables that are included with the Secure Workload M6 cluster.

Table 2. 39-RU Cluster, Single-Rack Configuration

Part Number

Description

Quantity

TA-RACK-UCS2-INT

Cisco R42612 dynamic rack with side panels

1

TA-ETH-RJ45-SINGLE

RJ-45 cable kit for a 39-RU single-rack configuration

1

TA-SFP-H10GB-CU2M

10GBASE-CU SFP+ 2-m cable

16

TA-SFP-H10GB-CU1-5

10GBASE-CU SFP+ 1.5-m cable

32

TA-QSFP-H40G-CU1M

40GBASE-CR4 passive copper 1-m cable

4

TA-SFP-H10GB-CU1M

10GBASE-CU SFP+ 1-m cable

25

TA-SFP-H10GB-CU2-5

10GBASE-CU SFP+ 2.5-m cable

20

Table 3. 39-RU Cluster, Dual-Rack Configuration

Part Number

Description

Quantity

TA-RACK-UCS2-INT

Cisco R42612 dynamic rack, with side panels

2

TA-ETH-RJ45-DUAL

RJ-45 cable kit for a 39-RU single-rack configuration

1

TA-SFP-H10GB-CU2M

10GBASE-CU SFP+ 2-m cable

15

TA-SFP-H10GB-CU1-5

10GBASE-CU SFP+ 1.5-m cable

19

TA-QSFP-H40G-CU1M

40GBASE-CR4 passive copper 1-m cable

1

TA-QSFP-H40G-CU5M

40GBASE-CR4 passive copper 5-m cable

3

TA-SFP-H10GB-CU2-5

10GBASE-CU SFP+ 2.5-m cable

12

TA-SFP-H10GB-CU5M

10GBASE-CU SFP+ 5-m cable

47

Table 4. 8-RU Cluster

Part Number

Description

Quantity

TA-RACK-UCS2-INT

Cisco R42612 dynamic rack, with side panels

1

CAB-ETH-S-RJ45

RJ-45 straight-through yellow 6-ft cable for Ethernet

6

TA-SFP-H10GB-CU1M

10GBASE-CU SFP+ 1-m cable

13

TA-SFP-H10GB-CU1-5

10GBASE-CU SFP+ 1.5-m cable

12

TA-QSFP-H40G-CU1M

40GBASE-CR4 passive copper 1-m cable

2

GLC-TE

1000BASE-T SFP transceiver module for Category 5 copper wire

6