Catalyst 5000 Family Installation Guide (May 2000)
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Removal and Replacement Procedures
![]() |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Table of ContentsRemoval and Replacement ProceduresRemoving and Replacing the Power Supply
Removing an AC-Input Power Supply
Connecting DC-Input Wires on the Catalyst 5002 SwitchRemoving AC-Input Power from a Catalyst 5500 Power Supply
Installing an AC-Input Power SupplyRemoving an AC-Input Power Supply for Catalyst 5000, Catalyst 5505, and Catalyst 5509 Switches Removing a DC-Input Power Supply Installing a DC-Input Power Supply Removing and Replacing the Chassis Fan Assembly Removal and Replacement Procedures
This chapter describes how to perform the following removal and replacement procedures for Catalyst 5000 family field-replaceable units (FRUs):
For instructions on installing and replacing switching modules, refer to the Catalyst 5000 Family Module Installation Guide. For instructions on installing and replacing supervisor engines, supervisor engine uplink modules and Flash PC cards, refer to the Catalyst 5000 Family Supervisor Engine Installation Guide. For instructions on upgrading a Supervisor Engine III with the NetFlow Feature Card (NFFC), refer to the Catalyst 5000 Family Multilayer Switching User Guide. Removing and Replacing the Power Supply
This section describes how to remove and install power supplies for the Catalyst 5000, Catalyst 5505, Catalyst 5509, and Catalyst 5500 switches. A flat-blade screwdriver is required to perform these procedures.
Removing an AC-Input Power SupplyThis warning applies to Catalyst 5500 AC-input power supplies only.
Removing AC-Input Power from a Catalyst 5500 Power SupplyRemove power from the AC-input power supply as follows: Step 1 Remove the power cord from the building power receptacle. Do not touch the metal prongs on the power cord when it is still connected to the power connection on the power supply. Step 2 Turn off the power switch on the power supply you are removing. Step 3 Remove the power cord from the power connection on the supply. Do not touch the metal prongs embedded in the power supply. Step 4 Continue the power supply removal with Step 4 in the following procedure.
Removing an AC-Input Power Supply for Catalyst 5000, Catalyst 5505, and Catalyst 5509 Switches
To remove an AC-input power supply, follow these steps: Step 1 Turn off the power switch on the power supply you are removing. (See Figure 5-1.) (For Catalyst 5500 power supplies, follow the procedure in the "Removing AC-Input Power from a Catalyst 5500 Power Supply" section.)
Figure 5-1: AC-Input Power Supply Front Panel: Catalyst 5000, Catalyst 5505, and Catalyst 5509 Switches
Step 2 Disconnect the power cord from the power source. Step 3 Disconnect the power cord from the power supply being removed. Step 4 Use a flat-blade screwdriver to loosen and remove the captive installation screws. (See Figure 5-1 for the Catalyst 5000, Catalyst 5505, and Catalyst 5509 switches, and Figure 5-2 for the Catalyst 5500 switch.)
Figure 5-2: AC-Input Power Supply Front Panel: Catalyst 5500 Switch
Step 5 Grasp the power supply handle with one hand. Place your other hand underneath to support the bottom of the supply, as shown in Figure 5-3 (Catalyst 5000 power supply is shown). Figure 5-3: Handling an AC-Input Power Supply
Step 6 Pull the supply out of the bay and put it aside. Step 7 If the power supply bay is to remain empty, install a blank power supply filler plate over the opening; secure it with the mounting screws. Installing an AC-Input Power Supply
Follow these steps to install an AC-input power supply, connect it to a power source, and verify its operation: Step 1 Turn off the power switch on the power supply you are installing. (See Figure 5-1 for the Catalyst 5000, Catalyst 5505, and Catalyst 5509 switches, and for the Catalyst 5500 switch.)
Step 2 Grasp the power supply handle with one hand. Place your other hand underneath to support the bottom of the supply, as shown in Figure 5-3. Step 3 Slide the power supply all the way into the power supply bay. Step 4 Use a flat-blade screwdriver to tighten the captive installation screws. (See Figure 5-1 for the Catalyst 5000, Catalyst 5505, and Catalyst 5509 switches, and Figure 5-2 for the Catalyst 5500 switch.)
Step 5 Prior to connecting the power supply to a power source, ensure that all site power and grounding requirements described in "Site Planning," have been met. Step 6 Plug the power cord into the power supply. Step 7 Connect the other end of the power cord to an AC-input power source.
