Fully Cisco® designed and engineered, the Cisco ONS 15600 Multiservice Switching Platform (MSSP) simplifies and revolutionizes bandwidth management in the metro core by allowing service providers to transparently integrate their metro core and metro edge networks, while dramatically reducing initial turnup costs.
The Cisco ONS 15600 MSSP (Figure 1) is a true multiservice switch, providing carrier-class reliability, availability, serviceability, operations, and management. The Cisco ONS 15600 MSSP combines the functionality of multiple metro systems, including SONET/SDH multiplexers and digital cross-connect network elements, in one scalable, easy-to-use platform. The Cisco ONS 15600 MSSP supports all metro topologies such as point-to-point, linear add/drop, rings, and mesh.
Figure 1. Cisco ONS 15600
Lowest First Cost
Figure 2. Optical Network Diagram
Carrier-Class Reliability and Availability
• System components - The Cisco ONS 15600 MSSP uses components with life spans that well exceed the serviceability lifetime of the five-nines reliability. The use of high-availability components minimizes the chances of a failure because of a component fault. If there is a component fault, the entire Cisco ONS 15600 system is 1:1 protected to help ensure carrier-class availability.
• Restoration time - The Cisco ONS 15600 MSSP supports less than 25ms protection switching time, a 50 percent improvement over current industry standards.
• System exposure - Exposed reset buttons produce a higher probability of vulnerability to faults caused by external forces. To remove that exposure, the Cisco ONS 15600 MSSP eliminates exposed reset buttons that could be pressed inadvertently. Furthermore, all fiber management and cable routing within the system allows room for maintenance activities yet prevents the fiber connectors from being dislodged and protects against micro-bends.
• Power - The power feeds need to be extremely robust when compared to a typical wire feed and must provide a mechanically rigid power delivery system that would be extremely difficult to displace. Each power feed to the Cisco ONS 15600 MSSP is carried over individually laminated solid metal bars that also provide an integrated approach to power filtering. These power feeds are fully redundant and fully isolated. The power feeds supply power to the A and B power bus bars, which in turn provide power to each shelf component through the redundant power backplane. If one of the power feeds fails, each shelf component automatically selects the working power backplane in an error-free transaction.
• Automatic shutdown - If both central office power feeds fail, the Cisco ONS 15600 MSSP performs an orderly, sequenced system shutdown. This "graceful shutdown" feature allows the platform to power down in an orderly and predictable manner, helping ensure that the platform sustains no damage and the system is ready to return to service when the central office/service point of presence (POP) fault is repaired.
• SONET/SDH backplane - The Cisco ONS 15600 MSSP has fully redundant backplane connectivity to the line interface cards and the cross-connect cards. The Cisco ONS 15600 MSSP traffic moves from the interface cards to the cross-connect cards and back by traffic being placed on both copies of the backplane. Each backplane trace on both copies is constantly monitored for quality. If errors are detected within the system, a hitless redundant copy switch is performed.
• Control backplane - Similar to the other data paths on the Cisco ONS 15600 MSSP, control signals are sent to each shelf component over a fully redundant control backplane. The Cisco ONS 15600 provides both processor redundancy and physical path redundancy for every control link in the system.
• Timing - The Cisco ONS 15600 MSSP provides an internal stratum 3E clock, providing extended holdover when operating in an internal timed mode. This timing or timing derived from an external BITS or line-timed source is provided to each of the shelf components through a redundant timing backplane. All timing in the system is redundant both at the card level and at the external source level.
Carrier-Class Serviceability
• Backplane connector replacement - The Cisco ONS 15600 MSSP allows for the in-service replacement of backplane connectors if they are damaged. When repair is performed properly with the supplied tool, a backplane can be safely repaired without powering the system down.
• Fully hot-swappable - All system components, including line interface cards, common cards, fan trays, power distribution units (PDUs), and customer access panels, are fully hot-swappable, allowing a service technician to add and remove components without having to remove power from the system.
Carrier-Class Operations
• Fully nonblocking connectivity - Helps ensure that all connections made through the Cisco ONS 15600 are nonblocking, thereby providing a very high degree of network reliability.
• Errorless software upgrades - There are no bit errors observable in overhead or payload streams during a software upgrade on the Cisco ONS 15600. An upgrade is normally characterized by a bulk reconfiguration of the system database and/or a replacement of system software or firmware.
• Multiarea Open Shortest Path First (OSPF) - Enables network scalability to scores of nodes directly connected to the Cisco ONS 15600 MSSP.
• Security features - Security is a top priority for every service provider, because without effective security, provisioned circuits and service provider revenue are at risk. Several security features are provided to offer adequate protection for a service provider's network:
– Firewall capability - Prevents users outside of the section data communication channel (SDCC) management network from sending traffic into the SDCC management network.
– Superuser-initiated logout - Allows the superuser to log out another user immediately.
– Password spinning - Allows a maximum number of login attempts, and blocks that username after the maximum number of attempts has been exceeded.
– Audit trail - Offers capability to archive the audit trail records.
– Timeout control - Times out a user session after a specified period of time has passed.
• Provisionable alarms - Alarm severity (critical, major, minor) as well as the service-affecting designation (rot reported, not alarmed) can be provisioned. The software also provides user-defined alarm profiles, along with a default alarm profile that is set to Telcordia or ITU specifications.
