Each chassis supports
up to eight -48 VDC, 80-amp power feeds, four
per PFU. Each feed consists of a supply and return cable.
IMPORTANT:
The power source must
be a UL/CSA listed device with a regulated output no greater
that -60VDC.
Typically, the
DC power feeds are fed from a power distribution frame (PDF) to
a power distribution panel (PDP) at the rack.
IMPORTANT:
The DC power Battery
Return (BR) or positive terminal, must
be grounded at the source end (power feed or mains power
end).
IMPORTANT:
Minimum 4 AWG multiple
strand, high-flex cable is recommended for final
connections from the PDP to the PFUs. Although the chassis
configuration may not draw maximum power, it should be sized
and wired to handle 12.8 kW of power to accommodate future
expansion. See
Power
Cable Requirements.
Each feed connects
to supply and return terminals on the rear of the PFUs using two-hole lugs
crimped to the end of each cable. The feed cables are routed
through openings in each side of the chassis. The input
terminals are wired through EMI filters to the ASR 5500 backplane.
For
a non-redundant chassis power configuration, live
power feeds must be connected to all four power inputs on PFU-A. For
a redundant power configuration, live power feeds must
be connected to all four power inputs on PFU-B. The
four power feeds per PFU assure that all power planes in the backplane
are energized; power is available to all card slots in
the chassis. For additional information, see
Internal
Power Planes.
The circuit breakers
at the power distribution panel must disconnect the supply line of
each -48VDC feed. However, it is recommended
that the circuit breakers at the power distribution panel simultaneously
disconnect both poles (supply and return) for
each -48 VDC feed to completely isolate the ASR 5500
from the power source.
To maintain power redundancy, separate –48
VDC supply circuits should be used to feed each DC power input on
both PFUs.
CAUTION:
Set the circuit breakers
on the distribution panel to the OFF position before making the power
connections at the PFUs.
Each power input cable
must be terminated with a supplied Panduit LCD4-14AF-L
2-hole, 90-degree lug using the appropriate
crimping tool and die.
The following alternate
lug types (not supplied with the chassis) are
also approved for use on the power feeds:
- Panduit LCC4-14AF-L, 4
AWG, 2-hole, 90-degree long
barrel lug
- Burndy YAZ2C2TC1490, 2
AWG, 2-hole, 90-degree long
barrel lug
If a DC power input
should fail, the operating supply circuits continue to
power the ASR 5500.