Table Of Contents
Specifications
Rack Specifications
PDU Specifications
Specifications
Revised: January 21, 2011, OL-23865-01
Rack Specifications
Table A-1 lists the specifications for Cisco R Series Racks.
Table A-1 Specifications
Cisco R42610 Rack
Standard
Expansion
Dimensions (H x W x D)
78.74 x 24 x 43.38 in. (2000 x 610 x 1102 mm)
78.74 x 23.58 x 43.38 in. (2000 x 599 x 1102 mm)
Dimensions (H x W x D) with packaging
89 x 33 x 47 in. (2261 x 838 x 1194 mm)
89 x 33 x 47 in. (2261 x 838 x 1194 mm)
Distance from front mounting rail to rear mounting rail
29.2 in (741 mm)
29.2 in (741 mm)
Weight
299.83 lb. (136 kg)
231. 49 lb. (105 kg)
Weight with packaging
354 lb. (161 kg)
284 lb. (129 kg)
Side panels included
Yes
No
Equipment mounting capacity
42RU
42RU
Static load capacity
2100 lb. (954 kg)
2100 lb. (954 kg)
Dynamic load capacity
Not applicable
Not applicable
PDU Specifications
Table A-2 toTable A-4 list the specifications for Cisco RP Series PDUs.
Table A-2 PDU Specifications
Description
0RU strip PDU 20 C13 and 4 C19
1RU PDU 2 C13 and 4 C19
Cisco option part number
RP208-30-1P-U-2 (US) or
RP230-30-U-2 (EU)
RP208-30-1P-U-1 (US) or
RP230-32-U-1 (EU)
RU size
0
0 or 1
Input voltage
200 to 240 VAC ±10%
200 to 240 VAC ±10%
Frequency
50 to 60 Hz
50 to 60 Hz
Amperage
30 A (US) or 32 A (EU)
30 A (US) or 32 A (EU)
UL rating
24 A
24 A
Input plug
NEMA L6-30P (US) or IEC309-32 EU
NEMA L6-30P (US) or IEC309-32 (EU)
Cord length
3m
3m
Output voltage
200 to 240 VAC
200 to 240 VAC
Receptacles
20 IEC 320 C13
4 IEC 320 C19
2 IEC 320 C13
4 IEC 320 C19
Circuit breakers1 2
2 two-pole 30A (UL 489/ CSA C22.2 No. 5.1)
2 two-pole 30A (UL 489/ CSA C22.2 No. 5.1)
Safety and Environmental
Operating temperature
50 to 122° F (10 to 50° C)
Operating relative humidity
5 to 90% (noncondensing)
Operating elevation
0 to 10,000 ft. (0 to 3048m)
Storage temperature
-40 to 140°F (-40 to 60° C)
Storage relative humidity
5 to 95% (including condensing)
Storage elevation
0 to 50,000 ft. (0 to 15,240m)
Acoustics
No fan; measure 1m from surface of PDU.
Safety
IEC 60950-1 EN 60950-1 UL/CSA 60950-1
IEC 60950-1 EN 60950-1 UL/CSA 60950-1
Unit dimensions (L x W x H)
60.6 x 17.4 x 3.4 in. (1540 x 44 x 85 mm)
17.6 x 13.8 x 18 x 11.1 (447 x 350 x 45 x 5 mm)
Unit weight
12.1 lb. (5.5 kg)
11.1 lb. (5 kg)
Packaging size (H x W x D)
170 x 170 x 1720 mm
180 x 495 x 565 mm
Total weight with packaging
15.5 lb. (7 kg)
18.3 lb. (8.3 kg)
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
Safety Earthing Terminal This symbol indicates the primary safety ground.
The PDU requires a dedicated branch circuit that meets the diagram in Figure A-1 and the PDU specifications:
Figure A-1 PDU Circuit
Table A-3 PDU Power Efficiency
Current (A)
1U Power loss (W)
0U Power loss (W)
0
>0.3
>0.2
5
3
4
32
100
80
Table A-4 Connector Specifications
Connector
Server Inlet
Rated Continuous Current
C13
C14
10 A
C19
C20
16 A