Cisco MDS 9500 Series Hardware Installation Guide
Technical Specifications
Downloads: This chapterpdf (PDF - 346.0KB) The complete bookPDF (PDF - 35.92MB) | Feedback

Technical Specifications

Table Of Contents

Technical Specifications

Switch Specifications

Module Specifications

Weight of Modules

Power Specifications for the Cisco MDS 9513 Director

Specifications for the Cisco MDS 9513 Power Supplies

Component Power Requirements and Heat Dissipation for the Cisco MDS 9513 Director

AC Power Consumption for the Cisco MDS 9513 Director

Power Specifications for the Cisco MDS 9509 Director

Specifications for the Cisco MDS 9509 Power Supplies

Component Power Requirements and Heat Dissipation for the Cisco MDS 9509 Director

AC Power Consumption for the Cisco MDS 9509 Director

Power Specifications for the Cisco MDS 9506 Director

Specifications for the Cisco MDS 9506 Power Supplies

Component Power Requirements and Heat Dissipation for the Cisco MDS 9506 Director

AC Power Consumption for the Cisco MDS 9506 Director

Transceiver Specifications


Technical Specifications


This appendix provides technical specifications and includes the following sections:

Switch Specifications

Module Specifications

Power Specifications for the Cisco MDS 9513 Director

Power Specifications for the Cisco MDS 9509 Director

Power Specifications for the Cisco MDS 9506 Director

Transceiver Specifications


Note Specifications for cables and connectors are provided in "Cable and Port Specifications."


Switch Specifications

The Cisco MDS 9500 Series supports hot-swappable fan modules that provide 85 cfm (cubic feet per minute) of airflow per slot with 410 W of power dissipation per slot.

Table D-1 lists the environmental specifications for the Cisco MDS 9500 Series.

Table D-1 Environmental Specifications for the Cisco MDS 9500 Series 

Description
Specification

Temperature, certified for operation

32 to 104°F (0 to 40°C)

Temperature, designed and tested for operation

32 to 130°F (0 to 55°C)

Temperature, ambient nonoperating and storage

-40 to 158°F (-40 to 70°C)

Humidity (RH), ambient (noncondensing) operating

10 to 90%

Humidity (RH), ambient (noncondensing) nonoperating and storage

5 to 95%

Altitude, certified for operation

0 to 6500 ft (0 to 2000 m)

Altitude, designed and tested for operation

-200 to 10000 ft (-60 to 3000 m)

Noise levels

70 dB


Table D-2 lists the physical specifications for the Cisco MDS 9513 Director.

Table D-2 Physical Specifications for the Cisco MDS 9513 Director 

Description
Specification

Dimensions (HxWxD)

24.5 x 17.5 x 28 in. (62.2 x 44.5 x 71.1 cm)
Chassis requires 14 RU1 , 15 RU with a rack-mount kit.
Chassis depth including cable guide is 33 in. (83.8 cm).

Crossbar module: 1.7 x 14.0 x 11.2 in. (4.4 x 35.6 x 28.4 cm)

Weight

Chassis only: 101 lb (45.36 kg)
Fully loaded chassis2 : 375 lb (170.10 kg)

System fan tray: 18 lbs (8.2 kg)

Crossbar module fan tray: 2.25 lbs (1.02 kg)

Power supply

6000-W, AC input
33 lb (15 kg)

Airflow

275 to 325 lfm3 through system fan module, or 90 cfm4 per supervisor, switching, or services module. Total of 1150 cfm if all slots are filled.

Spacing requirements:

If installed in an open rack (no side panels), the horizontal distance required between the chassis and any devices that exhaust air towards the chassis is a minimum of 12 in. (304 cm), and the distance required between the chassis air vents and any walls is a minimum of 6 in. (15.2 cm).

1 RU = rack unit; 1 RU = 1.75 in. (4.45 cm).

2 Depending on what modules are installed in the chassis.

3 lfm = linear feet per minute.

4 cfm = cubic feet per minute.


Table D-3 lists the physical specifications for the Cisco MDS 9509 Director.

Table D-3 Physical Specifications for the Cisco MDS 9509 Director 

Description
Specification

Dimensions (HxWxD)

24.5 x 17.25 x 18.8 in. (62.2 x 43.8 x 47.8 cm)
Chassis requires 14 RU1 plus space for shelf brackets.
Chassis depth including cable guide is 21.64 in. (55.0 cm).

Weight

Chassis only: 55 lb (24.9 kg)
Chassis configured with two supervisor modules, and 2500-W power supplies: 120 lb (54.4 kg)
Chassis configured with two supervisor modules, and 4000-W power supplies: 140 lb (63.5 kg)

System fan tray: 10.5 lb (5.0 kg).

Power supply

4000-W, AC input
3000-W, AC input
2500-W, AC input
2500-W, DC input

Airflow

300 lfm2 through system fan module, or 80 cfm3 per supervisor, switching, or services module. Total of 720 cfm if all slots are filled.

Spacing requirements:

If installed in a cabinet, a minimum clearance of 2.5 in. (6.4 cm) is required between the chassis air vents and the cabinet walls.

If installed in an open rack (no side panels), the horizontal distance required between the chassis and any devices that exhaust air towards the chassis is a minimum of 6 in. (15.2 cm), and the distance required between the chassis air vents and any walls is a minimum of 2.5 in. (6.4 cm).

