System Specifications

Environmental Specifications

Environment

Specification

Temperature

Ambient operating temperature

32 to 104°F (0 to 40°C)

Ambient nonoperating

–40 to 158°F (–40 to 70°C)

Relative humidity

Ambient (noncondensing)

5 to 95%

Altitude

Operating

0 to 13,123 feet (0 to 4,000 meters)

Switch Dimensions

Switch

Width

Depth

Height

Cisco Nexus 93180LC-EX

17.3 inches (43.9 cm)

22.5 inches (57.1 cm)

1.72 inches (4.4 cm) (1 RU)

Switch and Module Weights and Quantities

Component

Weight per Unit

Quantity

Cisco Nexus 93180LC-EX Chassis (N9K-C93180LC-EX)

17.2 lb (7.8 kg)

1

Fan Module

– Port-side intake (burgundy) (NXA-FAN-30CFM-B)

– Port-side exhaust (blue) (NXA-FAN-30CFM-F)

0.92 lb (0.4 kg)

0.92 lb (0.4 kg)

4

Power Supplies

– 500-W AC port-side intake (burgundy) (NXA-PAC-500W-PI)

– 500-W AC port-side exhaust (blue) (NXA-PAC-500W-PE)

– 1200-W HVAC/HVDC dual-direction (white) (N9K-PUV-1200W)

– 930-W DC port-side intake (burgundy) (NXA-PDC-930W-PI)

– 930-W DC port-side exhaust (blue) (NXA-PDC-930W-PE)

2.42 lb (1.1 kg)

2.42 lb (1.1 kg)

2.42 lb (1.1 kg)

2.42 lb (1.1 kg)

2.42 lb (1.1 kg)

2 (1 for operations and 1 for redundancy)

Transceiver and Cable Specifications

To determine which transceivers, adapters, and cables are supported by this switch, see http:/​/​www.cisco.com/​c/​en/​us/​support/​interfaces-modules/​transceiver-modules/​products-device-support-tables-list.html.

To see the transceiver specifications and installation information, see http:/​/​www.cisco.com/​c/​en/​us/​support/​interfaces-modules/​transceiver-modules/​products-device-support-tables-list.html.

Switch Power Input Requirements

The following table lists the typical amount of power consumed by the switch, and it lists the maximum amount of power that you must provision from the power source as input to the power supply and switch for peak conditions.


Note


Some power supplies might have UL listed capabilities that are greater than the maximum power requirements for a switch. To determine the power consumption characteristics for the switch, use the typical and maximum requirements listed in the following table.


Switch Typical Power Consumption (AC or DC) Maximum Power Consumption (AC or DC)

Cisco Nexus 93180LC-EX

220 W

500 W

Power Specifications

Power specifications include the specifications for each type of power supply module.

500-W AC Power Supply Specifications

These specifications apply to the following power supplies:

  • NXA-PAC-500W-PE

  • NXA-PAC-500W-PI

Characteristic Specification

AC input voltage

Nominal range: 100 and 240 VAC (Range: 90-132 VAC, 180-264 VAC)

AC input frequency

Nominal range: 50 to 60 Hz (Range: 47-63 Hz)

Maximum AC input current

7.6 A at 100 VAC

3.65 A at 208 VAC

Maximum input volt-amperes

760 A at 100 VAC

Maximum output power per power supply

500 W

Maximum inrush current

33 A (sub-cycle duration)

Maximum hold-up time

12 ms at 500 W

Power supply output voltage

12 VDC

Power supply standby voltage

12 VDC

Efficiency rating

Climate Savers Platinum Efficiency (80Plus Platinum certified)

Form factor

RSP1

1200-W HVAC/HVDC Power Supply Specifications

These specifications apply to the 1200-W HVAC/HVDC (N9K-PUV-1200W) power supplies.