• Ease of use - The Cisco ONS 15600 MSSP software enables customers to perform operations, administration, maintenance, and provisioning (OAM&P) tasks in the most efficient manner possible. This is accomplished with such features as a Java-based craft interface (Cisco Transport Controller) self-install wizard, span upgrade wizards, and circuit provisioning wizards.
Scalability
Patented Cooling for High Port-Density Long-Reach Optics
SONET/SDH DCC Processing Power Provides Full Visibility of the Network
Management and Provisioning
Figure 3. Cisco Transport Controller
Figure 4. A-to-Z Provisioning Example
Technical Specifications
Table 1. Technical Specifications for Cisco ONS 15600 MSSP
Platform Features
Topologies Supported
• 64 UPSR/SNCP (any combination of UPSR/SNCP, BLSR/MS-SPRing, and 1+1 APS/MSP can be mixed within the allowable maximums)
• 32 two-fiber BLSR/MS-SPRing with Dual Ring Interconnect (DRI) support
• 8 OC-192 / 32 OC-48 four-fiber BLSR (4f MS-SPRing: future release)
• 64 1+1 APS/MSP, uni-or bidirectional
• Path Protected Mesh Networking (PPMN)
Node Configurations
• Multiring (mixed UPSR/SNCP, BLSR/MS-SPRing, and 1+1 APS/MSP)
• Linear ADM
• Mesh
• Regenerator
• Star/hub
User Interface - Cisco Transport Controller
• Integrated node and subnetwork GUI craft interface
• Layered graphical views - network, node, and card levels
• A-to-Z circuit routing
– Automatic internode cross-connect provisioning
– Detailed circuit map
– Protected or unprotected circuits
– Nodal diversity option
– Balanced traffic option
– Single session, multiple circuit creation
• Node auto-discovery with provisionable subnetwork domain control
• Provisionable background maps
• System inventory
• Flexible color schemes
• Data export
• Online help
• Dynamic Host Configuration Protocol (DHCP) passthrough
• PC-based client
• Familiar browser interface - Netscape Navigator or Microsoft Internet Explorer
Maintenance
• Loopbacks - facility and terminal
• Protection switching
• Database backup and restore
• Lamp test
• Test and bridging access
Performance Monitoring (SONET/SDH)
• Telcordia GR-253-CORE, G.823, G.825, G.826, G.829
• 15 minute (32 entries), 24 hour (28 entries)
• Near- and far-end reporting
• Provisionable threshold crossing alerts
• Intermediate path performance monitoring (IPPM)
• SNMP Remote Monitoring (RMON)
Alarm Monitoring and Reporting
• Shelf LEDs are: Critical, Major, Minor, Processor
• The following cards have the following LEDs:
– TSC: STAT, SRV, ACT/STBY, Line, External, Free Run, Holdover, ACO
– CXC: STAT, SRV
– SSXC: STAT, SRV
– ASAP: STAT, SRV, SD, SF, Laser On
– Fan: STAT
• Cisco Transport Controller
• Cisco Transport Manager
• Thirty-two alarm contact closures (standard) - critical, major, minor, remote
System Upgrades
• Optical span
• Ring protection
• Software (local or remote)
Timing and Synchronization
• Two BITS inputs / two BITS outputs (BITSA and BITSB, user selectable) - 1544 Kbps (G-1244-CORE) 100 ohms balanced.
• Two E1 and 64k external clock inputs / two E1 and 64k clock outputs for use in SDH environments
• Line timing
• Stratum 3E internal oscillator
• Synchronous status messaging (SSM)
Additional Features
• Path trace (J1)
• Drop and continue
• Hairpinning
• DCC tunneling
• SDH transport over SONET (STM-1, STM-4, STM-16, and STM-64)
• Provisionable alarm profiles
• TL1 gateway provisioning
• Integrated fiber routing and storage
• Node data export and printing
Network Management Interface Support
• SNMP Versions 1 and 2c
• TL1 (GR-189-CORE and GR-833-CORE)
System Access
• 10BASE-T LAN, RJ-45 front and rear, provisionable Open Shortest Path First (OSPF)
• DB9 connectors for TL1 terminal
Regulatory and Standards
Compliance
• NEBS Level 3
• GR-1089-CORE
• GR-63-CORE
• GR-253-CORE
• European Telecommunication Standards Institute (ETSI) EN300-386
• G.781, G.782, G.783, G.811, G.812, G.813
Safety
• UL 60 950
• CSA C22.2, No. 950-95
• IEC 60825 Laser Safety Class 1
EMI
• FCC Part 15 Class A
• Industry Canada ICES-003 Class A
Physical
• Shelf weight: 120 to 206 lb (54.5 to 93.6 kg)
• Shelf dimensions (H x W x D): 25 x 23.6 x 23.6 in. (635 x 600 x 600 mm)
• Rack-mounting: Up to three shelves per 7-foot NEBS 2000 rack
Environmental
• Operating temperature: 23 to 122°F (-5 to 50°C)
• Storage temperature: -40 to 158°F (-40 to 70°C)
• Relative humidity: 0 to 95%, noncondensing
• ETSI 300 019 - Class 3.2 Operation, Class 1.2 Storage
Power
• -48VDC nominal, operating range -40 to -72VDC
• Up to 70 amps
• Dual power input feeds
• Dual A and B side power monitoring