1 RU = rack unit; 1 RU = 1.75 in. (4.45 cm)

2 lfm = linear feet per minute

3 cfm = cubic feet per minute


Table D-4 lists the physical specifications for the Cisco MDS 9506 Director.

Table D-4 Physical Specifications for the Cisco MDS 9506 Director 

Description
Specification

Dimensions (HxWxD)

12.25 x 17.37 x 21.75 in. (31.1 x 44.1 x 55.2 cm).
Chassis requires 7 RU1 .
Chassis depth including cable guides is 26.75 inches (67.9 cm).

Weight

Chassis only: 46 lb (20.9 kg).
Chassis configured with two supervisor modules, fan module, and two power supplies: 86 lb (39 kg).
System fan tray: 7.70 lbs (3.49 kg)
1900W AC power supply: 11 lbs (4.99 kg)

Power supply

1900-W, AC input
1900-W, DC input

Airflow

300 lfm2 through system fan module, or 80 cfm3 per supervisor, switching, or services module (total of 480 cfm if all slots are filled).
Spacing requirements:

If installed in a cabinet, a minimum of 2.5 in. (6.4 cm) is required between the chassis air vents and the cabinet walls.

If installed in an open rack (no side panels), the horizontal distance required between the chassis and any devices that exhaust air towards the chassis is a minimum of 6 in. (15.2 cm), and the distance required between the chassis air vents and any walls is a minimum of 2.5 in. (6.4 cm).

1 RU = rack unit; 1 RU = 1.75 in. (4.45 cm)

2 lfm = linear feet per minute

3 cfm = cubic feet per minute


Module Specifications

Table D-5 lists the specifications for the Cisco MDS 9500 Series supervisor modules, services modules, and switching modules.

Table D-5 Cisco MDS 9500 Series Module Specifications 

Description
Specification
Environmental Requirements

Temperature, certified for operation (module intake of ambient)

32 to 104°F (0 to 40°C)

Temperature, designed and tested for operation

32 to 130°F (0 to 55°C)

Temperature, ambient nonoperating and storage

-40 to 167°F (-40 to 75°C)

Humidity (RH), ambient (noncondensing) operating

10 to 90%

Altitude, certified for operation

0 to 6500 ft (0 to 2000 m)

Altitude, designed and tested for operation

-200 to 10000 ft (-60 to 3000 m)

Physical Characteristics

Dimensions

1.75 x15.5 x16.5 in. (4.4 x 39.4 x 41.9 cm)

Note These are the maximum dimensions of the faceplate and
board, and include the connectors on the board.

Weight

8 to 11.5 lb (1.4 to 5.2 kg)


Weight of Modules

Table D-6 lists the weight for each module in the Cisco MDS 9000 Family.

Table D-6 Weight of Modules in the Cisco MDS 9000 Family 

Module
Weight

8-port 10-Gbps FCoE module

8 lb (3.63 kg)

48-Port 8-Gbps Advanced Fibre Channel Switching module

10.0 lb (4.5 kg)

32-Port 8-Gbps Advanced Fibre Channel Switching module

10.0 lb (4.5 kg)

MDS 9513 256-Gbps Fabric 3 Module

5 lb (2.26 kg)

16-port Storage Services Node

10.0 lb (4.5 kg)

48-port 8-Gbps switching module

10.25 lb (4.65 kg)

24-port 8-Gbps switching module

10.25 lb (4.65 kg)

4/44-port 8-Gbps Host-Optimized switching module

9.75 lb (4.42 kg)

Fabric 2 external crossbar module (DS-13SLT-FAB2)

6 lb (2.7 kg)

Fabric 1 external crossbar module (DS-13SLT-FAB1)

6 lb (2.7 kg)

48-port 4-Gbps switching module

11.0 lb (4.99 kg)

24-port 4-Gbps switching module

7.75 lb (3.52 kg)

12-port 4-Gbps switching module

7.5 lb (3.40 kg)

4-Port 10-Gbps switching module

8.5 lb (3.86 kg)

32-port FC switching module

9 lb (4.1 kg)

16-port FC switching module

9 lb (4.1 kg)

SSM

11 lb (5 kg)

ASM

11 lb (5 kg)

CSM

11.5 lb (5.2 kg)

IPS-8

10 lb (4.5 kg)

IPS-4

9 lb (4.1 kg)

MSM-18/4

8.5 lb (3.86 kg)

MPS-14/2

10 lb (4.5 kg)

Supervisor-2A for MDS 9500 Series

7.25 lb (3.3 kg)

Supervisor-2 for MDS 9500 Series

7.25 lb (kg)

Supervisor-1 for MDS 9500 Series

9 lb (4.1 kg)

Supervisor for MDS 9200 Series

9 lb (4.1 kg)

Crossbar module fan tray

2.25 lb (1.13 kg)

Module blank panels

0.50 lb (0.25 kg)


Table D-7 lists the specifications for the batteries on the Cisco MDS 9000 Family caching services module.


Note The CSM does not support Cisco SAN-OS Release 3.0(1).