Step 8 Turn the power switch to the On (|) position on the power supply. Step 9 Verify power supply operation. Catalyst 5000 and Catalyst 5505 switchesVerify that the green LED on the power supply front panel is lit. This indicates that the power supply is on and receiving AC source power, providing +5, +12, and +24 VDC to internal components, and all internal voltages are within tolerance. Catalyst 5509 and Catalyst 5500 switchesVerify that the power supply front panel LEDs are in the following states:
Catalyst 5000, Catalyst 5505, Catalyst 5509, and Catalyst 5500 switches Verify that the appropriate supervisor engine module PS1 and PS2 LEDs are green. Enter the show system command to display the power supply and system status. If the LEDs or show system command indicate a power or other system problem, see "Troubleshooting the Installation," for troubleshooting information. Removing a DC-Input Power SupplyFollow these steps to remove a DC-input power supply: Step 1 Verify that power is off to the DC circuit on the power supply you are removing. Locate the circuit breaker on the panel board that services the DC circuit, switch the circuit breaker off and tape the switch handle in the off position. Step 2 Turn the power switch to the Off (0) position on the power supply you are removing. (See Figure 5-4 for the Catalyst 5000, Catalyst 5505, and Catalyst 5509 switches, and Figure 5-5 for the Catalyst 5500 switch.) Step 3 Remove the terminal block cover (see Figure 5-4 for the Catalyst 5000, Catalyst 5505, and Catalyst 5509 switches, and Figure 5-5 for the Catalyst 5500 switch). Catalyst 5000 and Catalyst 5505 switchesPress down the two plastic levers on each side of the terminal block cover and then remove the cover. Catalyst 5509 and Catalyst 5500 switchesRemove the two screws securing the terminal block cover and slide the cover straight off the terminal block. Figure 5-4: DC-Input Power Supply Front Panels: Catalyst 5000, Catalyst 5505, and Catalyst 5509 Switches
Figure 5-5: DC-Input Power Supply Front Panels: Catalyst 5500 Switch
Step 4 Disconnect the DC-input wires from the terminal block. Disconnect the ground wire last. Step 5 Use a screwdriver to loosen and remove the captive screws on the power supply. (See Figure 5-4 for the Catalyst 5000, Catalyst 5505, and Catalyst 5509 switches, and Figure 5-5 for the Catalyst 5500 switch.)
Step 6 Grasp the power supply handle with one hand. Place your other hand underneath as you slowly pull the power supply out of the bay. (See Figure 5-6.) Figure 5-6: Handling a DC-Input Power Supply
Step 7 If the bay is to remain empty, install a blank power supply filler plate (Cisco part number 700-00177-01) over the opening and secure it with the mounting screws. This protects the inner chassis from dust and prevents accidental contact with live voltage at the rear of the bay.
Step 8 Reinstall the power supply terminal block cover. Installing a DC-Input Power SupplyTo install a DC-input power supply, connect it to a power source, verify its operation, and follow these steps: Step 1 Verify that power is off to the DC circuit on the power supply you are installing. Locate the circuit breaker on the panel board that services the DC unit, switch the circuit breaker off and tape the switch handle in the off position. Step 2 Connect the switch to the central office (CO) ground through the CO ground connector shown in Figure 5-7. Remove the adhesive strip covering the CO ground connector on the switch. Use the following guidelines when connecting the switch to the CO ground:
Figure 5-7: DC-Input Power Supply CO Ground
Step 3 Turn the power switch to the Off (0) position on the power supply you are installing. (See Figure 5-4 for the Catalyst 5000, Catalyst 5505, and Catalyst 5509 switches, and Figure 5-5 for the Catalyst 5500 switch.)
Step 4 Grasp the power supply handle with one hand. Place your other hand underneath as you slowly insert the power supply into the bay. (See Figure 5-6.) Step 5 Use a screwdriver to tighten the captive screws on the power supply. (See Figure 5-4 for the Catalyst 5000, Catalyst 5505, and Catalyst 5509 switches, and Figure 5-5 for the Catalyst 5500 switch.)
Step 6 Remove the terminal block cover (see Figure 5-4 for the Catalyst 5000, Catalyst 5505, and Catalyst 5509 switches, and Figure 5-5 for the Catalyst 5500 switch). Catalyst 5000 and Catalyst 5505 switchesPress down the two plastic levers on each side of the terminal block cover and remove the cover. Catalyst 5509 and Catalyst 5500 switchesRemove the two screws securing the terminal block cover and slide the cover straight off the terminal block. Step 7 Attach the appropriate lugs to the DC-input wires. Maximum width of the lugs is 0.300 inch (7.6 mm). Suggested lugs are AMP 322985 or 52941. Suggested DC-input wires (90-degree copper conductors) are as follows:
Step 8 Connect the DC-input wires to the terminal block. Catalyst 5000 and Catalyst 5505 switchesFrom the top of the terminal block, connect the DC-input wires to the terminal block as follows (see Figure 5-8):
Figure 5-8: Catalyst 5000 and Catalyst 5505 Switches: DC-Input Power Supply Connectors
Catalyst 5509 and Catalyst 5500 switchesRoute the DC-input power cable through the conduit from your power source, through the conduit bracket on the power supply. Make a sufficient length of wire available to attach to the three terminal block connections. Attach and tighten the conduit to the conduit bracket. The method to attach this conduit depends on your site; the attachment procedure is beyond the scope of this publication. Connect the DC-input wires to the terminal block. See Figure 5-9 (Catalyst 5509 switch) or Figure 5-10 (Catalyst 5500 switch). The proper wiring sequence is ground to ground, positive to positive (line to L), and negative to negative (neutral to N). You should always connect the ground wire first and disconnect the ground wire last.
