IMPORTANT:
To comply with GR-1089
intra-building, lightning-immunity requirements
and ensure compliance with FCC Radiated Emissions Criteria, you
must use shielded-twisted pair (STP) cable
and ensure that it is properly terminated at both ends.
The 10/100Base-TX
ports of the FLC2 are suitable for connection to intra-building
or unexposed wiring or cabling only. These intra-building
ports MUST NOT be metallically connected to interfaces that connect
to the outside plant (OSP) or its wiring. These
interfaces are designed for use as intra-building interfaces
only (Type 2 or Type 4 ports as described in GR-1089-CORE, Issue
5) and require isolation from the exposed OSP cabling. The
addition of Primary Protectors is not sufficient protection in order
to connect these interfaces metallically to OSP wiring.
Figure 1. Fast Ethernet
Line Card Interface Connectors
The system uses these
interfaces to connect to other elements in the packet data network.
Each of these interfaces
is equipped with two light emitting diodes (LEDs):
-
Link: This
green LED shows whether or not the line card is connected to the
network. The LED is illuminated when the card is connected.
-
Activity: This
green LED shows when data is transmitted or received. The LED
is illuminated when data is passing through the interface.
Refer to the following
figure and table for pinouts for the RJ-45 Ethernet ports.
Figure 2. 10/100
Ethernet Interface Pinouts
Table 1. 10/100
Ethernet Interface Pinouts
| Pin |
100Base-T
100Mbps Cat5 |
|
1
|
TX+
|
|
2
|
TX-
|
|
3
|
RX+
|
|
4
|
Not applicable
|
|
5
|
Not applicable
|
|
6
|
RX-
|
|
7
|
Not applicable
|
|
8
|
Not applicable
|
|
RX = Receive
Data TX = Transmit Data
|
IMPORTANT:
Be sure to label the
interface cables with their destinations prior to connecting them
to the FLC2. This will assure proper reconnection should
the card need to be serviced.
To cable the FLC2, simply
plug an STC Ethernet cable from a network device into the desired
port.