Table D-7 Caching Services Module Battery Specifications 

Attribute
Value

Nominal voltage

9.6 V

Rated capacity

Typical discharge capacity at 0.2C rate: 2100 mAh

Minimum discharge capacity at 0.2C rate: 2000 mAh

Minimum discharge capacity at 5C rate: 1800 mAh
(1 V/cell discharge cut-off)

Discharge

The battery is capable of continuous discharge from 41 to 140°F (5 to 60°C) at 5C-rate

Charge

From 32 to 59°F (0 to 15°C) at C/10 rate and from 59 to 104°F (15 to 40°C) at C/2 rate

Storage temperature

32 to 95°F (0 to +35°C)

Relative humidity range

From 5 to 90%


Power Specifications for the Cisco MDS 9513 Director

This section includes the following topics:

Specifications for the Cisco MDS 9513 Power Supplies

Component Power Requirements and Heat Dissipation for the Cisco MDS 9513 Director

AC Power Consumption for the Cisco MDS 9513 Director

Specifications for the Cisco MDS 9513 Power Supplies

The 6000-W AC power supply provides power based upon the input voltage. Each power supply has two AC power connections and will provide power as follows:

One AC power connection @110 VAC = No output

Two AC power connection @110 VAC = 2900 W output

One AC power connection @ 220 VAC = 2900 W output

One AC power connection @110 VAC and one AC power connection @ 220 VAC = 2900 W output

Two AC power connection @ 220 VAC = 6000 W output

If a 110 VAC input is chosen, a 110-VAC power cord (CAB-7513AC=) must be ordered separately.


Note Power output does not include the power used by the individual modules used in the chassis.


Table D-8 lists the specifications for the Cisco MDS 9513 power supplies.

Table D-8 Specifications for Cisco MDS 9513 Power Supplies 

Description
Specification
6000-W AC Power Supply

Type

Autoranging input with power factor corrector.

Voltage

100 to 240 VAC (±10%).

Current rating

16 A maximum at 100 to 120 VAC and 2900-W output.
16 A maximum at 200 to 240 VAC and 6000-W output.

Frequency

50 to 60 Hz (nominal) (±3 Hz for full range).

Output capacity

One AC power connection @110 VAC = No output

Two AC power connection @110 VAC = 2900 W output

One AC power connection @ 220 VAC = 2900 W output

One AC power connection @110 VAC and one AC power connection @ 220 VAC = 2900 W output

Two AC power connection @ 220 VAC = 6000 W output

Output voltage at 110/120

3.3 V at 10 A, 50 V at 57 A

Output voltage at 200/240

3.3 V at 10A, 50 V at 119 A


Component Power Requirements and Heat Dissipation for the Cisco MDS 9513 Director

Consider heat dissipation when sizing the air-conditioning requirements for an installation. The power and heat associated with a Cisco MDS 9513 Director varies based upon the following considerations:

Power supply type

Switching module type and number of switching modules installed

Average switching traffic levels

Table D-9 lists the power requirements and heat dissipation for the components of the Cisco MDS 9513 Director.


Note Unless noted otherwise, the data listed in Table D-9 is based on worst-case conditions. Typical numbers are approximately 30 percent below the numbers listed here.


Table D-9 Requirements and Heat Dissipation for 6000-W AC Power Supplies 

Module Type/
Product Number
NX-OS Release
SAN-OS Release
Power Required (watts)
Heat Dissipation (BTU/hr)
Input Current
90 VAC (amps)
120 VAC (amps)
180 VAC (amps)
240 VAC (amps)

Fan tray 1 (front panel), DS-13SLT-FAN-F

 

3.x

248

1059

3.44

2.58

1.72

1.29

Fan tray 2 (rear panel), DS-13SLT-FAN-R

 

3.x

70

299

0.97

0.73

0.49

0.36

Cisco MDS 9513 chassis, DS-C9513, with front (DS-13SLT-FAN-F) and rear (DS-13SLT-FAN-R) fan trays

 

3.x

318

1358

4.41

3.31

2.21

1.65

Cisco MDS 9000 8-Port 10-Gbps FCoE module (DS-X9708-K9)

5.2

 

150

640

2.08

1.56

1.04

0.78

48-Port 8-Gbps Advanced Fibre Channel Switching module(DS-X9248-256K9)

5.2

 

310

1387

4.51

3.39

2.26

1.69

32-Port 8-Gbps Advanced Fibre Channel Switching module(DS-X9232-256K9)

5.2

 

302

1323

4.31

3.23

2.15

1.61

Cisco MDS 9513 256-Gbps Fabric 3 Module (DS-13SLT-FAB3)

5.2

 

83

427

1.39

1.04

0.69

0.52

Supervisor-2A, DS-X9530-SF2A-K9

5.2

 

126

538

1.75

1.31

0.88

0.66

Supervisor-2, DS-X9530-SF2-K9

 

3.x

126

538

1.75

1.31

0.88

0.66

48-port 4-Gbps switching module,
DS-X9148

 

3.x

185

790

2.57

1.93

1.28

0.96

24-port 4-Gbps switching module,
DS-X9124

 

3.x

147

628

2.04

1.53

1.02

0.77

12-port 4-Gbps switching module,
DS-X9112

 

3.x

132

564

1.83

1.38

0.92

0.69

4-port 10-Gbps switching module,
DS-X9704

 

3.x

172

734

2.39

1.79

1.19

0.90

18/4 Multiservice module, DS-X9304-18K9

 

3.2.(1)

