Installation and Configuration, Release 9.3.00
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||
Preliminary Steps Before Installing
![]() |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Table of ContentsPreliminary Steps Before InstallingSite Preparation
Parts Checklist Safety Requirements CEPT Requirements
Mechanical InstallationEMI Requirements Laser Safety Guidelines Maintaining Safety with Electricity Basic Guidelines Power and Grounding Preliminary Steps Before InstallingBefore proceeding with the installation of the BPX switch, follow these preliminary steps to ensure safety and reliability: Site PreparationThese site preparations are required.
Parts ChecklistBefore proceeding, go through this parts checklist to verify that all the parts you ordered are present, and that they are all in good condition. If there is anything missing or damaged, report it to your Cisco Order Administration representative. Plug-in cards may be shipped installed or under separate cover. The exact number of cards will vary from site to site, depending on the selected configuration. The BPX switch is shipped with all unused slots covered by backplane inserts that prevent radio frequency emissions from the equipment. The unit must not be operated with any unused slots left uncovered. Refer to this list to check the number and type of cards shipped against the number and type of card you ordered. Check that:
Safety RequirementsThis section details safety information for system planners, installers, and maintenance personnel. The mechanical design of the BPX switch prevents any access to exposed voltages without the use of tools. When installed properly, all front and rear cards are mechanically held captive.
CEPT RequirementsAll apparatus (such as, 48 VDC power supplies) connected to the BPX switch must comply with BS6301 or EN60950. EMI RequirementsCompliance with emission regulations depends upon adherence to the installation steps in this manual, including installation of faceplates for all slots and the use of shielded cables between systems. Laser Safety GuidelinesThe optical ports contain an information label as shown in Figure 7-1. Figure 7-1: Laser Information Label
Maintaining Safety with ElectricityYou must install your BPX switch in accordance with national and local electrical codes. United States: National Fire Protection Agency (NFPA) 70, United States National Electrical Code. Canada: Canadian Electrical Code, C22.1, part 1. Other countries: International Electrotechnical Commission (IEC) 364, part 1 through part 7. The BPX switch operates safely when it is used in accordance with its marked electrical ratings and product usage restrictions. Basic GuidelinesFollow these basic guidelines when working with any electrical equipment:
Any list of guidelines might not address all potentially hazardous situations in your working environment so be alert and exercise good judgment at all times. These safety guidelines will help to ensure your safety and protect the equipment:
Power and GroundingStep 1 In order for the BPX switch to function safely and correctly, along with peripheral equipment, use only the power cords, cables, and connectors specified for the attached peripheral equipment, and make sure they are in good condition. Step 2 Certain BPX switches are supplied with two power feeds (cords). Before commencing installation or maintenance inside the cabinet, be sure both power feeds are disconnected from their respective sources. Step 3 Ensure that the BPX switch frame is attached to an isolated ground connection (connection attached directly to ground through an uninterrupted line). Step 4 A conduit hookup box is factory-installed on each DC Power Entry Module for sites requiring wiring to be enclosed in conduit. A plastic terminal block cover is also provided for installations that do not require conduit hookup. Install one or the other as protection for the DC input. Step 5 For an AC system, verify that the node is powered from a dedicated AC branch circuit. The circuit shall be protected by a dedicated 2-pole circuit breaker sized such that the rated current and the trip delay is higher and longer than the BPX switch circuit breaker. A dedicated 20A, 2-pole AC circuit breaker with a long trip delay is recommended for installation.
Step 6 For a DC system, verify that the node is powered from a dedicated DC branch circuit. The circuit shall be protected by a dedicated circuit breaker sized such that the rated current and the trip delay is higher and longer than the BPX switch circuit breaker. A dedicated 50A, 1-pole DC circuit breaker with a long trip delay is recommended for installation.