Figure 5-9: Catalyst 5509 Switch: DC-Input Power Supply Connectors
Figure 5-10: Catalyst 5500 Switch: DC-Input Power Supply Connectors
Step 9 After ensuring that all wire connections are secure, reinstall the terminal block cover.
Step 10 Remove the tape from the circuit breaker switch handle and restore power by moving the circuit breaker switch handle to the On (|) position. Step 11 Turn the power switch to the On (|) position on the power supply. Step 12 Verify power supply operation. Catalyst 5000 and Catalyst 5505 switchesVerify that the green LED on the power supply front panel is on. This indicates that the power supply is on and receiving DC source power, providing +5, +12, and +24 VDC to internal components, and all internal voltages are within tolerance. Catalyst 5509 and Catalyst 5500 switchesVerify that the power supply front panel LEDs are in the following states:
Catalyst 5000, Catalyst 5505, Catalyst 5509, and Catalyst 5500 switchesVerify that the appropriate supervisor engine PS1 and PS2 LEDs are green. Enter the show system command to display the power supply and system status. If the LEDs or show system command indicate a power or other system problem, see "Troubleshooting the Installation." Connecting DC-Input Wires on the Catalyst 5002 SwitchTo connect the DC-input wires to the DC-input power supplies, follow the steps in this section. Required Tools and MaterialsThe required tools and materials are as follows:
ProcedureTo connect the DC-input wires, follow these steps: Step 1 Turn power off to the DC-input circuit. Step 2 Remove the adhesive strip covering the CO ground point on the switch, and then connect the switch to the CO ground through the CO ground point (located at the lower left side of the switch). Step 3 Connect the DC-input wires to the terminal block as follows (see Figure 5-11): a. Using a small flathead screwdriver, loosen the three screws on the terminal block. b. From the top of the terminal block, insert the input wires as follows:
c. Tighten the three screws, ensuring that each input wire is securely connected. d. Repeat Step a through Step c for the other terminal block.
Figure 5-11: DC-Input Power Supply Terminal Block Connectors
Step 4 Remove the tape from the circuit breaker switch handle; restore power by moving the circuit breaker switch handle to the On (|) position. Step 5 Verify power supply operation as follows: a. Listen for the system fans and ensure that the fan LED on the supervisor engine is green. b. While the system initializes, check that the System Status LED on the supervisor engine is orange until the boot is complete.
c. When the system boot is complete (it takes a few seconds), the supervisor engine begins to initialize the switching module.
d. Enter the show system command to display the power supply and system status. e. Check the LEDs or the show system command display for an indication of a power or other system problem. If a problem is observed, see "Troubleshooting the Installation." Japan OnlyTerminal Block Cover InstallationInstall the terminal block cover as follows (see Figure 5-12):
Step 1 Remove the outer screw from each terminal block. Set the screws in a secure place because you will reuse them later. Step 2 Screw the two standoff posts into the two outer screw holes. Do not overtighten the standoff posts. Step 3 Position the terminal block cover over the terminal block while carefully routing the input wires out the side of the cover. Figure 5-12: Japan Only: Installing the Terminal Block Cover
Step 4 Secure the terminal block cover using the two screws removed earlier. Step 5 Return to Step 4 of the installation procedure. Removing and Replacing the Chassis Fan Assembly
This section describes how to remove and install chassis fan assemblies for the Catalyst 5505, Catalyst 5000, Catalyst 5509, and Catalyst 5500 switches. A flat-blade screwdriver is required to perform this procedure. Removing the Fan Assembly
To remove the existing chassis fan assembly, follow these steps: Step 1 Locate the fan assembly to the left of the card cage. (See Figure 5-13 for the Catalyst 5000 and Catalyst 5505 switches, Figure 5-14 for the Catalyst 5509 switch, and Figure 5-15 for the Catalyst 5500 switch.) Step 2 Loosen the two captive installation screws by turning them counterclockwise. Step 3 Grasp the fan assembly with both hands and pull it outward; joggle it if necessary to unseat it from the backplane. Pull it clear of the chassis and place it in a safe place. Figure 5-13: Catalyst 5000 and Catalyst 5505 Switches: Chassis Fan Assembly
Figure 5-14: Catalyst 5509 Switch: Chassis Fan Assembly
Figure 5-15: Catalyst 5500 Switch: Chassis Fan Assembly
Installing the Fan AssemblyTo install the new fan assembly, follow these steps: Step 1 Hold the fan assembly with the fans facing to the right. Step 2 Place the fan assembly into the front chassis cavity so it rests on the chassis, and then lift the fan assembly up slightly aligning the top and bottom guides. Step 3 Push the fan assembly into the chassis until the captive installation screws meet the chassis. Step 4 Tighten the captive installation screws by turning them clockwise. Verifying the InstallationTo verify that the new fan assembly is installed correctly, follow these steps: Step 1 Listen for the fans; you should immediately hear them operating. If you do not hear them, ensure that the fan assembly is inserted completely in the chassis and the faceplate is flush with the switch back panel. Step 2 If after several attempts the fans do not operate, or if you experience trouble with the installation (for instance, if the captive installation screws do not align with the chassis holes), contact a Cisco customer service representative for assistance.
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|