200

855

2.78

2.08

1.39

1.04

Crossbar module, DS-13SLT-FAB1, DS-13SLT-FAB2

 

3.x

63

269

0.88

0.66

0.44

0.33

48-port 8-Gbps switching module,
DS-X9248-96K9

4.x

 

298

1273

4.14

3.11

2.07

1.55

24-port 8-Gbps switching module,
DS-X9224-96K

4.x

 

273

1163

3.79

2.84

1.90

1.42

4/44-port 8-Gbps Host-Optimized switching module,
DS-X9248-48K9

4.x

 

214

915

2.98

2.23

1.49

1.12

16-port Storage Services Node, DS-X9316-SSNK9

4.2(1)

 

298

1273

4.14

3.11

2.08

1.55


AC Power Consumption for the Cisco MDS 9513 Director

Table D-10 shows the typical AC power consumption for a Cisco MDS 9513 Director.

Table D-10 Typical AC Power Consumption for a Cisco MDS 9513 Director

Module Type / Product Number
Typical AC Power Consumption (Watts)

Cisco MDS 9513 chassis, DS-C9513, with front (DS-13SLT-FAN-F) and rear (DS-13SLT-FAN-R) fan trays, two Supervisor-2 (DS-X9530-SF2-K9) or Supervisor-2A (DS-X9530-SF2A-K9) modules, and two crossbar modules (DS-13SLT-FAB1, DS-13SLT-FAB2, or DS-13SLT-FAB3)

697

48-port 4-Gbps switching module, DS-X9148

181

24-port 4-Gbps switching module, DS-X9124

127

12-port 4-Gbps switching module, DS-X9112

107

4-port 10-Gbps switching module, DS-X9704

162

48-port 8-Gbps switching module, DS-X9248-96K9

230

24-port 8-Gbps switching module, DS-X9224-96K

221

4/44-port 8-Gbps Host-Optimized switching module,
DS-X9248-48K9

175

16-port Storage Services Node, DS-X9316-SSNK9

257

8-port 10-Gbps FCoE module, DS-X9708-K9

107

48-Port 8-Gbps Advanced Fibre Channel Switching module, DS-X9248-256K9

267

32-Port 8-Gbps Advanced Fibre Channel Switching module, DS-X9232-256K9

243


Power Specifications for the Cisco MDS 9509 Director

This section includes the following topics:

Specifications for the Cisco MDS 9509 Power Supplies

Component Power Requirements and Heat Dissipation for the Cisco MDS 9509 Director

AC Power Consumption for the Cisco MDS 9509 Director

Specifications for the Cisco MDS 9509 Power Supplies

The 3000-W AC power supply provides power based upon the input voltage, as follows:

Maximum of 1400 W at input of 100 to 120 VAC (1174 W available to modules and fans)

Maximum of 3000 W at input of 200 to 240 VAC (2774 W available to modules and fans)

The 2500-W AC power supply provides power based upon the input voltage, as follows:

Maximum of 1325 W at input of 100 to 120 VAC (1150 W available to modules and fans)

Maximum of 2525 W at input of 200 to 240 VAC (2331 W available to modules and fans)

If a 110-VAC input is chosen, a 110-VAC power cord (CAB-7513AC=) must be ordered separately.

Table D-11 lists the specifications for the Cisco MDS 9509 power supplies.

Table D-11 Specifications for Cisco MDS 9509 Power Supplies 

Description
Specification
2500-W AC Power Supply

Type

Autoranging input with power factor corrector.

Voltage

100 to 240 VAC (±10%).

Current rating

16 A maximum at 100 to 120 VAC and 1300-W output.
16 A maximum at 200 to 240 VAC and 2500-W output.

Note For current ratings of plugs, see Figure E-5.

Frequency

50 to 60 Hz (nominal) (±3 Hz for full range).

Output capacity

1325 W maximum (100 to 120 VAC).
2525 W maximum (200 to 240 VAC).

Output voltage at 110/120

3.3 V at 15 A; 5 V at 5 A; 12 V at 12 A; 42 V at 27.5 A.

Output voltage at 200/240

3.3 V at 1 5 A; 5 V at 5 A; 12 V at 12 A; 42 V at 55.5 A.

2500-W DC Power Supply

Voltage

-48 VDC to -60 VDC continuous.

Current rating

70 A at -48 VDC; 55 A at -60 VDC; 80 A at -40.5 VDC.

Terminal block

Accommodates 2 to 14 AWG copper conductors. Use 90°C copper conductors for North American installations.

Note Actual size of the wire required is determined by the installer or local electrician. Terminal block material is rated at 302°F (150°C).

Output capacity

2525 W maximum (-48 to -60 VDC).

Output voltage

3.3 V at 15 A; 5 V at 5 A; 12 V at 12 A; 42 V at 55.5 A.

3000-W AC Power Supply

Type

Autoranging input with power factor corrector.

Voltage

100 to 240 VAC (±10%).

Current rating

17.6 A maximum at 100 to 120 VAC and 1400-W output.
17.6 A maximum at 200 to 240 VAC and 3000-W output.

For current ratings of plugs, see Figure E-5

Frequency

50 to 60 Hz (nominal) (±3 Hz for full range).

