Table A-1 Cisco CRS-1 8-Slot Line Card Chassis Component and Power Specifications
Supported Cards and Modules
|
8 modular services cards (MSCs
8 physical layer interface modules (PLIMs), one for each MSC
4 switch fabric cards (SFCs)
2 route processors (RPs)
2 fan trays
1 air filter
|
Power Distribution Units
|
2 AC or 2 DC power distribution units (PDUs) (cannot mix AC and DC PDUs in the chassis)
|
DC PDU
|
Supports 1 DC power entry module (PEM)
|
AC PDU
|
Supports 1 AC rectifier module
|
Maximum Power Consumption
|
This represents total input power.
|
Maximum DC
|
8.0 kW
|
Maximum AC
|
8.75 kW (Delta or Wye 3-phase)
|
|
Note Proper grounding is also required at the site to ensure that equipment is not damaged by lightning or power surges.
|
DC Power Lug Torque Ranges
|
|
Minimum torque
|
20 in-lb (2.2 N-m)
|
Maximum torque
|
30 in-lb (3.3 N-m)
|
Power Redundancy
|
|
DC
|
2N (three "A" battery plant feeds for one PDU, and three "B" battery plant feeds for the other PDU)
|
AC (Delta or Wye 3-phase)
|
2N (two independent Delta or Wye 3-phase power sources required)
|
DC Input
|
|
Nominal input voltage
|
-48 VDC North America -54 VDC Telco (RBOC) -60 VDC International (range -40.5 to -75 VDC)
|
Input current (PDU rated for 60 A)
|
56 A (nominal) 66 A at -40.5 VDC (maximum)
|
AC Input, Delta 3-phase
|
3W + PE
|
Input voltage
|
3-phase 200 to 240 VAC (nominal) (range 170 to 264 VAC, phase-to-phase)
|
Line frequency
|
50 to 60 Hz (range 47 to 63 Hz)
|
Recommended AC service (PDU rated for 24 A)
|
30 A
|
AC Input, Wye 3-phase
|
3W + N + PE
|
Input voltage
|
3-phase 200 to 240 VAC (nominal) (range 170 to 264 VAC, phase-to-neutral) (range 295 to 457 VAC, phase-to-phase)
|
Line frequency
|
50 to 60 Hz (nominal) (range 47 to 63 Hz)
|
Recommended AC service (PDU rated for 14 A)
|
16 A International 20 A North America
|