System Specifications
Environmental Specifications
Environment |
Specification |
|
---|---|---|
Temperature |
Ambient operating temperature |
32 to 104°F (0 to 40°C) |
Ambient nonoperating |
–40 to 158°F (–40 to 70°C) |
|
Relative humidity |
Nonoperating |
5 to 85% |
Altitude |
Operating |
0 to 13,123 feet (0 to 4,000 meters) |
Switch Dimensions
Switch |
Width |
Depth |
Height |
---|---|---|---|
Cisco Nexus 9396PX |
17.5 inches (44.5 cm) |
22.5 inches (57.1 cm) |
3.5 inches (8.9 cm) (2 RU) |
Switch and Module Weights and Quantities
Component |
Weight per Unit |
Quantity |
---|---|---|
Cisco Nexus 9396PX Chassis (N9K-C9396PX) |
22.45 lb (10.2 kg) |
1 |
Uplink Module – M4PC-CFP2 – M6PQ and M6PQ-E – M12PQ |
— 2.6 lb (1.2 kg) 2.0 lb (0.9 kg) 3.12 lb (1.4 kg) |
1 |
Fan Modules (fan modules that are currently shipped with the switch). – Port-side exhaust (blue) (N9K-C9300-FAN2-B) – Port-side intake (burgundy) (N9K-C9300-FAN2) |
— 1.14 lb (0.5 kg) 1.14 lb (0.5 kg) |
3 (2 for operations and 1 for redundancy) |
Fan Modules (fan modules that were previously shipped with the switch). – Port-side exhaust (blue) (N9K-C9300-FAN1-B) – Port-side intake (burgundy) (N9K-C9300-FAN1) |
— |
3 (2 for operations and 1 for redundancy) |
0.92 lb (0.4 kg) |
||
0.92 lb (0.4 kg) |
||
Power Supply module – 650-W AC port-side exhaust (blue) (N9K-PAC-650W-B) – 650-W AC port-side intake (burgundy) (N9K-PAC-650W) – 1200-W HVAC/HVDC dual-direction (white) (N9K-PUV-1200W) – 930-W DC port-side exhaust (gray) (UCS-PSU-6332-DC) – 930-W DC port-side intake (green) (UCSC-PSU-930WDC) |
— 2.42 lb (1.1 kg) 2.42 lb (1.1 kg) 2.42 lb (1.1 kg) 2.42 lb (1.1 kg) 2.42 lb (1.1 kg) |
2 (1 for operations and 1 for redundancy) |
Transceiver and Cable Specifications
To determine which transceivers, adapters, and cables are supported by this switch, see https://www.cisco.com/c/en/us/support/interfaces-modules/transceiver-modules/products-device-support-tables-list.html.
To see the transceiver specifications and installation information, see https://www.cisco.com/c/en/us/support/interfaces-modules/transceiver-modules/products-device-support-tables-list.html.
Switch Power Input Requirements
The following table lists the typical amount of power that the switch consumes. It also lists the maximum amount of power that you must provision for the switch and power supply for peak conditions.
![]() Note |
Some power supplies have capabilities that are greater than the maximum power requirements for a switch. To determine the power consumption characteristics for the switch, use the typical and maximum requirements that are listed in the following table. |
Switch | Typical Power Consumption (AC or DC) | Maximum Power Consumption (AC or DC) | Heat Dissipation Requirement |
---|---|---|---|
Cisco Nexus 9396PX |
232 W |
455 W |
1552.524 BTUs per hour |
Power Specifications
Power specifications include the specifications for each type of power supply module.
650-W AC Power Supply Specifications
These specifications apply to the following power supplies:
-
N9K-PAC-650W
-
N9K-PAC-650W-B
Characteristic | Specification |
---|---|
AC input voltage |
Nominal range: 100 and 240 VAC (Range: 90-132 VAC, 180-264 VAC) |
AC input frequency |
Nominal range: 50 to 60 Hz (Range: 47-63 Hz) |
Maximum AC input current |
7.6 A at 100 VAC 3.65 A at 208 VAC |
Maximum input volt-amperes |
760 A at 100 VAC |
Maximum output power per power supply |
650 W |
Maximum inrush current |
33 A (sub-cycle duration) |
Maximum hold-up time |
12 ms at 650 W |
Power supply output voltage |
12 VDC |
Power supply standby voltage |
12 VDC |
Efficiency rating |
Climate Savers Platinum Efficiency (80Plus Platinum certified) |
Form factor |
RSP1 |
1200-W HVAC/HVDC Power Supply Specifications
These specifications apply to the 1200-W HVAC/HVDC (N9K-PUV-1200W) power supplies.
Characteristic | Specification |
---|---|
Input voltage
|
Nominal (Range)
|
AC input frequency |
Nominal: 50 to 60 Hz (Range: 47-63 Hz) |
Maximum inrush current |
35 A (cold turn on); 70 A (hot turn on) |
Maximum output Watts
|
Per power supply
|
Power supply output voltage
|
Per power supply
|
Power supply standby voltage |
12 V at 2.5 A |
Efficiency rating |
Climate Savers Platinum Efficiency (80Plus Platinum certified) |
Form factor |
RSP1 |
930-W DC Power Supply (Port-Side Intake) Specifications
These specifications apply to the 930-W DC (UCSC-PSU-930WDC) port-side intake power supplies.