Output capacity

1400 W maximum (100 to 120 VAC).
3000 W maximum (200 to 240 VAC).

Output voltage at 110/120

3.3 V at 15 A; 12 V at 12 A; 42 V at 27.9 A.

Output voltage at 200/240

3.3 V at 1 5 A; 12 V at 12 A; 42 V at 66 A.

4000-W AC Power Supply

Type

High-line input with power factor corrector, 220 VAC, single-phase circuit.

Voltage

200 to 240 VAC (±10%).

Current rating

23 A

Note For current ratings of plugs, see Figure E-8.

Frequency

50/60 Hz (nominal) (±3% for full range).

Output capacity

4000 W maximum.

Output voltage at 200/240

3.3 V at 15 A; 5 V at 5 A; 12 V at 12 A; 42 V at 91.2 A


Component Power Requirements and Heat Dissipation for the Cisco MDS 9509 Director

When sizing the air-conditioning requirements for an installation, consider heat dissipation. The power and heat associated with a Cisco MDS 9509 Director varies based upon the following considerations:

Power supply type

Switching module type and number of switching modules installed

Average switching traffic levels

Table D-12 and Table D-13 list the power requirements and heat dissipation for the components of the Cisco MDS 9509 Director.


Note Unless noted otherwise, the data listed in Table D-12 and Table D-13 is based on worst-case conditions. Typical numbers are approximately 30 percent below the numbers listed here.


Table D-12 Requirements and Heat Dissipation for 2500-, 3000-, and 4000-W AC Power Supplies 

Module Type/
Product Number
NX-OS Release
SAN-OS Release
Power Required (watts)
Heat Dissipation (BTU/hr)
Input Current
90 VAC (amps)
120 VAC (amps)
180 VAC (amps)
240 VAC (amps)

Cisco MDS 9509 chassis with fan module
DS-C9509

 

3.x

210

897

2.92

2.19

1.46

1.09

 

2.x and 1.x

216

920

3.00

2.25

1.50

1.13

Supervisor/fabric 1
DS-X9530-SF1

 

3.x

210

897

2.92

2.19

1.46

1.09

 

2.x and 1.x

220

940

3.05

2.29

1.53

1.15

Supervisor-2, DS-X9530-SF2-K9

 

3.x

126

538

1.75

1.31

0.88

0.66

48-port 4-Gbps switching module,
DS-X9148

 

3.x

185

790

2.57

1.93

1.28

0.96

 

2.x and 1.x

24-port 4-Gbps switching module,
DS-X9124

 

3.x

147

628

2.04

1.53

1.02

0.77

 

2.x and 1.x

12-port 4-Gbps switching module,
DS-X9112

 

3.x

132

564

1.83

1.38

0.92

0.69

 

2.x and 1.x

4-port 10-Gbps switching module,
DS-X9704

 

3.x

172

734

2.39

1.79

1.19

0.90

 

2.x and 1.x

32-port 1-Gbps/2-Gbps Fibre Channel module,
DS-X9032

 

3.x

191

816

.2.65

1.99

1.33

0.99

 

2.x and 1.x

200

855

2.78

2.08

1.39

1.04

16-port 1-Gbps/2-Gbps Fibre Channel module,
DS-X9016

 

3.x

210

897

2.92

2.19

1.46

1.09

 

2.x and 1.x

220

940

3.05

2.29

1.53

1.15

18/4 Multiservice module, DS-X9304-18K9

 

3.2.(1)

200

855

2.78

2.08

1.39

1.04

MPS-14/2 module DS-X9302-14K9

 

3.x

200

854

2.78

2.08

1.39

1.04

 

2.x and 1.x

227

970

3.15

2.37

1.57

1.19

8-port IPS module
DS-X9308-SMIP

 

3.x

200

854

2.78

2.08

1.39

1.04

 

2.x and 1.x

220

940

3.05

2.29

1.53

1.15

4-port IPS module
DS-X9304-SMIP

 

3.x

160

683

2.22

1.67

1.11

0.83

 

2.x and 1.x

185

789

2.57

1.93

1.28

0.96

32-port SSM
DS-X9032-SSM

 

3.x

281

1200

3.90

2.93

1.95

1.46

 

2.x and 1.x

295

1260

4.10

3.07

2.05

1.54

32-port ASM
DS-X9032-SMV

 

3.x

281

1200

3.90

2.93

1.95

1.46

 

2.x and 1.x

295

1260

4.10

3.07

2.05

1.54

CSM
DS-X9560-SMC

 

3.x

200

854

2.78

2.08

1.39

1.04

 

2.x and 1.x

210

919

2.99

2.19

1.50

1.12

48-port 8-Gbps switching module,
DS-X9248-96K9

4.x

 

298

1273

4.14

3.11

2.07

1.55

24-port 8-Gbps switching module,
DS-X9224-96K

4.x

 

273

1163

3.79

2.84

1.90

1.42

4/44-port 8-Gbps Host-Optimized switching module,
DS-X9248-48K9

4.x

 

214

915

2.98

2.23

1.49

1.12

16-port Storage Services Node, DS-X9316-SSNK9

4.2(1)

 

298

1273

4.14

3.11

2.08

1.55

Cisco MDS 9000 8-Port 10-Gbps FCoE module (DS-X9708-K9)

5.2

 

150

640

2.08

1.56

1.04

0.78

48-Port 8-Gbps Advanced Fibre Channel Switching module(DS-X9248-256K9)

5.2

 

