Temperature requirements
For every 300 meters (1000 feet) above sea level, the maximum temperature is reduced by 1 degree Celsius. The non-operating temperature of the switch is -40 to 158 degrees Fahrenheit (-40 to 70 degrees Celsius).
Overview of Module Temperatures
Built-in, automatic sensors in all switches in the Cisco N9000 Series monitor your switch at all times. Each module (supervisor, I/O, and fabric) has temperature sensors with two thresholds:
Note |
For any Major temperature alarms from the sensors, the switch powers down in 2 minutes. Power on the switch after fixing the temperature issue. |
-
Minor temperature threshold—If exceeded, a minor alarm occurs and these actions happen for all four sensors:
-
System messages display.
-
System sends Call Home alerts (if configured).
-
System sends SNMP notifications (if configured).
-
System fan speed will increment.
-
-
Major temperature threshold—If exceeded, a major alarm occurs and these actions happen:
If the threshold is exceeded in a switching module, only that module is shut down.
For all sensors:
-
System messages display.
-
System sends Call Home alerts (if configured).
-
System sends SNMP notifications (if configured).
-
System fan speed will increment.
-
If the major threshold is exceeded in a switching module, only that module is shut down.
-
If the major threshold is exceeded in an active supervisor module with HA-standby or standby present, only that supervisor module is shut down and the standby supervisor module takes over.
-
If you do not have a standby supervisor module in your switch, you have 2 minutes to decrease the temperature. During this interval, the software monitors the temperature every 5 seconds and continuously sends system messages every 10 seconds, as configured.
-