Table B-1 Fabric Card Chassis Specifications
Chassis Dimensions
|
|
Height
|
84 in. (213.4 cm) with top power shelf installed
|
Width
|
23.6 in. (60.0 cm)
|
Depth
|
36.9 in. (93.9 cm) without cosmetic doors and cards 41.5 in. (105.4 cm) with front and rear doors
|
Overhead clearance
|
24 in. (61 cm) overhead clearance recommended. This overhead clearance includes 12 in. (30.5 cm) for the tray and 12 in. (30.5 cm) for access to the cables.
|
Chassis Weight
|
|
Chassis shipping weight
|
1075 lb (487.6 kg) fabric card chassis with shipping crate and pallet
780 lb (354 kg) chassis with fans and blanks (as shipped)
|
Chassis with power shelves only, no power modules
|
849 lb (385 kg)
|
Chassis with power shelves, power modules, and alarm modules
|
970 lb (440 kg)
|
Chassis, fully loaded with cards, without cosmetics
|
1585 lb (719 kg)
|
Chassis, fully loaded with cards and cosmetics (doors, panels, grilles, and so on)
|
1629 lb (739 kg)
|
Floor Loading
|
|
Chassis footprint
|
6.72 sq. ft (6243 sq. cm), with cosmetics and doors
|
Floor contact area
|
4.72 sq. ft (4385 sq. cm)
|
Maximum floor loading
|
Without cosmetics and doors:
1585 lb/4.72 sq. ft = 335 lb/sq. ft 719 kg/4385 sq. cm = 0.164 kg/sq. cm
With cosmetics and doors:
1695 lb/4.72 sq. ft = 359 lb/sq. ft 769 kg/4385 sq. cm = 0.175 kg/sq. cm
|
Supported Cards and Modules
|
8 S2 switch fabric cards (up to 24 cards in the future)
2 shelf controller cards (2-port or 22-port version)
2 fan trays (with 9 fans each)
1 air filter
|
Power Shelves
|
2 AC or 2 DC power shelves for each chassis (cannot mix AC and DC shelves in a chassis)
|
DC power shelf
|
Requires 2 DC power entry modules (PEMs) for each shelf
|
AC power shelf
|
Requires 3 AC rectifier modules for each shelf
|
Maximum Power Consumption (total input power)
|
|
Maximum DC
|
9.0 kW
|
Maximum AC
|
11.1 kW (Delta or Wye 3-phase)
|
| |
Note Proper grounding is also required at the site to ensure that equipment is not damaged by lightning or power surges.
|
Power Redundancy (2N)
|
|
DC
|
4 inputs of -48 or -60 VDC for each power shelf ("A" battery plant to one shelf, "B" battery plant to the other)
|
AC (Delta or Wye 3-phase)
|
2 independent Delta or Wye 3-phase power sources required, one for each power shelf.
|
DC Input
|
|
Nominal input voltage
|
-48 VDC North America -54 VDC Telco (RBOC) -60 VDC European Community (range -42 to -75 VDC)
|
Input current
|
46 A max at -48 VDC 37 A max at -60 VDC
55 A maximum at -42 VDC (low voltage extreme)
|
AC Input, Delta 3-phase
|
3W + PE (3 wire + protective earthing1 )
|
Input voltage
|
3-phase 200 to 240 VAC, phase-to-phase (nominal) (range 180 to 264 VAC, phase-to-phase)
|
Line frequency
|
50 or 60 Hz (nominal) (range 47 to 63 Hz)
|
Recommended AC service
|
60 A
|
AC Input, Wye 3-phase
|
3W + N + PE (3 wire + neutral + protective earthing1)
|
Input voltage
|
3-phase 200-240/346-415 VAC (range 180 to 264 VAC, phase-to-neutral) (range 311 to 456 VAC, phase-to-phase)
|
Line frequency
|
50 or 60 Hz (nominal) (range 47 to 63 Hz)
|
Recommended AC service
|
32 A
|