310

1387

4.51

3.39

2.26

1.69

32-Port 8-Gbps Advanced Fibre Channel Switching module(DS-X9232-256K9)

5.2

 

302

1323

4.31

3.23

2.15

1.61

Supervisor-2A, DS-X9530-SF2A-K9

5.2

 

126

538

1.75

1.31

0.88

0.66


Table D-13 Power Requirements and Heat Dissipation for the 2500-W DC Power Supply 

Module Type/
Product Number
SAN-OS Release
Power Required (watts)
Heat Dissipation (BTU/hr)
Input Current
48 VDC (amps)
60 VDC (amps)

Cisco MDS 9509
chassis with fan module
DS-C9509

3.x

210

956

5.83

4.67

2.x and 1.x

216

983

6.00

4.80

Supervisor/fabric 1
DS-X9530-SF1

3.x

210

956

5.83

4.67

2.x and 1.x

220

1000

6.10

4.88

32-port 1-Gbps/2-Gbps Fibre Channel module
DS-X9032

3.x

191

869

5.31

4.24

2.x and 1.x

200

911

5.56

4.45

16-port 1-Gbps/2-Gbps Fibre Channel module
DS-X9016

3.x

210

956

5.83

4.67

2.x and 1.x

220

1000

6.10

4.88

MSM-18/4 module, DS-X9304-18K9

3.2(1)

200

855

2.78

2.08

MPS-14/2 module
DS-X9302-14K9

3.x

200

910

5.56

4.44

2.x and 1.x

227

970

3.15

2.37

8-port IPS module
DS-X9308-SMIP

3.x

200

910

5.56

4.44

2.x and 1.x

220

1000

6.10

4.88

4-port IPS module
DS-X9304-SMIP

3.x

160

728

4.44

3.56

2.x and 1.x

185

841

5.14

4.11

32-port SSM
DS-X9032-SSM

3.x

281

1279

7.81

6.24

2.x and 1.x

295

1342

8.19

6.56

32-port ASM
DS-X9032-SMV

3.x

281

1279

7.81

6.24

2.x and 1.x

295

1342

8.19

6.56

CSM
DS-X9560-SMC

3.x

200

910

5.56

4.44

2.x and 1.x

210

956

5.83

4.67


AC Power Consumption for the Cisco MDS 9509 Director

Table D-14 shows the typical AC power consumption for the Cisco MDS 9509 Director

Table D-14 Typical AC Power Consumption for a Cisco MDS 9509 Director

Module Type / Product Number
Typical AC Power Consumption (Watts)

Cisco MDS 9509 chassis, DS-C9509, with fan module, and two Supervisor-2 (DS-X9530-SF2-K9) or Supervisor-2A (DS-X9530-SF2A-K9)

380

Cisco MDS 9509 chassis, DS-C9509, with fan module, and two Supervisor-1 (DS-X9530-SF1-K9)

622

48-port 4-Gbps switching module, DS-X9148

181

24-port 4-Gbps switching module, DS-X9124

127

12-port 4-Gbps switching module, DS-X9112

107

4-port 10-Gbps switching module, DS-X9704

162

32-port 1-Gbps/2-Gbps Fibre Channel module, DS-X9032

174

16-port 1-Gbps/2-Gbps Fibre Channel module, DS-X9016

144

Cisco MDS 9000 Family 18/4 - port Multiservice module

199.8

MPS-14/2 module, DS-X9302-14K9

178

32-port SSM, DS-X9032-SSM

211

8-port IPS module, DS-X9308-SMIP

175

4-port IPS module, DS-X9304-SMIP

128

48-port 8-Gbps switching module, DS-X9248-96K9

230

24-port 8-Gbps switching module, DS-X9224-96K

221

4/44-port 8-Gbps Host-Optimized switching module,
DS-X9248-48K9

175

16-port Storage Services Node, DS-X9316-SSNK9

257

Cisco MDS 9000 8-Port 10-Gbps FCoE module (DS-X9708-K9)

107

48-Port 8-Gbps Advanced Fibre Channel Switching module(DS-X9248-256K9)

267

32-Port 8-Gbps Advanced Fibre Channel Switching module(DS-X9232-256K9)

243

Supervisor-2A, DS-X9530-SF2A-K9

697


Power Specifications for the Cisco MDS 9506 Director

This section includes the following topics:

Specifications for the Cisco MDS 9506 Power Supplies

Component Power Requirements and Heat Dissipation for the Cisco MDS 9506 Director

AC Power Consumption for the Cisco MDS 9506 Director

Specifications for the Cisco MDS 9506 Power Supplies


Caution The following applies to AC power supplies on the Cisco MDS 9506 only:
The DS-C9506 equipment is suitable for use on TN power systems and the IT-power system connection of Norway (max 230 v phase-phase). If connected to a 230/400-V IT power system, beware of high-leakage current. Earth connection is essential before connecting the supply.

The 1900-W AC power supply provides power based upon the input voltage:

Maximum of 1050 W at input of 100 to 120 VAC

Maximum of 1900 W at input of 200 to 240 VAC

A 110-VAC power cord (CAB-7513AC=) must be ordered separately.

Table D-15 lists the specifications for the Cisco MDS 9506 power supplies.

Table D-15 Specifications for Cisco MDS 9506 Power Supplies 

Description
Specification
1900-W AC Power Supply

Type

Autoranging input with power factor corrector.