Characteristic | Specification |
---|---|
DC input voltage range |
Nominal range: -48 to -60 VDC nominal (Range: -40 to -60 VDC) |
Maximum DC input current |
23 A at -48 VDC |
Maximum input W |
1104 W |
Maximum output power per power supply |
930 W |
Maximum inrush current |
35 A (sub-cycle duration) |
Maximum hold-up time |
8 ms at 930 W |
Power supply output voltage |
12 VDC |
Power supply standby voltage |
12 VDC |
Efficiency rating |
Greater than 92% at 50% load |
Form factor |
RSP1 |
930-W DC Power Supply (Port-Side Exhaust) Specifications
These specifications apply to the 930-W DC (UCS-PSU-6332-DC) power supplies.
Characteristic | Specification |
---|---|
Maximum DC input current |
23 A at -48 VDC |
Maximum input W |
1104 W |
Maximum output power per power supply |
930 W |
Maximum inrush current |
35 A at +35° Celcius |
Maximum hold-up time |
8 ms at 50 % load |
Power supply output voltage |
12 VDC |
Power supply standby voltage |
12 VDC |
Efficiency rating |
Climate Savers Platinum Efficiency (80Plus Platinum certified) |
Form factor |
1U |
Power Cable Specifications
The following sections specify the power cables that you can order and use with this switch.
AC Power Cables Supported by NX-OS Mode Switches
Power Type | Power Cord Part Number | Cord Set Description |
---|---|---|
CAB-C13-C14-2M |
Power Cord Jumper, C13-C14 Connectors, 6.6 feet (2.0 m) |
|
CAB-C13-C14-AC |
Power cord, C13 to C14 (recessed receptacle), 10 A, 9.8 feet (3 m) |
|
CAB-C13-CBN |
Cabinet jumper power cord, 250 VAC, 10 A, C14-C13 connectors, 2.3 feet (0.7 m) |
|
Argentina |
CAB-250V-10A-AR |
250 V, 10 A, 8.2 feet (2.5 m) |
Australia |
CAB-9K10A-AU |
250 VAC, 10 A, 3112 plug, 8.2 feet (2.5 m) |
Brazil |
CAB-250V-10A-BR |
250 V, 10 A, 6.9 feet (2.1 m) |
European Union |
CAB-9K10A-EU |
250 VAC, 10 A, CEE 7/7 plug, 8.2 feet (2.5 m) |
India |
CAB-IND-10A |
10 A, 8.2 feet (2.5 m) |
Israel |
CAB-250V-10A-IS |
250 V, 10 A, 8.2 feet (2.5 m) |
Italy |
CAB-9K10A-IT |
250 VAC, 10 A, CEI 23-16/VII plug, 8.2 feet (2.5 m) |
North America |
CAB-9K12A-NA |
125 VAC, 13 A, NEMA 5-15 plug, 8.2 feet (2.5 m) |
North America |
CAB-AC-L620-C13 |
NEMA L6-20-C13, 6.6 feet (2.0 m) |
North America |
CAB-N5K6A-NA |
200/240V, 6A, 8.2 feet (2.5 m) |
Peoples Republic of China |
CAB-250V-10A-CN |
250 V, 10 A, 8.2 feet (2.5 m) |
South Africa |
CAB-250V-10A-ID |
250 V, 10 A, 8.2 feet (2.5 m) |
Switzerland |
CAB-9K10A-SW |
250 VAC, 10 A, MP232 plug, 8.2 feet (2.5 m) |
United Kingdom |
CAB-9K10A-UK |
250 VAC, 10 A, BS1363 plug (13 A fuse), 8.2 (2.5 m) |
All except Argentina, Brazil, and Japan |
NO-POWER-CORD |
No power cord included with switch |
HVAC/HVDC Power Cables Supported by ACI-Mode and NX-OS Mode Switches
Part Number |
Cord Set Description |
Photo |
---|---|---|
CAB-HVAC-SD-0.6M |
HVAC 2-foot (0.6 m) cable with Saf-D-Grid and SD connectors |
![]() |
CAB-HVAC-C14-2M |
HVAC 6.6-foot (2.0 m) cable with Saf-D-Grid and C14 connector (use for up to 240 V) |
![]() |
CAB-HVAC-RT-0.6M |
HVAC 2-foot (0.6 m) cable with Saf-D-Grid and RT connector |
![]() |
CAB-HVDC-3T-2M |
HVDC 6.6-foot (2.0 m) cable with Saf-D-Grid and three terminal connectors |
![]() |
NO-POWER-CORD |
All except Argentina, Brazil, and Japan No power cord included with switch |
Not applicable |
1 |
Connect this end to the power supply unit. |
DC Power Cable Specifications
Power Supply | Power Cord | Cord Set Description |
---|---|---|
UCSC-PSU-930WDC (port-side intake airflow) |
(customer supplied) |
8 AWG insulated cable (10 AWG minimum) for each power supply |
UCS-PSU-6332-DC (port-side exhaust airflow) |
CAB-48DC-40A-8AWG |
8-AWG cable with 3-pin keyed power supply connector and three wires (power source connection) |
All except Argentina, Brazil, and Japan |
NO-POWER-CORD |
No power cord included with switch |
Regulatory Standards Compliance Specifications
The following table lists the regulatory standards compliance for the switch.
Specification |
Description |
---|---|
Regulatory compliance |
Products should comply with CE Markings according to directives 2004/108/EC and 2006/95/EC. |
Safety |
|
EMC: Emissions |
|
EMC: Immunity |
|
RoHS |
The product is RoH-6 compliant with exceptions for leaded-ball grid-array (BGA) balls and lead press-fit connectors. |