Cisco R-Series Rack and RP-Series PDU Installation Guide
Specifications
Downloads: This chapterpdf (PDF - 231.0KB) The complete bookPDF (PDF - 9.44MB) | Feedback

Table of Contents

Specifications

Rack Specifications

PDU Specifications

Specifications

Rack Specifications

Table A-1 lists the specifications for Cisco R-Series Racks.

 

Table A-1 Specifications

Cisco R42610 Rack
Standard
Expansion
Dynamic

Dimensions (H x W x D)

78.74 x 24 x 43.38 in.
(2000 x 610 x 1102 mm)

78.74 x 23.58 x 43.38 in.
(2000 x 599 x 1102 mm)

78.74 x 24 x 43.38 in.
(2000 x 610 x 1102 mm)

Dimensions (H x W x D) with packaging

89 x 33 x 47 in.
(2261 x 838 x 1194 mm)

89 x 33 x 47 in.
(2261 x 838 x 1194 mm)

85 x 39 x 47 in.
(2169 x 992 x 1200 mm)

Distance from front mounting rail to rear mounting rail

29.2 in (741 mm)

29.2 in (741 mm)

29.2 in (741 mm)

Weight

299.83 lb. (136 kg)

231. 49 lb. (105 kg)

299.83 lb. (136 kg)

Weight with packaging

354 lb. (161 kg)

284 lb. (129 kg)

473 lb. (215 kg)

Side panels included

Yes

No

Yes

Equipment mounting capacity

42RU

42RU

42RU

Static load capacity

3000 lb.
(1360 kg)

3000 lb.
(1360 kg)

3000 lb.
(1360 kg)

Dynamic load capacity

Not applicable

Not applicable

2150 lb.
(975 kg)

PDU Specifications

Table A-2 to Table A-4 list the specifications for Cisco RP-Series PDUs.

 

Table A-2 PDU Specifications

Description
0RU strip PDU 20 C13 and 4 C19
1RU PDU 2 C13 and 4 C19

Cisco option part number

RP208-30-1P-U-2 (US) or

RP230-30-U-2 (EU)

RP208-30-1P-U-1 (US) or

RP230-32-U-1 (EU)

RU size

0

0 or 1

Input voltage

200 to 240 VAC ±10%

200 to 240 VAC ±10%

Frequency

50 to 60 Hz

50 to 60 Hz

Amperage

30 A (US) or
32 A (EU)

30 A (US) or
32 A (EU)

UL rating

24 A

24 A

Input plug

NEMA L6-30P (US) or IEC309-32 EU

NEMA L6-30P (US) or IEC309-32 (EU)

Cord length

3m

3m

Output voltage

200 to 240 VAC

200 to 240 VAC

Receptacles

20 IEC 320 C13

4 IEC 320 C19

2 IEC 320 C13

4 IEC 320 C19

Circuit breakers1 2

2 two-pole 30A (UL 489/
CSA C22.2 No. 5.1)

2 two-pole 30A (UL 489/
CSA C22.2 No. 5.1)

Safety and Environmental

Operating temperature

50 to 122° F (10 to 50° C)

Operating relative humidity

5 to 90% (non-condensing)

Operating elevation

0 to 10,000 ft. (0 to 3048m)

Storage temperature

-40 to 140°F (-40 to 60° C)

Storage relative humidity

5 to 95% (including condensing)

Storage elevation

0 to 50,000 ft. (0 to 15,240m)

Acoustics

No fan; measure 1m from surface of PDU.

Safety

IEC 60950-1
EN 60950-1
UL/CSA 60950-1

IEC 60950-1
EN 60950-1
UL/CSA 60950-1

Unit dimensions
(L x W x H)

60.6 x 17.4 x 3.4 in.
(1540 x 44 x 85 mm)

17.6 x 13.8 x 18 x 11.1
(447 x 350 x 45 x 5 mm)

Unit weight

12.1 lb. (5.5 kg)

11.1 lb. (5 kg)

Packaging size
(H x W x D)

170 x 170 x 1720 mm

180 x 495 x 565 mm

Total weight with packaging

15.5 lb. (7 kg)

18.3 lb. (8.3 kg)

1.To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent protection with an ampere rating in accordance with the National Electrical Code (NEC). ANSI/NFPA 70 or your local electrical code.

2.The circuit breaker must be wall mounted and easily accessible to the operator.

This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.

Safety Earthing Terminal This symbol indicates the primary safety ground.

The PDU requires a dedicated branch circuit that meets the diagram in Figure A-1 and the PDU specifications:

Figure A-1 PDU Circuit

 

 

Table A-3 PDU Power Efficiency

Current (A)
1U Power loss (W)
0U Power loss (W)

0

>0.3

>0.2

5

3

4

32

100

80

Table A-4 Connector Specifications

Connector
Server Inlet
Rated Continuous Current

C13

C14

10 A

C19

C20

16 A