Voltage

100 to 240 VAC (±10%).

Current rating

12 A maximum at 100 to 120 VAC and 1050-W output.
12 A maximum at 200 to 240 VAC and 1900-W output.

Note For current ratings of plugs, see Figure E-5.

Frequency

50/60 Hz (nominal) (±3 Hz for full range).

Output capacity

1050 W maximum (at input of 100 to 120 VAC).
1900 W maximum (at input of 200 to 240 VAC).

Output voltage at 110/120

3.3 V at 2.5 A; 1.5 V at 15 A; 50 V at 20.4 A.

Output voltage at 200/240

3.3 V at 2.5 A; 1.5 V at 15 A; 50 V at 37.4 A.

1900-W DC Power Supply

Voltage

-48 to -60 VDC continuous.

Current rating

50 A at -48 VDC, 40 A at -60 VDC, 60 A at -40.5 VDC.

Terminal block

Accommodates 2 to 14 AWG copper conductors. Use 90°C copper conductors for North American installations.

Note Actual size of the wire required is determined by the installer or local electrician. Terminal block material is rated at 302°F (150°C).

Output capacity

1900 W maximum (at input of -48 to -60 VDC).

Output voltage

3.3 V at 2.5 A; 1.5 V at 15 A; 50 V at 37.4 A.


Component Power Requirements and Heat Dissipation for the Cisco MDS 9506 Director

When sizing the air-conditioning requirements for an installation, consider heat dissipation. The power and heat associated with a Cisco MDS 9506 Director varies depending upon the following:

Power supply type

Switching module type and number of switching modules installed

Average switching traffic levels

Table D-16 and Table D-17 list the AC and DC power requirements and heat dissipation for the components of the Cisco MDS 9506 Director.


Note Unless noted otherwise, the information listed in Table D-16 and Table D-17 is based on worst-case conditions. Typical numbers are approximately 30 percent below the numbers listed here.


Table D-16 Power Requirements and Heat Dissipation for the 1900-W AC Power Supply 

Module Type/
Product Number
NX-OS Release
SAN-OS Release
Power
Required (watts)
Heat Dissipation (BTU/hr)
Input Current
90 VAC (amps)
120 VAC (amps)
180 VAC (amps)
240 VAC (amps)

Cisco MDS 9506 chassis with fan module
DS-C9506

 

3.x

126

538

1.75

1.31

0.88

0.66

 

2.x and 1.x

126

538

1.75

1.32

0.88

0.66

Supervisor/fabric 1
DS-X9530-SF1

 

3.x

210

897

2.92

2.19

1.46

1.09

 

2.x and 1.x

220

940

3.05

2.29

1.53

1.15

Cisco MDS 9000 8-Port 10-Gbps FCoE module (DS-X9708-K9)

5.2

 

150

640

2.08

1.56

1.04

0.78

48-Port 8-Gbps Advanced Fibre Channel Switching module(DS-X9248-256K9)

5.2

 

310

1387

4.51

3.39

2.26

1.69

32-Port 8-Gbps Advanced Fibre Channel Switching module(DS-X9232-256K9)

5.2

 

302

1323

4.31

3.23

2.15

1.61

Supervisor-2A, DS-X9530-SF2A-K9

5.2

 

126

538

1.75

1.31

0.88

0.66

Supervisor-2, DS-X9530-SF2-K9

 

3.x

126

538

1.75

1.31

0.88

0.66

48-port 4-Gbps switching module,
DS-X9148

 

3.x

185

790

2.57

1.93

1.28

0.96

 

2.x and 1.x

24-port 4-Gbps switching module,
DS-X9124

 

3.x

147

628

2.04

1.53

1.02

0.77

 

2.x and 1.x

12-port 4-Gbps switching module,
DS-X9112

 

3.x

132

564

1.83

1.38

0.92

0.69

 

2.x and 1.x

4-port 10-Gbps switching module,
DS-X9704

 

3.x

172

734

2.39

1.79

1.19

0.90

 

2.x and 1.x

32-port 1-Gbps/2-Gbps Fibre Channel module
DS-X9032

 

3.x

191

816

2.65

1.99

1.33

0.99

 

2.x and 1.x

200

855

2.78

2.08

1.39

1.04

16-port 1-Gbps/2-Gbps Fibre Channel module
DS-X9016

 

3.x

210

897

2.92

2.19

1.46

1.09

 

2.x and 1.x

220

940

3.05

2.29

1.53

1.15

18/4 Multiservice module, DS-X9304-18K9

 

3.2.(1)

200

855

2.78

2.08

1.39

1.04

MPS-14/2 module DS-X9302-14K9

 

3.x

200

854

2.78

2.08

1.39

1.04

 

2.x and 1.x

227

970

3.15

2.37

1.57

1.19

8-port IPS module
DS-X9308-SMIP

 

3.x

200

854

2.78

2.08

1.39

1.04

 

2.x and 1.x

220

940

3.05

2.29

1.53

1.15

4-port IPS module
DS-X9304-SMIP

 

3.x

160

683

2.22

1.67

1.11

0.83

 

2.x and 1.x

185

789

2.57

1.93

1.28

0.96

32-port SSM
DS-X9032-SSM

 

3.x

281

1200

3.90

2.93

1.95

1.46

 

