Catalyst 2948G, 2948G-GE-TX, and 2980G Hardware Installation Guide
|
|||||||||||||||||||||||||||||||||||||||
Site Planning
![]() |
||||||||||||||||||||||||||||||||||||||||
Table of ContentsSite PlanningSite Power Requirements and Heat Dissipation System Ground Connection Guidelines (Catalyst 2948G and 2980G Switches Only) Site-Planning Checklist Site Planning
This chapter describes how to prepare your site for the installation of your switch and contains these sections:
Site Power Requirements and Heat Dissipation
This section provides site power requirements and heat dissipation specifications for the Catalyst 2948G, 2948G-GE-TX, and 2980G switches. You should verify site power before you install a switch. Power requirements can vary for each Catalyst switch. Knowing the power requirements can be useful for planning the power distribution system needed to support the switches. Heat specifications are used for determining the air-conditioning requirements for an installation.
Table 2-1 describes the power requirements and heat dissipation specifications for the Catalyst 2948G, 2948G-GE-TX, and 2980G switches. Table 2-1 Power Requirements and Heat Dissipation Specifications
System Ground Connection Guidelines (Catalyst 2948G and 2980G Switches Only)Two system (earth) grounding holes are provided in an enclosure near the power supplies.
See Figure 2-1 for the location of the grounding holes on the Catalyst 2948G switches and Figure 2-2 for the location on the Catalyst 2980G switches. Figure 2-1 Grounding Holes on the Catalyst 2948G Switch Figure 2-2 Grounding Holes on the Catalyst 2980G Switch To make an adequate grounding connection, you need these components and tools:
The grounding lugs are not available from Cisco Systems; any electrical-connector vendor can provide this lug.
Connecting the Switch to Earth GroundThis procedure describes how to connect the Catalyst 2948G, 2948G-GE-TX, and 2980G switches to earth ground. We strongly recommend that you complete this procedure before connecting system power or turning on your switch. To attach the grounding lug and cable to the grounding pad on the Catalyst 2948G, 2948G-GE-TX, and 2980G switches, follow these steps: Step 1 Use a wire-stripping tool to remove approximately 0.75 inches (19 mm) of the covering from the end of the grounding wire. Step 2 Insert the stripped end of the grounding wire into the open end of the grounding lug. Step 3 Use the crimping tool to secure the grounding wire in place in the grounding lug. Step 4 Locate the grounding pad on the switch. See Figure 2-3 for the location of the grounding pad on the Catalyst 2948G switch and Figure 2-4 for the Catalyst 2980G switch. Figure 2-3 Connecting System Ground on the Catalyst 2948G Switch Figure 2-4 Connecting System Ground on the Catalyst 2980G Switch Step 5 Remove the label that covers the grounding pad. Step 6 Place the grounding lug against the grounding pad on the rear panel of the switch. Step 7 Install locking washers; tighten them to secure the grounding lug to the grounding pad. Step 8 Insert two screws through the holes in the grounding lug and the grounding pad. Ensure that the grounding lug and the attached wire will not interfere with other switch hardware or rack equipment. Step 9 Prepare the other end of the grounding wire and connect it to an appropriate grounding point at your site to ensure adequate earth ground for the switch. Site-Planning ChecklistTable 2-2 lists the site-planning activities that you should complete before you install the Catalyst 2948G, 2948G-GE-TX, and 2980G switches. Completing each activity helps ensure a successful switch installation. Table 2-2 Site-Planning Checklist
|
||||||||||||||||||||||||||||||||||||||||
|
|