Characteristic Specification

Input voltage

  • AC (for 1230 W output)

  • DC (for 1230 W output)

Nominal (Range)

  • 200 to 277 VAC

  • –240 to –380 VDC

AC input frequency

Nominal: 50 to 60 Hz (Range: 47-63 Hz)

Maximum inrush current

35 A (cold turn on); 70 A (hot turn on)

Maximum output Watts

  • For 200 to 277 VAC

  • For 192 to 400 VDC

Per power supply

  • 1230 W

  • 1230 W

Power supply output voltage

  • For 200 to 277 VAC

  • For 192 to 400 VDC

Per power supply

  • 12 VAC at 100 A

  • 12 VDC at 100 A

Power supply standby voltage

12 V at 2.5 A

Efficiency rating

Climate Savers Platinum Efficiency (80Plus Platinum certified)

Form factor

RSP1

930-W DC Power Supply Specifications

These specifications apply to the following power supplies:

  • NXA-PDC-930W-PE

  • NXA-PDC-930W-PI

Characteristic Specification

DC input voltage range

Nominal range: -48 to -60 VDC nominal (Range: -40 to -60 VDC

Maximum DC input current

23 A at -48 VDC

Maximum input W

1104 W

Maximum output power per power supply

930 W

Maximum inrush current

35 A (sub-cycle duration)

Maximum hold-up time

8 ms at 930 W

Power supply output voltage

12 VDC

Power supply standby voltage

12 VDC

Efficiency rating

Greater than 92% at 50% load

Form factor

RSP1

Power Cord Specifications

The following tables specify the power cables that you should order and use with AC, DC, and HVAC/HVDC power supplies.

Table 1 Power Cable Specifications for AC Power Supplies
Locale Power Cord Part Number Cord Set Description

CAB-C13-C14-2M

Power Cord Jumper, C13-C14 Connectors, 6.6 feet (2.0 m)

CAB-C13-C14-AC

Power cord, C13 to C14 (recessed receptacle), 10 A, 9.8 feet (3 m)

CAB-C13-CBN

Cabinet jumper power cord, 250 VAC, 10 A, C14-C13 connectors, 2.3 feet (0.7 m)

Argentina

CAB-250V-10A-AR

250 V, 10 A, 8.2 feet (2.5 m)

Australia

CAB-9K10A-AU

250 VAC, 10 A, 3112 plug, 8.2 feet (2.5 m)

Brazil

CAB-250V-10A-BR

250 V, 10 A, 6.9 feet (2.1 m)

European Union

CAB-9K10A-EU

250 VAC, 10 A, CEE 7/7 plug, 8.2 feet (2.5 m)

India

CAB-IND-10A

10 A, 8.2 feet (2.5 m)

Israel

CAB-250V-10A-IS

250 V, 10 A, 8.2 feet (2.5 m)

Italy

CAB-9K10A-IT

250 VAC, 10 A, CEI 23-16/VII plug, 8.2 feet (2.5 m)

North America

CAB-9K12A-NA

125 VAC, 13 A, NEMA 5-15 plug, 8.2 feet (2.5 m)

North America

CAB-AC-L620-C13

NEMA L6-20-C13, 6.6 feet (2.0 m)

North America

CAB-N5K6A-NA

200/240V, 6A, 8.2 feet (2.5 m)

Peoples Republic of China

CAB-250V-10A-CN

250 V, 10 A, 8.2 feet (2.5 m)

South Africa

CAB-250V-10A-ID

250 V, 10 A, 8.2 feet (2.5 m)

Switzerland

CAB-9K10A-SW

250 VAC, 10 A, MP232 plug, 8.2 feet (2.5 m)

United Kingdom

CAB-9K10A-UK

250 VAC, 10 A, BS1363 plug (13 A fuse), 8.2 (2.5 m)

Table 2 Power Cable Specifications for HVAC/HVDC Power Supplies

Power Type

Power Cord Part Number

Cord Set Description

HVAC

CAB-HVAC-SD-0.6M

2-foot (0.6 m) cable with Saf-D-Grid and SD connectors

HVAC

CAB-HVAC-C14-2M

6.6-foot (2.0 m) cable with Saf-D-Grid and C14 connector (use for up to 240 V)

HVAC

CAB-HVAC-RT-0.6M

2-foot (0.6 m) cable with Saf-D-Grid and RT connector

HVDC

CAB-HVDC-3T-2M

6.6-foot (2.0 m) cable with Saf-D-Grid and three terminal connectors

Table 3 Power Cable Specifications for DC Power Supplies
Power Supply Power Cord Cord Set Description

NXA-PDC-930W-PI (port-side intake airflow)

(customer supplied)

8 AWG insulated cable (10 AWG minimum) for each power supply

NXA-PDC-930W-PI (port-side intake airflow)

CAB-48DC-40A-8AWG

8-AWG cable with 3-pin keyed power supply connector and three wires (power source connection)

NXA-PDC-930W-PE (port-side exhaust airflow)

CAB-48DC-40A-8AWG

8-AWG cable with 3-pin keyed power supply connector and three wires (power source connection)