2.x and 1.x

295

1260

4.10

3.07

2.05

1.54

32-port ASM
DS-X9032-SMV

 

3.x

281

1200

3.90

2.93

1.95

1.46

 

2.x and 1.x

295

1260

4.10

3.07

2.05

1.54

CSM
DS-X9560-SMC

 

3.x

200

854

2.78

2.08

1.39

1.04

 

2.x and 1.x

210

907

2.95

2.22

1.48

1.11

48-port 8-Gbps switching module,
DS-X9248-96K9

4.x

 

298

1273

4.14

3.11

2.07

1.55

24-port 8-Gbps switching module,
DS-X9224-96K

4.x

 

273

1163

3.79

2.84

1.90

1.42

4/44-port 8-Gbps Host-Optimized switching module,
DS-X9248-48K9

4.x

 

214

915

2.98

2.23

1.49

1.12

16-port Storage Services Node (DS-X9316-SSNK9)

4.2(1)

 

298

1273

4.14

3.11

2.08

1.55


Table D-17 Power Requirements and Heat Dissipation for the 1900-W DC Power Supply 

Module Type/
Product Number
SAN-OS Release
Power Required (watts)
Heat Dissipation (BTU/hr)
Input Current
48 VDC (amps)
60 VDC (amps)

Cisco MDS 9506
chassis with fan module
DS-C9506

3.x

126

573

3.50

2.80

2.x and 1.x

126

573

3.50

2.80

Supervisor/fabric 1
DS-X9530-SF1

3.x

210

956

5.83

4.67

2.x and 1.x

220

1000

6.10

4.88

32-port 1-Gbps/2-Gbps Fibre Channel module
DS-X9032

3.x

191

869

5.31

4.24

2.x and 1.x

200

911

5.56

4.45

16-port 1-Gbps/2-Gbps Fibre Channel module
DS-X9016

3.x

210

956

5.83

4.67

2.x and 1.x

220

1000

6.10

4.88

18/4 Multiservice module, DS-X9304-18K9

3.2.(1)

200

855

2.78

2.08

MPS-14/2 module DS-X9302-14K9

3.x

200

910

5.56

4.44

2.x and 1.x

227

970

3.15

2.37

8-port IPS module
DS-X9308-SMIP

3.x

200

910

5.56

4.44

2.x and 1.x

220

1000

6.10

4.88

4-port IPS module
DS-X9304-SMIP

3.x

160

728

4.44

3.56

2.x and 1.x

185

841

5.14

4.11

32-port SSM
DS-X9032-SSM

3.x

281

1279

7.81

6.24

2.x and 1.x

295

1342

8.19

6.56

32-port ASM
DS-X9032-SMV

3.x

281

1279

7.81

6.24

2.x and 1.x

295

1342

8.19

6.56

CSM
DS-X9560-SMC

3.x

200

910

5.56

4.44

2.x and 1.x

210

955

5.83

4.66


AC Power Consumption for the Cisco MDS 9506 Director

Table D-18 shows the typical AC power consumption for the Cisco MDS 9506 Director.

Table D-18 Typical AC Power Consumption for a Cisco MDS 9506 Director

Module Type / Product Number
Typical AC Power Consumption (Watts)

Cisco MDS 9506 chassis, DS-C9506, with fan module, and two Supervisor-2 (DS-X9530-SF2-K9) or Supervisor-2A (DS-X9530-SF2A-K9) modules

395

Cisco MDS 9506 chassis, DS-C9506, with fan module, and two Supervisor-1 (DS-X9530-SF1-K9)

624

48-port 4-Gbps switching module, DS-X9148

181

24-port 4-Gbps switching module, DS-X9124

127

12-port 4-Gbps switching module, DS-X9112

107

4-port 10-Gbps switching module, DS-X9704

162

32-port 1-Gbps/2-Gbps Fibre Channel module, DS-X9032

174

16-port 1-Gbps/2-Gbps Fibre Channel module, DS-X9016

144

Cisco MDS 9000 Family 18/4 - port Multiservice module

199.8

MPS-14/2 module, DS-X9302-14K9

178

32-port SSM, DS-X9032-SSM

211

8-port IPS module, DS-X9308-SMIP

175

4-port IPS module, DS-X9304-SMIP

128

48-port 8-Gbps switching module, DS-X9248-96K9

230

24-port 8-Gbps switching module, DS-X9224-96K

221

4/44-port 8-Gbps Host-Optimized switching module,
DS-X9248-48K9

175

16-port Storage Services Node (DS-X9316-SSNK9)

257

Cisco MDS 9000 8-Port 10-Gbps FCoE module (DS-X9708-K9)

107

48-Port 8-Gbps Advanced Fibre Channel Switching module(DS-X9248-256K9)

267

32-Port 8-Gbps Advanced Fibre Channel Switching module(DS-X9232-256K9)

243

Supervisor-2A, DS-X9530-SF2A-K9

697


Transceiver Specifications

The Cisco MDS 9500 Series is compatible with X2, SFP, and SFP+ transceivers and cables that have SC and LC connectors. For more information, see the Cisco MDS 9000 Family Pluggable Transceivers data sheet at this URL: http://www.cisco.com/en/US/prod/collateral/ps4159/ps6409/ps4358/product_data_sheet09186a00801bc698.html .