The documentation set for this product strives to use bias-free language. For the purposes of this documentation set, bias-free is defined as language that does not imply discrimination based on age, disability, gender, racial identity, ethnic identity, sexual orientation, socioeconomic status, and intersectionality. Exceptions may be present in the documentation due to language that is hardcoded in the user interfaces of the product software, language used based on RFP documentation, or language that is used by a referenced third-party product. Learn more about how Cisco is using Inclusive Language.
This section provides the technical specification for the Cisco IE 2000U switches.
Table 15 lists the operating temperatures for the Cisco IE 2000U switches.
|
|
---|---|
Note: The safety certifications apply only to ambient temperatures under 140°F (60°C). However, the Cisco IE 2000U switch can function in the substation installations under the environmental conditions shown in Table 16.
Table 16 lists the technical specifications for the Cisco IE 2000U switches.
|
|
Operating temperature3 |
■-40°C to +70°C (Vented Enclosure Operating) ■-40°C to +60°C (Sealed Enclosure Operating) ■-34°C to +74°C (100LFM or more Fan or Blower equipped Enclosure Operating) ■-40°C to +85°C (Type Tested to +85°C for 16 hours) 4 |
Operating altitude5 |
|
|
|
■Maximum operating range: 9.6 to 60 VDC ■The DC-input power supply is an SELV circuit, and it can only be connected to another SELV circuit. ■IE 2000U-16TC-GP may require an additional power input connection to power the PoE ports. This connection requires 48/54 VDC @ 2.5.A. |
|
Note: Switch models with PoE capability require an additional power input connection to power the PoE ports. This connection requires 48/54 VDC @ 2.5 A. |
|
■6-port models—10 W (typical), 13 W (maximum) ■10-port models—14 W (typical), 18 W (maximum) ■20-port models—18 W (typical), 23 W (maximum) Note: Typical power consumption is with a 24 VDC input voltage at a 40°C (104°F) ambient temperature. Note: Maximum power consumption is the extreme level at any operational DC input voltage over the entire operating temperature range. |
|
|
|
■IE 2000U-4S-G: 2.45 lbs (1.11 kg) ■IE 2000U-4T-G: 2.45 lbs (1.11 kg) ■IE 2000U-4TS-G: 2.45 lbs (1.11 kg) ■IE 2000U-8TC-G: 3.45 lbs (1.57 kg) ■IE 2000U-16TC-G: 4.35 lbs (1.98 kg) |
|
5.10 x 2.95 x 4.29 in. (13.0 cm x 7.5 cm x 10.9 cm) Note: Depth is the distance from the rail; the depth including the rail is 4.51 in. (11.5 cm). |
|
5.1 x 3.6 x 5.04 in. (13.0 cm x 9.1 cm x 12.8 cm) Note: Depth is the distance from the rail; the depth including the rail is 5.26 in. (13.4 cm). |
|
5.1 x 5.0 x 5.04 in. (13.0 cm x 12.7 cm x 12.8 cm) Note: Depth is the distance from the rail; the depth including the rail is 5.26 in. (13.4 cm). |
|
Table 17 lists the alarm ratings for the Cisco IE 2000 switches.
|
|
---|---|
Table 18 lists the hazardous location standards for the Cisco IE 2000U switches.
|
|
---|---|
UL 60079-0, 5th Ed, 2009-10-21 |