Rack and Cabinet Requirements

Want to summarize with AI?

Log in

The type of racks and cabinets to mount your switch.


Install these types of racks or cabinets for your switch:

  • Standard perforated cabinets

  • Solid-walled cabinets with a roof fan tray (bottom-to-top cooling)

  • Standard open four-post Telco racks

Work with your cabinet vendors to determine which of their cabinets meet these requirements or see the Cisco Technical Assistance Center (TAC) for recommendations:

  • Use a standard 19-inch (48.3-cm), four-post Electronic Industries Alliance (EIA) cabinet or rack with mounting rails that conform to English universal hole spacing per section 1 of the ANSI/EIA-310-D-1992 standard.

  • The depth of a four-post rack must be 24 to 32 inches (61.0 to 81.3 cm) between the front and rear mounting rails (for proper mounting of the bottom-support brackets or other mounting hardware).

You must also have power receptacles that are located within reach of the power cords that are used with the switch.