Step 7 An insulated grounding conductor should be installed as part of the branch circuit that supplies the unit. This grounding conductor is identical in size to the grounded and ungrounded branch circuit supply conductors, but is green with yellow stripes. Mechanical Installation
Horizontal PositioningBPX switch shelves are designed to be mounted to two sets of vertical mounting rails in either a Cisco cabinet or a standard 19-inch equipment rack with unrestricted front to rear air flow. When installed in a Cisco cabinet (see Figure 7-2), the front flanges of the BPX switch are secured to the front rails of the Cisco cabinet. In factory installations, rear support is provided by rear mounting rails in the cabinet at a setback of 19.86 inches. As an option, a rear set of rails located at a setback of approximately 30 inches may be used for rear support. BPX switch shelves can also be mid-mounted to an open T-Rail type rack (see Figure 7-3) with unrestricted front to rear air flow. To facilitate this type of installation, brackets may be fastened to the BPX switch shelf at a 5 or 10 inch setback for supporting the front of the BPX switch shelf. Additional rear mounting support is also recommended. Contact Customer Service for further information. Vertical PositioningFor recommended typical equipment configurations in a Cisco cabinet, refer to Chapter 2, BPX Switch Physical Overview Figure 7-2: Cabinet Mounting Options for the BPX Shelf
Figure 7-3: BPX Shelf and T-Rail (Open Rack) or Equivalent Mounting Options
Installing a BPX Switch Shelf, Preliminary StepsThe BPX switch shelf is designed for mounting in a standard 19-inch (48.25 cm.) equipment rack such as the standard Cisco cabinet. A minimum width between rails of 17.750 inches (44.45 cm) is required (see Figure 7-4 and Figure 7-5). Mounting flanges are permanently attached to the front edge of the BPX switch shelf. It is recommended that you mount the shelf with all plug-in cards temporarily removed to lessen the weight. There are two types of BPX switch shelves with special installation requirements:
Temporary support brackets and a spacer bar are furnished to ease installation by supporting the BPX shelf as you slide it into a cabinet.
The following instructions apply to a BPX switch shelf installation in a Cisco cabinet which has rear rails at 19.86 inches (50.5 cm) or in a customer supplied standard 19-inch (48.25 cm) equipment rack with rear rails at a 30 inch (76.2 cm) setback. To install the BPX switch shelf in a Cisco cabinet: Step 1 Position the shipping container and pallet in front of the cabinet with the rear of the chassis towards the cabinet. Remove the foam strips on the sides, front, and rear. Step 2 Remove the card retaining bracket from the front of the chassis by unscrewing the four Phillips screws. This bracket is used to retain the boards during shipping. Step 3 Remove the Air Intake Grill and all front and rear cards from the shelf and temporarily set them aside as follows: a. Locate the small access hole in the top center of the front Air Intake Grille below the card slots (see Figure 7-6 for location). b. Insert a small slotted blade screwdriver (0.20/0.25 inch blade width) into the access hole until it stops (approximately 1 inch). c. Carefully rotate the screwdriver approximately a quarter turn in either direction. The top of the Air Intake Grille should spring out. d. Remove Air Intake Grille.
e. To remove the cards, rotate the extractor handles at the top and bottom of each card to release the card and slide it out. Step 4 Decide where the BPX switch is to be located. Refer to Figure 7-2 through Figure 7-5 for typical mounting dimensions. The top of the spacer bracket should be temporarily installed in the rack 22.75" (57.8 cm.) below the location selected for the top of the BPX switch chassis. Step 5 Install the temporary support brackets and spacer bar (shipped with the unit). Use two mounting screws to attach each temporary support bracket and two screws to attach the temporary spacer bar to the rack (see Figure 7-7 and Figure 7-8).
Step 6 If you are installing the BPX switch shelf in a Cisco cabinet and using factory installed rear rails located at a 19.86 inch setback from the front, then see the installation instructions in Chapter 8, Installation with Cisco Cabinets including 7000 Series Routers , for instructions. Step 7 If you are installing the BPX switch shelf in a customer-supplied cabinet using rear rail mounting support brackets located at a setback of approximately 30 inches from the front, then see the installation instructions in Chapter 9, Installation in Customer Cabinet. Figure 7-4: Rack Mounting Dimensions, DC Powered Shelf
Figure 7-5: Rack Mounting Dimensions, AC Powered Shelf
Figure 7-6: Removing an Air Intake Grille
Figure 7-7: Temporary Spacer Bar and Support Brackets Installation
Figure 7-8: BPX Switch Shelf Aligned with Temporary Support Brackets and Bar
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|